Plan Review Notes
Plan Review Notes For Permit 20120098
Permit Number 20120098
Review Stop P
Sequence Number 1
Notes
Date Text
2020-12-28 18:43:0012/28/20 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. ON SHEET A0.0;
  
 A. THE INDEXED DRAWING IS MISSING P-2 PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 B. PLEASE PROVIDE UNDER CODES, THE YEAR, PLUMBING AND
 ACCESSIBILITY REFERENCED USED PER THE WPB AMENDMENTS TO
 THE FBC SEC. 101.4 REFERENCED CODES.
  
 2. ON SHEET P-1;
  
 A. PLEASE PROVIDE THE TOILET FACILITIES' LOCATION AND
 DISTANCE PER THE 2017 FBC SEC P 403.3.3 LOCATION OF
 TOILET FACILITIES.
  
 B. PLEASE PROVIDE THE DRINKING FOUNTAIN LOCATION AND
 DISTANCE PER THE 2017 FBC SEC P 403.5 DRINKING FOUNTAIN
 LOCATION.
  
 C. PLEASE SHOW HAMMER ARRESTOR( DISHWASHER AND FRIG) ON
 THE ISOMETRIC WATER DIAGRAM, INLINE VACUUM BREAKER FOR
 THE ICE MAKER ON FRIG( IF EQUIPPED WITH ONE) PER THE
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 D. THE THIRD NOTE DOWN IS NOT REQUIRED AS THIS IS A
 SINK. YOU MAY CHOOSE TO LEAVE IT ON THERE.
  
 E. THE FOURTH NOTE DOWN REFERS TO AN ASSE 1022 DEVICE
 ON THE SAME PAGE, BUT IT SHALL BE 1024 PER THE 2017 FBC
 SEC. 608.13.10.
  
 3. ON SHEET A-1.1, PLEASE SHOW THE CLEAR FLOOR SPACE
 DIAGRAM AND DIMENSIONS FOR THE KITCHEN BREAK ROOM PER
 THE 2017 FBC ACC SEC. 606.2. 2 CLEAR FLOOR SPACE.
  
 4. ON SHEET P-2;
  
 A. THE SINK DETAIL SHOWS A SINGLE VALVE ON THE SINK,
 AND IT SEVERS HOT AND COLD SHUT OFF. PLEASE SHOW EACH
 VALVE FOR EACH SEPARATE SOURCE OF WATER PER THE 2017
 FBC SEC. P 606.2 LOCATION OF SHUTOFF VALVES.
  
 B. PLEASE REMOVE ON THE PLUMBING SPECIFICATION ALL
 VERBIAGE THAT DOES NOT PERTAIN TO THIS CONSTRUCTION
 PROJECT PER THE AMENDMENTS TO THE FBC SEC. 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  