| 2020-12-14 14:48:47 | 1ST REVIEW FBC-2017 RES. FUEL GAS |
| | PERMIT- 20120096 |
| | 12/14/2020 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| | EDITION 2017 |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) PLEASE CLARIFY THE EXACT LOCATIONS OF THE NEW METER |
| | AND NEW GAS LINE. THE DRAWING APPEARS TO INDICATE THE |
| | METER IS FREESTANDING ON THE PROPERTY OR POSSIBLY |
| | INSTALLED ON A SITE WALL. THERE ARE NOTES INDICATING |
| | THE NEW GAS PIPING TO BE INSTALLED ON UNISTRUTS ALONG |
| | THE PROPERTY LINE WHICH IS ASSUMED TO BE ON THE BLOCK |
| | SITE WALL INSTALLED UNDER PERMIT- 07100359. PLEASE |
| | PROVIDE A COPY OF THE SURVEY MARKED UP TO SHOW THE |
| | INSTALLATION LOCATIONS. PLEASE NOTE THE SITE WALL IS |
| | INSTALLED IN A UTILITY EASEMENT, THEREFORE IF THE METER |
| | AND PIPING ARE TO BE INSTALLED ON THE WALL AN EASEMENT |
| | CONSENT FORM SHALL BE SUBMITTED WITH THE SURVEY- |
| | SECTION 107.2.1 WPB. THE EASEMENT CONSENT FORM CAN BE |
| | FOUND ON THE CITY OF WEST PALM BEACH WEBSITE. IF YOU |
| | NEED ASSISTANCE WITH OBTAINING THE FORM PLEASE EMAIL |
| | [email protected]. |
| | |
| | 2) PROVIDE A GAS RISER DRAWING- SECTION 107.3.5.3 WPB. |
| | THE RISER SHALL PROVIDE THE FOLLOWING INFORMATION: |
| | |
| | A) DELIVERY PRESSURE AT THE METER- SECTIONS G2413.1 FBC |
| | RES. |
| | |
| | B) TOTAL DEVELOPED LENGTH OF THE PIPING FROM THE METER |
| | TO THE MOST REMOTE GAS OUTLET- SECTION G2413.4.1. |
| | |
| | D) BRANCH AND CUT PIPING LENGTHS- SECTION G2413.4.2. |
| | PLEASE INCLUDE THE PIPING RUN TO THE EXISTING GAS RANGE |
| | THAT IS BEING REPLACED. |
| | |
| | E) INDIVIDUAL GAS LOADS AT OUTLETS AND TOTAL LOAD OF |
| | THE SYSTEM- SECTIONS G2412.3, G2412.4, & G2413.2 FBC |
| | RES. |
| | |
| | F) LOCATIONS OF REGULATORS AND OUTLET PRESSURES- |
| | SECTIONS G2421.1 & G2421.2. |
| | |
| | G) PIPE SIZING TABLES- SECTION G2413.3. |
| | |
| | 3) INDICATE A GAS-TIGHT CAP WILL BE PROVIDED FOR THE |
| | PIPING SUPPLYING THE FUTURE POOL HEATER- SECTION |
| | G2415.15 FBC RES. |
| | |
| | 4) THE CONTRACTOR OR QUALIFIER WHO PREPARED THE DRAWING |
| | SHALL PROVIDE HIS/HER PRINTED NAME AND SIGNATURE ON IT- |
| | SECTION 107.2.1 WPB, AND FLORIDA STATUTES 471.003(2)(H) |
| | & 471.025. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |