| Plan Review Notes For Permit 20111127 |
| Permit Number |
20111127 |
|
| Review Stop |
G |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2020-12-08 10:44:54 | 1ST REVIEW FBC-2017 RES. FUEL GAS | | | PERMIT- 20111127 | | | 12/8/2020 | | | | | | CODES IN EFFECT: | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH | | | EDITION 2017 | | | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 | | | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 | | | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | | 2017 | | | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 | | | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | | EDITION 2017 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) GAS RISER: A MINIMUM 1 IN. RISER PIPE IS REQUIRED AT | | | THE METER PRIOR TO THE FIRST TEE BASED ON THE GAS LOAD | | | OF 1,123,200 BTU LOAD AT 120 FT. TOTAL RUN LENGTH- SEE | | | TABLES G2413.4(2) [402.4(5)] FOR SCHEDULE 40 GALVANIZED | | | PIPE, AND TABLE G2413.4(8) [402.4(22)] FOR PE PIPE. | | | | | | 2) THE GENERATOR SPECS SUBMITTED UNDER PERMIT 20110839 | | | INDICATE 359,000 BTU LOAD FOR THE 27 KW GENERATOR. | | | PLEASE CORRECT THE LOADS ON THE RISER- SECTION 107.2.1 | | | WPB. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|