| 2020-12-04 15:45:25 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | 1) THERE DOES NOT APPEAR TO BE A LIFE SAFETY PLAN. AS |
| | THIS IS AN ASSEMBLY OCCUPANCY, A LIFE SAFETY PLAN IS |
| | REQUIRED. |
| | |
| | PER NFPA 101, CH 12 12.4.1.4.3 LIFE SAFETY FLOOR PLANS. |
| | LIFE SAFETY FLOOR PLANS OF EACH |
| | LEVEL SHALL BE PROVIDED ? AS APPLICABLE ? WITH THE |
| | FOLLOWING: |
| | (1) OCCUPANT LOAD, EXIT LOCATION, EGRESS CAPACITY, MAIN |
| | ENTRANCE/EXIT, HORIZONTAL EXITS, TRAVEL DISTANCE, AND |
| | EXIT |
| | DISCHARGE |
| | |
| | PLEASE PROVIDE DETAILS |
| | |
| | |
| | 2) THERE IS A BASEMENT INDICATED AND AS THIS IS A NEW |
| | ASSEMBLY/CHANGE OF OCCUPANCY AND THE BASEMENT HAS WALLS |
| | AND STORAGE FIRE SPRINKLER PROTECTION IS REQUIRED. |
| | |
| | SEE FL BUILDING CODE 903.2.11.1.3 |
| | |
| | PLEASE REVIEW AND CORRECT OR PROVIDE APPLICABLE CODE |
| | REFERNCES AND DETAILED NARRATIVE. |
| | |
| | |
| | |
| | 3) THERE IS STORAGE INDICATED IN THE BASEMENT. AS THIS |
| | IS RESTURAUNT WITH POSSIBLE AEROSOL PRODUCTS, PLEASE |
| | PROVIDE IN COMPLAINCE WITH THE BELOW CODE. |
| | |
| | PER NFPA 1 |
| | |
| | 61.3.4.2 FIRE PROTECTION ? BASIC REQUIREMENTS. |
| | 61.3.4.2.1 STORAGE OF LEVEL 2 AND LEVEL 3 AEROSOL |
| | PRODUCTS SHALL |
| | NOT BE PERMITTED IN BASEMENT AREAS OF WAREHOUSES. [30B: |
| | 6.4.2.1] |
| | 61.3.4.2.1.1 STORAGE OF LEVEL 2 AND LEVEL 3 AEROSOL |
| | PRODUCTS SHALL |
| | BE PERMITTED AS PROVIDED FOR IN 6.3.3 OF NFPA 30B. |
| | [30B: |
| | 6.4.2.1.1] |
| | |
| | PLEASE PROVIDE DETAILS. |
| | |
| | |
| | |
| | 4) THE IS A STAIRWELL LEADING DOWN INTO THE BASEMENT |
| | THAT MAY BE CONFUSED AS AN EXIT. |
| | |
| | PER NFPA 101, CH 7 MEANS OF EGRESS |
| | |
| | 7.10.8.3* NO EXIT. |
| | 7.10.8.3.1 ANY DOOR, PASSAGE, OR STAIRWAY THAT IS |
| | NEITHER AN EXIT NOR A |
| | WAY OF EXIT ACCESS AND THAT IS LOCATED OR ARRANGED SO |
| | THAT IT IS LIKELY TO |
| | BE MISTAKEN FOR AN EXIT SHALL BE IDENTIFIED BY A SIGN |
| | THAT READS AS |
| | FOLLOWS: |
| | NO |
| | EXIT |
| | |
| | A.7.10.8.3 THE LIKELIHOOD OF OCCUPANTS MISTAKING |
| | PASSAGEWAYS |
| | OR STAIRWAYS THAT LEAD TO DEAD-END SPACES FOR EXIT |
| | DOORS |
| | AND BECOMING TRAPPED GOVERNS THE NEED FOR EXIT SIGNS. |
| | THUS, |
| | SUCH AREAS SHOULD BE MARKED WITH A SIGN THAT READS AS |
| | FOLLOWS: |
| | NO EXIT |
| | SUPPLEMENTARY IDENTIFICATION INDICATING THE CHARACTER |
| | OF |
| | THE AREA, SUCH AS TO BASEMENT, STOREROOM, LINEN |
| | CLOSET, OR THE LIKE, IS PERMITTED TO BE PROVIDED. |
| | |
| | PLEASE CORRECT AND PROVIDE FOR THE APPLICABLE SIGNANGE. |
| | |
| | |
| | 5) THERE ARE INDICATIONS OF OUTDOOR SMOKERS. AS THIS IS |
| | LOCATED CLOSE TO RESIDENTIAL HOMES PLEASE PROVIDE HOW |
| | THE SMOKE FROM THESE SMOKERS WILL BE CONTROLLED. |
| | |
| | PLEASE PROVIDE DETAILS. |
| | |
| | |
| | 6) SHEET A 102 - THERE IS AN INDICATION OF WALK-IN |
| | COOLERS WITH NO DETAIL |
| | |
| | PLEASE PROVIDE SPECIFIC DETAILS OF THESE COOLERS, |
| | INCLUDING EXACT CONFIGURATION, DOORS, LIGHTING, EXITS, |
| | EXIT HARDWARE. |
| | |
| | |
| | 7) SHEET E 2.1 - THERE ARE INDICATION OF AN EXT SIGNS |
| | OVER DOORS 12 & 13 THAT LEAD TO THE OUTDOOR ENCLOSED |
| | SMOKER AREA. |
| | |
| | THERE IS ONE INSWING DOOR FROM THAT AREA. THE DOES NOT |
| | APPEAR TO BE ANY EXIT SIGNAGE OVER THIS DOOR AND IT |
| | NEEDS TO SWING IN PATH OF EXIT TRAVEL AND BE EQUIPPED |
| | WITH EXIT HARDWARE. |
| | |
| | ADDITIONALLY, THE EXIT PATH IS REQUIRED TO BE |
| | ILLUMINATED. |
| | |
| | PLEASE REVIW AND CORRECT. |
| | |
| | |
| | 8) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | 9) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |