Plan Review Notes
Plan Review Notes For Permit 20120024
Permit Number 20120024
Review Stop P
Sequence Number 1
Notes
Date Text
2020-12-29 13:04:0312/29/20 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. ON SHEET S-1 ISOMETRIC;
  
 A. THE CABANA BATH TOILET NEEDS TO BE IN A BATHROOM
 GROUP, NOT ON THE TRUNK LINE THAT RUNS TO THE SECOND
 FLOOR PER THE 2017 FBC R 3109.1 WASTE STACK VENT
 PERMITTED.
  
 B. ON THE SECOND FLOOR, THE WASHING MACHINE NEEDS TO BE
 DOWN STEAM OF THE BATHROOM GROUP WHICH A THREE-INCH
 DRAIN AND A TWO-INCH DISCHARGE ON THE DRAIN ARM PER THE
 TABLE P3201.7 SIZE OF TRAPS FOR PLUMBING FIXTURES
  
 2. HOT WATER PIPES NOT IN CONDITION SPACE SHALL BE
 INSULATED WITH A MINIMUM R-3 PER THE 2017 FBC SEC. RE
 403.5.3.
  
 3. A SUB PLUMBING AND GAS PERMIT IS REQUIRED BY A
 LICENSED CONTRACTOR FOR THE SCOPE OF WORK PER THE WPB
 AMENDMENTS TO THE FBC SEC. 105.1.
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  