| Plan Review Notes For Permit 20111112 |
| Permit Number |
20111112 |
|
| Review Stop |
P |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2021-03-09 08:25:19 | 1) SHT. P3.2 - THE REQUIRED RECIRCULATION LINE ON THE | | | WATER SYSTEM RISER IS NOT CLEAR ON THE WATER RISER. THE | | | WATER RISER SHOWS WHAT IS SUPPOSED TO BE THE 1/2 INCH | | | HOT WATER RETURN LINE AT THE WATER HEATER SUPPLYING HOT | | | WATER TO THE FIXTURES AND ALSO SUPPLYING A 3/4 INCH, 1 | | | INCH AND AN 1 1/4 INCH HOT WATER LINE. THE RECIRCUATION | | | LINE ON THE WATER RISER IS SUPPLYING HOT WATER TO THE | | | FIXTURES IN ONE HALF OF THE BUILDING. COMPLY WITH | | | FBC-PLUMBING SEC.607.2.1 & FBC-ENERGY SEC. C404.6, | | | C404.6.1. THE SYSTEM RETURN PIPE SHALL BE A DEDICATED | | | RETURN PIPE OR A COLD WATER SUPPLY PIPE . AS DESIGNED, | | | I DO NOT SEE HOW THE PRESENT SYSTEM COMPLIES. CLARIFY. | | | 2ND REQUEST. | | | 2) SHT. A5.03 DETAIL #9 - PLACE A NOTE ON THE PLAN THAT | | | THE THRESHOLD WILL NOT EXCEED 1/2 INCH IN HEIGHT PER | | | FBC-ACCESS. SEC. 404.2.5 AND WILL COMPLY WITH | | | SEC.303.3. THE NOTE WAS PLACED ON DETAIL #10 WHICH IS | | | THE SHOWER DETAIL. MY PREVIOUS REVIEW REQUESTED THE | | | NOTE TO BE PLACED ON DETAIL #9. 2ND REQUEST. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | | | | |
|