2021-05-25 15:08:50ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 PANEL IN LIVING ROOM LOOKS TO BE IN A CLOSET.
 OVERCURRENT PROTECTION DEVICES ARE NOT PERMITTED IN THE
 VICINITY OF EASILY IGNITABLE MATERIAL, SUCH AS IN
 CLOTHES CLOSETS. PROVIDE CLARIFICATION AND/OR
 CORRECTION. NEC 240.24(D);
  
 ISLAND NEEDS AN OUTLET PER CODE.
 ISLAND COUNTERTOP SPACES. AT LEAST ONE RECEPTACLE SHALL
 BE INSTALLED AT EACH ISLAND COUNTERTOP SPACE WITH A
 LONG DIMENSION OF 600 MM (24 IN.) OR GREATER AND A
 SHORT DIMENSION OF 300 MM (12 IN.) OR GREATER
  
 SMOKE ALARMS ARE SHOWN TO CLOSE TO THE BATHROOM DOOR.
 SMOKE ALARM IS SHOWN TO CLOSE TO STOVE PLEASE CORRECT
 PER FBC R314.
  
 ARC FAULT PROTECTION REQUIRED PER 210.12(B)
  
  