| 2021-04-07 09:44:26 | WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION |
| | SERVICES/ BUILDING DIVISION |
| | 2017 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 20120003 |
| | ADD: 2400 S DIXIE HWY. |
| | CONT: BUTLER CONSTRUCTION |
| | TEL: 561-832-9700 |
| | E-MAIL: [email protected] |
| | |
| | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 3RD REVIEW |
| | DATE: WED. APRIL 07TH/2021 |
| | ACTION: BUILDING PROVISOS |
| | |
| | 1) BUILDING PROVISO: THE PROPOSED FLOOR PLAN SHOWS A |
| | NEW WALK IN COOLER / FREEZER. PLEASE NOTE WALK IN |
| | COOLERS REQUIRE A SEPARATE PERMIT, REVIEW AND |
| | ASSOCIATED FEES. THEY ARE ALSO PART OF THE COMPONENTS |
| | AND CLADDING OF THE BUILDING AND REQUIRE PRODUCT |
| | APPROVALS. 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA |
| | DEPARTMENT OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE |
| | 61G20-3.005, RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY |
| | OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE |
| | PRODUCT APPROVALS: (31)(G) EXTERIOR COOLER, FREEZERS. |
| | THE 602 SQ. FT. COOLERS WILL ALSO NEED TO SHOW |
| | COMPLIANCE WITH THE 2017 FBC-B SECTION 2603.4.1.2 AND |
| | 2603.4.1.3. |
| | |
| | 2) BUILDING PROVISO: WELDED OR BOLTED CONNECTIONS. THE |
| | CONTRACTOR IS REQUIRED TO PROVIDE WELD PROCEDURE |
| | SPECIFICATIONS & WELDER OPERATOR PERFORMANCE |
| | QUALIFICATION RECORDS IN ACCORDANCE WITH THE REFERENCED |
| | STANDARDS AT TIME OF INSPECTION FOR FIELD WIELDING, ON |
| | THE JOB-SITE WIELDING. THIRD PARTY CERTIFICATION WILL |
| | BE REQUIRED. REPORTS SUBMITTED TO BUILDING INSPECTOR AT |
| | TIME OF FRAMING INSPECTION. |
| | 2017 FBC-B 2204.1 WELDING |
| | 1. WELD PROCEDURES SPECIFICATIONS |
| | 2. QUALIFICATIONS OF WELDING PERSONAL |
| | 2017 FBC-B 2204.2 BOLTING. |
| | IF FURTHER CLARIFICATION AND OR QUESTIONS IS REQUIRED, |
| | PLEASE CONTACT THE CHIEF BUILDING INSPECTOR KEN CONRAD |
| | AT 561-805-6666. |
| | |
| | 3) BUILDING PROVISO/ DEFERRED SUBMITTALS: 2017 FBC-B |
| | 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.4.1 |
| | COMPONENTS & CLADDING. FLORIDA DEPARTMENT OF COMMUNITY |
| | AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3 |
| | NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR |
| | CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT |
| | APPROVALS: |
| | (31)(A) EXTERIOR DOORS, MULLIONS. |
| | (B) WINDOWS & MULLIONS |
| | (C) PANEL WALLS: STOREFRONTS, WALL LOUVERS. |
| | (D) ROOFING PRODUCTS AND ASSEMBLIES, LIGHTWEIGHT |
| | CONCRETE INSULATION, ROOF TOP CURBS |
| | (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C |
| | STANDS |
| | |
| | 4) W. P. B. 107.3.4. PRODUCT APPROVALS. THOSE PRODUCTS |
| | WHICH ARE REGULATED BY FLORIDA ADMINISTRATIVE CODE RULE |
| | 61G20 SHALL BE REVIEWED AND APPROVED IN WRITING (SHOP |
| | DRAWING STAMP OF APPROVAL) BY THE DESIGNER OF RECORD |
| | PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC. |
| | |
| | 5) BUILDING PROVISO/ DEFERRED SUBMITTALS: IDENTIFY |
| | GLAZING/ MULLIONS. PLEASE IDENTIFY ON THE PRODUCT |
| | APPROVAL BEFORE SUBMITTING TO DESIGNER OF RECORD AND |
| | BEFORE SUBMISSION TO THE BUILDING DEPARTMENT. FOR ALL |
| | PRODUCTS WITH GLAZING, PLEASE IDENTIFY THE OPENING |
| | WIDTH & HEIGHT, TYPE OF GLAZING, MULLION SIZE, LENGTH |
| | IF UNREINFORCED OR REINFORCED INFORMATION IF REQUIRED, |
| | ATTACHMENTS AND ASSOCIATE PRESSURES FOR EACH OPENING |
| | SIZE. 2017 FBC-B 1405.13.1 INSTALLATION. WINDOWS AND |
| | DOORS SHALL BE INSTALLED IN ACCORDANCE WITH APPROVED |
| | MANUFACTURERS INSTRUCTIONS. FASTENER SIZE AND SPACING |
| | SHALL BE PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE |
| | CALCULATED BASED ON MAXIMUM LOADS AND SPACING USED IN |
| | THE TESTS. |
| | |
| | 6) BUILDING PROVISO/ DEFERRED SUBMITTALS: THE ROOF TOP |
| | A/C STAND PRODUCT APPROVALS, TO BE REVIEWED BY THE |
| | DESIGNER OF RECORD. PLEASE IDENTIFY THE FOLLOWING |
| | REQUIREMENTS CALCULATING THE AREA (SIDE VIEW) OF THE |
| | ROOF TOP COMPRESSORS, CONFIGURATION ON STAND, THE MEAN |
| | ROOF HEIGHT OF THE STAND AND COMPRESSORS, WEIGHT, |
| | CIRCLED THE DESIGN PARAMETERS IN THE TABLES, ANCHORS |
| | AND UPLIFT VERSES MOMENT FOR THE UNIT TO THE STAND AND |
| | THE STAND TO THE ROOF. THE PRODUCT APPROVAL IS TO BE |
| | REVIEWED BY THE DESIGNER OF RECORD, APPROVED BEFORE |
| | SUBMISSION TO THE BUILDING DEPARTMENT. |
| | |
| | 7) BUILDING PROVISO/ DEFERRED SUBMITTALS: ROOF TOP & |
| | EQUIPMENT MAINTENANCE LADDER SHOP DRAWINGS TO BE |
| | SUBMITTED TO DESIGNER OF RECORD FOR REVIEW AND SHOP |
| | DRAWING STAMP OF APPROVAL BEFORE BEING SUBMITTED TO THE |
| | BUILDING DEPARTMENT. 2017 FBC-M 306.5 EQUIPMENT AND |
| | APPLIANCES ON ROOFS. |
| | |
| | JAMES A. WITMER BN, PX, SFP, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT |