| 2020-12-08 16:40:02 | 1ST REVIEW FBC-2017 PLUMBING |
| | PERMIT-2012003 |
| | 12/10/2020 |
| | CODES IN EFFECT: |
| | |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) A MINIMUM OF TWO DRINKING FOUNTAINS ARE REQUIRED PER |
| | FBCACCESS. SEC. 211.2 & FBC-PLUMBING SEC. 410.3. |
| | 2) BAR AREA SHALL HAVE AN ACCESSIBLE TOP ELEVATION AS |
| | PER FBC 2017 A 902.1 A902.2 A902.3 |
| | 3) PLEASE PROVIDE THE USE AND OCCUPANCY FOR THIS |
| | INTERIOR BUILD-OUT WILL BE. PREVIOUS CITY RECORD |
| | INDICATES THAT THIS WAS A A3 GYM AND IT APEARS THIS IS |
| | GOING TO BE A A2. THIS INFORMATION NEEDS TO BE ON THE |
| | PLANS. WPB AMENDMENTS TO THE FBC SEC. 107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | 4) A SEPARATE PERMIT WILL BE REQUIRED FOR THE BACKFLOW |
| | PREVENTER. MANUFACTURER'S SPECIFICATIONS AND A SEPARATE |
| | PLUMBING PERMIT SHALL BE SUBMITTED PRIOR TO THE |
| | INSTALLATION OF THE DEVICE. THE DEVICES MUST BE |
| | INSTALLED BY A LICENSED PLUMBING |
| | CONTRACTOR.F.S.489.103. |
| | 5) A SEPARATE PERMIT WILL BE REQUIRED FOR THE GREASE |
| | INTERCEPTOR. MANUFACTURER'S SPECIFICATIONS & DETAILS |
| | AND FACTORY SIZING CALCULATIONS WILL BE REQUIRED TO BE |
| | SUBMITTED PRIOR TO ISSUANCE OF THE INTERCEPTOR PERMIT. |
| | 6) A SEPARATE PERMIT WILL BE REQUIRED FOR THE GAS. |
| | 7) BACKLOW PREVENTERS ARE REQUIRED AT THE ICE MAKER, |
| | COFFEE, CARBONATED SODA, CAN WASH, DISHWASHER AND SHALL |
| | BE INDICATED ON P0.4 |
| | 8) ON P0.3 CIRCUIT VENT REQUIRED BEFORE THE LAST WATER |
| | CLOSET AND BEFORE THE FLOOR DRAIN. |
| | 9) PROVIDE THE DISTANCES FOR DRAIN S3 AND FS FROM POINT |
| | OF VENT, IT MAY BE NECISSARY TO ADD A VENT ON THE DRAIN |
| | MARKED S3 |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |