2020-12-29 16:17:10PLAN REVIEW / ELECTRICAL
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 2014 NEC
  
 1ST REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. INDICATE AIC RATING OF SERVICE EQUIPMENT.
 E3404.2INTERRUPTING RATING.
 EQUIPMENT INTENDED TO INTERRUPT CURRENT AT FAULT LEVELS
 SHALL HAVE A MINIMUM INTERRUPTING RATING OF 10,000
 AMPERES. EQUIPMENT INTENDED TO INTERRUPT CURRENT AT
 LEVELS OTHER THAN FAULT LEVELS SHALL HAVE AN
 INTERRUPTING RATING AT NOMINAL CIRCUIT VOLTAGE OF NOT
 LESS THAN THE CURRENT THAT MUST BE INTERRUPTED. (110.9)
  
 2. PROVIDE MAIN DISCONNECT.
 E3601.6.2SERVICE DISCONNECT LOCATION.
 THE SERVICE DISCONNECTING MEANS SHALL BE INSTALLED AT A
 READILY ACCESSIBLE LOCATION EITHER OUTSIDE OF A
 BUILDING OR INSIDE NEAREST THE POINT OF ENTRANCE OF THE
 SERVICE CONDUCTORS. SERVICE DISCONNECTING MEANS SHALL
 NOT BE INSTALLED IN BATHROOMS. EACH OCCUPANT SHALL HAVE
 ACCESS TO THE DISCONNECT SERVING THE DWELLING UNIT IN
 WHICH THEY RESIDE. [230.70(A)(1), 230.72(C)]
  
 3. SMOKE ALARMS.
 1104.1SMOKE ALARMS IN EXISTING PORTIONS OF A BUILDING.
 R314.2.2ALTERATIONS, REPAIRS AND ADDITIONS.
 WHERE ALTERATIONS, REPAIRS OR ADDITIONS REQUIRING A
 PERMIT OCCUR, OR WHERE ONE OR MORE SLEEPING ROOMS ARE
 ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL
 DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS
 LOCATED AS REQUIRED FOR NEW DWELLINGS.
  
 R314.3 LOCATION.
 SMOKE ALARMS SHALL BE INSTALLED IN THE FOLLOWING
 LOCATIONS:
 1. 1.IN EACH SLEEPING ROOM.
 2. 2.OUTSIDE EACH SEPARATE SLEEPING AREA IN THE
 IMMEDIATE VICINITY OF THE BEDROOMS.
 3. 3.ON EACH ADDITIONAL STORY OF THE DWELLING,
 INCLUDING BASEMENTS AND HABITABLE ATTICS AND NOT
 INCLUDING CRAWL SPACES AND UNINHABITABLE ATTICS. IN
 DWELLINGS OR DWELLING UNITS WITH SPLIT LEVELS AND
 WITHOUT AN INTERVENING DOOR BETWEEN THE ADJACENT
 LEVELS, A SMOKE ALARM INSTALLED ON THE UPPER LEVEL
 SHALL SUFFICE FOR THE ADJACENT LOWER LEVEL PROVIDED
 THAT THE LOWER LEVEL IS LESS THAN ONE FULL STORY BELOW
 THE UPPER LEVEL.
 4. 4.SMOKE ALARMS SHALL BE INSTALLED NOT LESS THAN 3
 FEET (914 MM) HORIZONTALLY FROM THE DOOR OR OPENING OF
 A BATHROOM THAT CONTAINS A BATHTUB OR SHOWER UNLESS
 THIS WOULD PREVENT PLACEMENT OF A SMOKE ALARM REQUIRED
 BY SECTION R314.3
  
 R314.4 INTERCONNECTION.
 WHERE MORE THAN ONE SMOKE ALARM IS REQUIRED TO BE
 INSTALLED WITHIN AN INDIVIDUAL DWELLING UNIT IN
 ACCORDANCE WITH SECTION R314.3, THE ALARM DEVICES SHALL
 BE INTERCONNECTED IN SUCH A MANNER THAT THE ACTUATION
 OF ONE ALARM WILL ACTIVATE ALL OF THE ALARMS IN THE
 INDIVIDUAL DWELLING UNIT. PHYSICAL INTERCONNECTION OF
 SMOKE ALARMS SHALL NOT BE REQUIRED WHERE LISTED
 WIRELESS ALARMS ARE INSTALLED AND ALL ALARMS SOUND UPON
 ACTIVATION OF ONE ALARM.
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  