Plan Review Notes
Plan Review Notes For Permit 20111112
Permit Number 20111112
Review Stop P
Sequence Number 3
Notes
Date Text
2021-03-09 08:25:191) SHT. P3.2 - THE REQUIRED RECIRCULATION LINE ON THE
 WATER SYSTEM RISER IS NOT CLEAR ON THE WATER RISER. THE
 WATER RISER SHOWS WHAT IS SUPPOSED TO BE THE 1/2 INCH
 HOT WATER RETURN LINE AT THE WATER HEATER SUPPLYING HOT
 WATER TO THE FIXTURES AND ALSO SUPPLYING A 3/4 INCH, 1
 INCH AND AN 1 1/4 INCH HOT WATER LINE. THE RECIRCUATION
 LINE ON THE WATER RISER IS SUPPLYING HOT WATER TO THE
 FIXTURES IN ONE HALF OF THE BUILDING. COMPLY WITH
 FBC-PLUMBING SEC.607.2.1 & FBC-ENERGY SEC. C404.6,
 C404.6.1. THE SYSTEM RETURN PIPE SHALL BE A DEDICATED
 RETURN PIPE OR A COLD WATER SUPPLY PIPE . AS DESIGNED,
 I DO NOT SEE HOW THE PRESENT SYSTEM COMPLIES. CLARIFY.
 2ND REQUEST.
 2) SHT. A5.03 DETAIL #9 - PLACE A NOTE ON THE PLAN THAT
 THE THRESHOLD WILL NOT EXCEED 1/2 INCH IN HEIGHT PER
 FBC-ACCESS. SEC. 404.2.5 AND WILL COMPLY WITH
 SEC.303.3. THE NOTE WAS PLACED ON DETAIL #10 WHICH IS
 THE SHOWER DETAIL. MY PREVIOUS REVIEW REQUESTED THE
 NOTE TO BE PLACED ON DETAIL #9. 2ND REQUEST.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  