| 2021-03-03 10:54:01 | WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION |
| | SERVICES/ BUILDING DIVISION |
| | 2017 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 20120003 |
| | ADD: 2400 S DIXIE HWY. |
| | CONT: BUTLER CONSTRUCTION |
| | TEL: 561-832-9700 |
| | E-MAIL: [email protected] |
| | |
| | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 2ND REVIEW |
| | DATE: WED. MARCH 03RD/2021 |
| | ACTION: DENIED |
| | |
| | 1-2) COMPLIED. |
| | |
| | 3) SHEET A101: |
| | 3A) COMPLIED. |
| | |
| | 3B) SEMI-COMPLIED. A NEW SHEET SHOWING THE BASEMENT |
| | STAIR, HANDRAIL AND ENCLOSURE. THE BASEMENT PORTION OF |
| | THE STAIRWAY IS AN OPEN STAIR, NO ENCLOSURE. EXIT |
| | ACCESS STAIRWAYS ARE ALLOWED IN THE 2017 FBC-B SECTION |
| | 1019.3. THE SUBMITTED PLAN DOES NOT SHOW A GUARDRAIL, |
| | IT WAS ASSUMED THERE WAS A WALL AND GUARDRAILS WERE NOT |
| | REQUIRED. GUARDRAILS MUST SHOW COMPLIANCE WITH THE 2017 |
| | FBC-B SECTIONS 1015.3 & 11015.4. |
| | |
| | 1ST ROUND OF COMMENTS. THERE IS NO INFORMATION ON THE |
| | STAIRWAY AND HANDRAILS IF THEY ARE EXISTING AND THE |
| | RISE / RUN OF THE STAIRS NOR IF THERE IS ANY HANDRAILS. |
| | SEE THE 2017 FBC-EXISTING BUILDING CODE SECTION |
| | 1012.4.2. |
| | |
| | 4) SHEET A102 THE PROPOSED 1ST FLOOR PLAN: |
| | 4A)2ND REQUEST. EGRESS DOORWAYS MUST SHOW THEY ARE |
| | ACCESSIBLE, THE INTERIOR AND EXTERIOR GRADE ARE IN |
| | COMPLIANCE WITH THE 2017 ACCESSIBILITY CODE SECTION |
| | 303.2 VERTICAL OR 303.3 BEVELED, CHANGE IN LEVEL GRADE. |
| | 1ST ROUND OF COMMENTS. THE PLANS DO NOT SHOW WHICH |
| | EGRESS DOORS ARE ACCESSIBLE EXITS. 2017 |
| | FBC-ACCESSIBILITY CODE SECTION 207.1 MEANS OF EGRESS |
| | SHALL COMPLY WITH SECTION 1003.2.13 OF THE |
| | INTERNATIONAL BUILDING CODE (2000 EDITION AND 2001 |
| | SUPPLEMENT) OR SECTION 1007 OF THE INTERNATIONAL |
| | BUILDING CODE (2003 EDITION). |
| | |
| | 2003 IBC-B 1007.1 WHERE MORE THAN ONE MEANS OF EGRESS |
| | IS REQUIRED BY SECTIONS 1014.1 OR 1018.1 FROM ANY |
| | ACCESSIBLE SPACE, EACH ACCESSIBLE PORTION OF THE SPACE |
| | SHALL BE SERVED BY NOT LESS THAN TWO MEANS OF EGRESS. |
| | |
| | 4B) SEE NOTE ABOVE 2ND REVIEW. THE PLANS DO NOT SHOW |
| | COMPLIANCE WITH SECTION 1007.1.1 OF THE 2017 FBC-B, TWO |
| | EXITS AND OR EXIT ACCESS DOORWAYS. |
| | WHERE 2 EXIT OR EXIT ACCESS DOORWAYS ARE REQUIRED FROM |
| | ANY PORTION OF THE EXIT ACCESS, THEY SHALL BE PLACED A |
| | DISTANCE APART EQUAL TO NOT LESS THAN ? THE OVERALL |
| | MAXIMUM OVERALL DIAGONAL DIMENSION OF THE BUILDING OR |
| | AREA TO BE SERVED MEASURED IN A STRAIGHT LINE BETWEEN |
| | THEM. |
| | EXCEPTION BUILDINGS EQUIPPED THROUGHOUT WITH AN |
| | AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE WITH SECTION |
| | 903.3.1.1 OR 903.3.1.2, THE SEPARATION DISTANCE SHALL |
| | NOT BE LESS THAN 1/3RD OVERALL DIAGONAL DIMENSION OF |
| | THE BUILDING OR AREA TO BE SERVED MEASURED IN A |
| | STRAIGHT LINE BETWEEN THEM. |
| | |
| | 4C)2ND REVIEW. SEE COMMENT 3B. |
| | 1ST ROUND OF COMMENTS. PLEASE REVIEW THE STAIRWAY THAT |
| | LEADS FORM THE BASEMENT. THE 2017 FBC-B SECTION 1019.3 |
| | WOULD REQUIRE THE STAIRWAY TO BE ENCLOSED WITH A SHAFT |
| | ENCLOSURE CONSTRUCTED IN ACCORDANCE WITH 713. DOORS |
| | WILL NEED TO SHOW COMPLIANCE WITH 713.7 & 716 FOR FIRE |
| | BARRIER. DOORS SHALL BE SELF OR AUTOMATIC CLOSING BY |
| | SMOKE DETECTION IN ACCORDANCE WITH 716.5.9.3. |
| | |
| | 4D) BUILDING PROVISO: THE PROPOSED FLOOR PLAN SHOWS A |
| | NEW 602 SQ. FT. WALK IN COOLER. PLEASE NOTE WALK IN |
| | COOLERS REQUIRE A SEPARATE PERMIT, REVIEW AND |
| | ASSOCIATED FEES. THEY ARE ALSO PART OF THE COMPONENTS |
| | AND CLADDING OF THE BUILDING AND REQUIRE PRODUCT |
| | APPROVALS. 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA |
| | DEPARTMENT OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE |
| | 61G20-3.005, RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY |
| | OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE |
| | PRODUCT APPROVALS: (31)(G) EXTERIOR COOLER, FREEZERS. |
| | THE 602 SQ. FT. COOLERS WILL ALSO NEED TO SHOW |
| | COMPLIANCE WITH THE 2017 FBC-B SECTION 2603.4.1.2 AND |
| | 2603.4.1.3. |
| | |
| | 4E) THE PLAN INDICATES THERE IS 110 INDOOR SEATS. THE |
| | FLOOR PLAN DOES NOT SHOW ANY ACCESSIBLE SEATING. PLEASE |
| | SHOW COMPLIANCE WITH THE FOLLOWING ACCESSIBILITY |
| | REQUIREMENTS: |
| | |
| | 4E)(1)SEMI-COMPLIED. 226.1 WHERE DINING SURFACES ARE |
| | PROVIDED FOR THE CONSUMPTION OF FOOD OR DRINK, AT LEAST |
| | 5 PERCENT OF THE SEATING SPACES AND STANDING SPACES AT |
| | THE DINING SURFACES SHALL COMPLY WITH 902. |
| | 110X0.05= 6 ACCESSIBLE SEATS. THE PROBLEM IS THE BAR |
| | AREA SEATING. |
| | |
| | 4E)(2) SEMI-COMPLIED. THE PROBLEM IS THE BAR AREA |
| | SEATING. 226.2 DISPERSION. DINING SURFACES AND WORK |
| | SURFACES REQUIRED TO COMPLY WITH 902 SHALL BE DISPERSED |
| | THROUGHOUT THE SPACE OR FACILITY CONTAINING DINING |
| | SURFACES AND WORK SURFACES. |
| | |
| | 4E)(3) SEMI-COMPLIED, THE PROBLEM IS THE BAR AREA |
| | SEATING. 206.2.5 206.2.5 RESTAURANTS AND CAFETERIAS. IN |
| | RESTAURANTS AND CAFETERIAS, AN ACCESSIBLE ROUTE SHALL |
| | BE PROVIDED TO ALL DINING AREAS, INCLUDING RAISED OR |
| | SUNKEN DINING AREAS, AND OUTDOOR DINING AREAS. |
| | |
| | 4E)(4) SEMI-COMPLIED, THE PROBLEM IS THE BAR AREA |
| | SEATING. 902.1 .DINING SURFACES AND WORK SURFACES SHALL |
| | COMPLY WITH 902.2 AND 902.3. ADVISORY 902.1 GENERAL. |
| | DINING SURFACES INCLUDE, BUT ARE NOT LIMITED TO, BARS, |
| | TABLES, LUNCH COUNTERS, AND BOOTHS. |
| | |
| | 4E)(5)(1) COMPLIED. 902.2 CLEAR FLOOR OR GROUND SPACE. |
| | A CLEAR FLOOR SPACE COMPLYING WITH 305 POSITIONED FOR A |
| | FORWARD APPROACH SHALL BE PROVIDED. KNEE AND TOE |
| | CLEARANCE COMPLYING WITH 306 SHALL BE PROVIDED. |
| | |
| | 4E)(5)(2) SEMI-COMPLIED ,THE PROBLEM AREA IS THE BAR |
| | AREA SEATING. PLEASE PROVIDE A CUT SECTION THROUGH THE |
| | ACCESSIBLE SEATING AREA AT THE BAR TO SHOW COMPLIANCE |
| | WITH 902.3 HEIGHT. THE TOPS OF DINING SURFACES AND WORK |
| | SURFACES SHALL BE 28 INCHES MINIMUM AND 34 INCHES |
| | MAXIMUM ABOVE THE FINISH FLOOR OR GROUND. |
| | |
| | 4F) 2ND REQUEST, THE DESIGNER OF RECORD SHOW THE |
| | MANEUVERING CLEARANCES ON THE WRONG SIDE OF THE DOOR. |
| | PLEASE LOOK AT DOORS 12 & 13 MISSING MANEUVERING |
| | CLEARANCES AT DOORS. ACCESS. CODE 404.2.4 MANEUVERING |
| | CLEARANCES. DOORS. |
| | MINIMUM MANEUVERING CLEARANCES AT DOORS AND GATES SHALL |
| | COMPLY WITH 404.2.4. MANEUVERING CLEARANCES SHALL |
| | EXTEND THE FULL WIDTH OF THE DOORWAY AND THE REQUIRED |
| | LATCH SIDE FOR SIDE CLEARANCE. |
| | |
| | 4G) COMPLIED. |
| | |
| | 5) SHEET A104 ENLARGES RESTROOM FLOOR PLAN & |
| | ELEVATIONS: |
| | 5A) 2ND REQUEST. PLEASE BE AWARE ONE NOTE WAS ADDED |
| | CERAMIC TILE WAINSCOT WAS ADDED FOR ALL ELEVATIONS. THE |
| | HEIGHT OF THE WAINSCOT IS NOT GIVEN AND IN THE FINISH |
| | SCHEDULE THE WALL SCHEDULE STILL STATES TO PAINT THE |
| | DRYWALL WALLS. |
| | 1ST ROUND COMMENT. THERE IS NO FINISHES SHEET FOR |
| | FLOORS, WALLS & CEILINGS. SHEET A104 IN THE SOUTH |
| | ELEVATION OF THE MENS RESTROOM STATES LINE OF SMOOTH, |
| | HARD, NONABSORBENT SURFACES ABOVE THE FLOOR. 2017 FBC-B |
| | 1210.2.2. WALLS & PARTITIONS. THIS COMMENT IS A RESULT |
| | OF THE BUILDING OFFICIAL INTERPRETATION. IN RESTROOMS |
| | EPOXY PAINT IS NO LONGER CONSIDERED A SMOOTH HARD, |
| | NON-ABSORBENT SURFACE. |
| | |
| | 5A)(1) SEMI-COMPLIED. 1210.2.2 WALLS & PARTITIONS |
| | WITHIN 2 FEET OF SERVICE SINKS, URINALS, AND WATER |
| | CLOSETS SHALL HAVE A SMOOTH, HARD, NON-ABSORBENT |
| | SURFACE TO A HEIGHT OF NOT LESS THAN 4 FEET ABOVE THE |
| | FLOOR, EXCEPT FOR STRUCTURAL ELEMENTS, THE MATERIAL |
| | USED IN SUCH WALLS SHALL BE OF A TYPE THAT IS NOT |
| | ADVERSELY AFFECTED BY MOISTURE. |
| | |
| | 5B) COMPLIED. LOCATION OF THE BABY CHANGING TABLE. |
| | |
| | 5C) 2ND ROUND OF COMMENTS. THE PLANS SHOW THE 40 INCHES |
| | TO THE BOTTOM OF THE MIRROR, NOT THE REFLECTIVE |
| | SURFACE. |
| | 1ST ROUND OF COMMENTS. IN BOTH THE MENS AND WOMENS |
| | RESTROOMS THE HEIGHT ABOVE THE FLOOR IS NOT GIVEN, SHOW |
| | COMPLIANCE WITH 603.3 MIRRORS. 2017 FBC-ACCESSIBILITY |
| | CODE. MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS |
| | SHALL BE INSTALLED WITH THE BOTTOM EDGE OF THE |
| | REFLECTING SURFACE 40 INCHES MAXIMUM ABOVE THE FINISH |
| | FLOOR OR GROUND. |
| | |
| | 5D-F) COMPLIED. |
| | |
| | 5G) 2ND ROUND OF COMMENTS. ALL PARTS OF 5G. TO ANSWER |
| | CODE REQUIREMENTS YOU CAN NOT RECITE THE CODE. 2017 |
| | WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| | CODE, CHAPTER 1, ADMINISTRATION 107.2.1. W.P.B. |
| | ADMINISTRATIVE CODE/2017 DRAWINGS & SPECIFICATIONS |
| | SHALL CONTAIN INFORMATION, IN THE FORM OF NOTES OR |
| | OTHERWISE, AS TO THE QUALITY OF MATERIALS, WHERE |
| | QUALITY IS ESSENTIAL TO CONFORMITY WITH THE TECHNICAL |
| | CODES. SUCH INFORMATION SHALL BE SPECIFIC TO THE |
| | TECHNICAL CODES "CODE SECTIONS SHALL NOT BE CITED AS A |
| | WHOLE OR IN PART, NOR THE TERM "LEGAL" OR ITS |
| | EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC |
| | INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE |
| | SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND |
| | EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT |
| | WILL CONFORM TO THE PROVISIONS OF THIS CODE AND |
| | RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS |
| | DETERMINED BY THE BUILDING OFFICIAL. |
| | |
| | 1ST ROUND OF COMMENTS. WHAT DETAILS FOR ACCESSIBILITY |
| | WERE NOT PROVIDED AND OR EXCEPTION ARE FOR DRINKING |
| | FOUNTAINS. |
| | 5G)(1) 602.2 CLEAR FLOOR SPACE. A CLEAR FLOOR SPACE |
| | COMPLYING WITH 305, POSITIONED FOR A FORWARD APPROACH, |
| | AND KNEE AND TOE CLEARANCE COMPLYING WITH 306 SHALL BE |
| | PROVIDED. |
| | |
| | 5G)(2) SPOUT OUTLETS/ DRINKING FOUNTAINS. 2017 ACCESS. |
| | CODE. SPOUT OUTLETS SHALL COMPLY WITH: |
| | 602.4 SPOUT HEIGHT. 36 INCHES MAXIMUM ABOVE THE FINISH |
| | FLOOR OR GROUND FOR WHEELCHAIR BOUND INDIVIDUALS. |
| | 602.7 SPOUT HEIGHT FOR THE STANDING PERSONS SHALL BE |
| | BETWEEN 38 TO 43 INCHES ABOVE FINISH FLOOR. |
| | |
| | 5G)(3) PROTRUDING OBJECTS 307.2 PROTRUSION LIMITS |
| | 307.2. OBJECTS WITH LEADING EDGES MORE THAN 27 INCHES |
| | AND NOT MORE THAN 80 INCHES ABOVE THE FLOOR SHALL NOT |
| | PROTRUDE MORE THAN 4 INCHES HORIZONTALLY INTO THE |
| | CIRCULATION PATH. |
| | |
| | 6) COMPLIED. |
| | |
| | 7) THE COMPONENT AND CLADDING PRESSURES FOUND ON S302 |
| | FOR THE ROOF AND WALL ZONES ARE GIVEN IN VASD. THANK |
| | YOU. THE WALL PRESSURES ARE UP TO 9.0 LBS. LOW PER PSF. |
| | WE ARE TAKING THE PRESSURES FROM AN ENGINEERS SPREAD |
| | SHEET FOR WALL COMPONENTS & CLADDING AND COMPARING TO |
| | ASCE 7-10 FIGURE 30.5.1, AS WELL AS THE PRESSURES FOUND |
| | IN THE 2017 RESIDENTIAL CODE THE SIMPLIFIED TABLE |
| | R301.2(2). |
| | |
| | 8) BUILDING PROVISO: WELDED OR BOLTED CONNECTIONS. THE |
| | CONTRACTOR IS REQUIRED TO PROVIDE WELD PROCEDURE |
| | SPECIFICATIONS & WELDER OPERATOR PERFORMANCE |
| | QUALIFICATION RECORDS IN ACCORDANCE WITH THE REFERENCED |
| | STANDARDS AT TIME OF INSPECTION FOR FIELD WIELDING, ON |
| | THE JOB-SITE WIELDING. THIRD PARTY CERTIFICATION WILL |
| | BE REQUIRED. REPORTS SUBMITTED TO BUILDING INSPECTOR AT |
| | TIME OF FRAMING INSPECTION. |
| | 2017 FBC-B 2204.1 WELDING |
| | 1. WELD PROCEDURES SPECIFICATIONS |
| | 2. QUALIFICATIONS OF WELDING PERSONAL |
| | 2017 FBC-B 2204.2 BOLTING. |
| | IF FURTHER CLARIFICATION AND OR QUESTIONS IS REQUIRED, |
| | PLEASE CONTACT THE CHIEF BUILDING INSPECTOR KEN CONRAD |
| | AT 561-805-6666. |
| | |
| | 9) BUILDING PROVISO/ DEFERRED SUBMITTALS: 2017 FBC-B |
| | 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.4.1 |
| | COMPONENTS & CLADDING. FLORIDA DEPARTMENT OF COMMUNITY |
| | AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3 |
| | NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR |
| | CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT |
| | APPROVALS: |
| | (31)(A) EXTERIOR DOORS, MULLIONS. |
| | (B) WINDOWS & MULLIONS |
| | (C) PANEL WALLS: STOREFRONTS, WALL LOUVERS. |
| | (D) ROOFING PRODUCTS AND ASSEMBLIES, LIGHTWEIGHT |
| | CONCRETE INSULATION, ROOF TOP CURBS |
| | (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C |
| | STANDS |
| | |
| | 10) W. P. B. 107.3.4. PRODUCT APPROVALS. THOSE PRODUCTS |
| | WHICH ARE REGULATED BY FLORIDA ADMINISTRATIVE CODE RULE |
| | 61G20 SHALL BE REVIEWED AND APPROVED IN WRITING (SHOP |
| | DRAWING STAMP OF APPROVAL) BY THE DESIGNER OF RECORD |
| | PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC. |
| | |
| | 11) BUILDING PROVISO/ DEFERRED SUBMITTALS: IDENTIFY |
| | GLAZING/ MULLIONS. PLEASE IDENTIFY ON THE PRODUCT |
| | APPROVAL BEFORE SUBMITTING TO DESIGNER OF RECORD AND |
| | BEFORE SUBMISSION TO THE BUILDING DEPARTMENT. FOR ALL |
| | PRODUCTS WITH GLAZING, PLEASE IDENTIFY THE OPENING |
| | WIDTH & HEIGHT, TYPE OF GLAZING, MULLION SIZE, LENGTH |
| | IF UNREINFORCED OR REINFORCED INFORMATION IF REQUIRED, |
| | ATTACHMENTS AND ASSOCIATE PRESSURES FOR EACH OPENING |
| | SIZE. 2017 FBC-B 1405.13.1 INSTALLATION. WINDOWS AND |
| | DOORS SHALL BE INSTALLED IN ACCORDANCE WITH APPROVED |
| | MANUFACTURERS INSTRUCTIONS. FASTENER SIZE AND SPACING |
| | SHALL BE PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE |
| | CALCULATED BASED ON MAXIMUM LOADS AND SPACING USED IN |
| | THE TESTS. |
| | |
| | 12) BUILDING PROVISO/ DEFERRED SUBMITTALS: THE ROOF TOP |
| | A/C STAND PRODUCT APPROVALS, TO BE REVIEWED BY THE |
| | DESIGNER OF RECORD. PLEASE IDENTIFY THE FOLLOWING |
| | REQUIREMENTS CALCULATING THE AREA (SIDE VIEW) OF THE |
| | ROOF TOP COMPRESSORS, CONFIGURATION ON STAND, THE MEAN |
| | ROOF HEIGHT OF THE STAND AND COMPRESSORS, WEIGHT, |
| | CIRCLED THE DESIGN PARAMETERS IN THE TABLES, ANCHORS |
| | AND UPLIFT VERSES MOMENT FOR THE UNIT TO THE STAND AND |
| | THE STAND TO THE ROOF. THE PRODUCT APPROVAL IS TO BE |
| | REVIEWED BY THE DESIGNER OF RECORD, APPROVED BEFORE |
| | SUBMISSION TO THE BUILDING DEPARTMENT. |
| | |
| | 13) 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF |
| | THIS SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE |
| | PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE |
| | TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO |
| | THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD. |
| | DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR |
| | APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED |
| | DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST |
| | THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS |
| | FOR REVIEW BY THE BUILDING OFFICIAL. |
| | DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE |
| | SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN |
| | RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD |
| | THEM TO THE BUILDING OFFICIAL WITH A NOTATION |
| | INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE |
| | BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO |
| | THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL |
| | ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED |
| | SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING |
| | OFFICIAL. |
| | |
| | 14) BUILDING PROVISO/ DEFERRED SUBMITTALS: ROOF TOP & |
| | EQUIPMENT MAINTENANCE LADDER SHOP DRAWINGS TO BE |
| | SUBMITTED TO DESIGNER OF RECORD FOR REVIEW AND SHOP |
| | DRAWING STAMP OF APPROVAL BEFORE BEING SUBMITTED TO THE |
| | BUILDING DEPARTMENT. 2017 FBC-M 306.5 EQUIPMENT AND |
| | APPLIANCES ON ROOFS. |
| | |
| | 15) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | |
| | PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID |
| | 19 |
| | IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS |
| | 561-718-9724. |
| | WORKING HOURS ARE MON.- WED. 8:00 AM- NOON. PART-TIME/ |
| | RETIRED. |