| Plan Review Notes For Permit 20111182 |
| Permit Number |
20111182 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2021-05-25 15:08:50 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | FLORIDA BUILDING CODE 2020 7TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED | | | NFPA 70 2017 EDITION | | | | | | JAKE LEAHY BN, BU, PX | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | PANEL IN LIVING ROOM LOOKS TO BE IN A CLOSET. | | | OVERCURRENT PROTECTION DEVICES ARE NOT PERMITTED IN THE | | | VICINITY OF EASILY IGNITABLE MATERIAL, SUCH AS IN | | | CLOTHES CLOSETS. PROVIDE CLARIFICATION AND/OR | | | CORRECTION. NEC 240.24(D); | | | | | | ISLAND NEEDS AN OUTLET PER CODE. | | | ISLAND COUNTERTOP SPACES. AT LEAST ONE RECEPTACLE SHALL | | | BE INSTALLED AT EACH ISLAND COUNTERTOP SPACE WITH A | | | LONG DIMENSION OF 600 MM (24 IN.) OR GREATER AND A | | | SHORT DIMENSION OF 300 MM (12 IN.) OR GREATER | | | | | | SMOKE ALARMS ARE SHOWN TO CLOSE TO THE BATHROOM DOOR. | | | SMOKE ALARM IS SHOWN TO CLOSE TO STOVE PLEASE CORRECT | | | PER FBC R314. | | | | | | ARC FAULT PROTECTION REQUIRED PER 210.12(B) | | | | | | |
|