| Date |
Text |
| 2021-02-23 07:18:10 | 1) SHT. A5.03 - FIXTURE MOUNTING DIAGRAM - THIS DIAGRAM |
| | STILL SHOWS THE GRAB BARS AT THE WATER CLOSETS BEING |
| | MEASURED TO THE CENTERLINE OF THE BAR. THE GRAB BARS |
| | SHALL BE MEASURED TO THE TOP OFF THE GRIPPING SURFACE |
| | PER FBC-ACCESS. SEC. 609.4. |
| | 2) SHT. A5.03 DETAIL #9 - PLACE A NOTE ON THE PLAN THAT |
| | THE THRESHOLD WILL NOT EXCEED 1/2 INCH IN HEIGHT PER |
| | FBC-ACCESS. SEC. 404.2.5 AND WILL COMPLY WITH |
| | SEC.303.3. |
| | 3) SHT. P3.2 - THE REQUIRED RECIRCULATION LINE ON THE |
| | WATER SYSTEM IS NOT CLEAR ON THE WATER RISER. IN |
| | ADDITION, THE WATTER RISER SHOWS A 1/2 INCH LINE AT THE |
| | WATER HEATER SUPPLYING HOT WATER TO THE FIXTURES AND |
| | ALSO SUPPLYING A 3/4 INH, 1 INCCH AND AN 1 1/4 INCH HOT |
| | WATER LINE. I DO NOT SEE THE RECIRCUATION LINE ON THE |
| | WATER RISER.COMPLY WITH FBC-PLUMBING SEC.607.2. THE HOT |
| | WATER SYSTEM SHALL BE INSULATED IN ITS ENTIRETY PER |
| | FBC-ENERGY SEC. C404.4. THE THICKNESS OF THE INSULATION |
| | SHALL COMPLY WITH FBC-ENERGY TABLE C403.2.10. |
| | 4) THE SANITARY RISER APPEARS TO SHOW VENTS THAT EXCEED |
| | 40 FEET IN DEVELOPED LENGTH. VENTS EXCEEDING 40 FEET IN |
| | DEVELOPED LENGTH SHALL BE INCREASED BY ONE NOMINAL PIPE |
| | SIZE FOR THE ENTIRE LENGTH OF VENT PIPE PER |
| | FBC-PLUMBING SEC.906.2. THE VENT PIPE HAS NOT BEEN |
| | INCREASED FOR THE ENTIRE DEVELOPED LENGTH. THE SANITARY |
| | RISER SHOWS A 2 INCH VENT INCREASING TO 3 INCHES. THE |
| | VENT SHALL BE 3 INCH IN ITS ENTIRETU. |
| | 5) SHT. A5.03 - SHOW THE DIMEENSION FROM THE FINISH |
| | FLOOR TO THE BOTTOM EDGE OF THE REFLECTIVE SURFACE OF |
| | THE MIRROR. COMPLY WITH FBC-ACCESS. SEC.603.3. THE |
| | NARRATIVE RESPONSE REFERS TO SHT. A5.01 WHICH IS FOR |
| | PARTITION TYPESAND NOT APPLICABLE.. |
| | 6) SHT. A1.30 - EQUIPMENT GENERAL NOTES REFERS TO |
| | MIAMI-DADE SEC. 24-42.4. DELETE THIS NOTE AS IT IS NOT |
| | APPLICABLE. |
| | 7) PLACE A NOTE ON SHT. CP-101 THAT A SEPARATE PERMIT |
| | IS REQUIRED FOR THE NEW BACKFLOW PREVENTER. |
| | |
| | TIM LARGE |
| | CHIEF PLUMBING INSPECTOR |
| | PLUMBING PLAN REVIEW |
| | 561-805-6692 |
| | [email protected] |
| | |
| | |