2021-02-23 07:18:101) SHT. A5.03 - FIXTURE MOUNTING DIAGRAM - THIS DIAGRAM
 STILL SHOWS THE GRAB BARS AT THE WATER CLOSETS BEING
 MEASURED TO THE CENTERLINE OF THE BAR. THE GRAB BARS
 SHALL BE MEASURED TO THE TOP OFF THE GRIPPING SURFACE
 PER FBC-ACCESS. SEC. 609.4.
 2) SHT. A5.03 DETAIL #9 - PLACE A NOTE ON THE PLAN THAT
 THE THRESHOLD WILL NOT EXCEED 1/2 INCH IN HEIGHT PER
 FBC-ACCESS. SEC. 404.2.5 AND WILL COMPLY WITH
 SEC.303.3.
 3) SHT. P3.2 - THE REQUIRED RECIRCULATION LINE ON THE
 WATER SYSTEM IS NOT CLEAR ON THE WATER RISER. IN
 ADDITION, THE WATTER RISER SHOWS A 1/2 INCH LINE AT THE
 WATER HEATER SUPPLYING HOT WATER TO THE FIXTURES AND
 ALSO SUPPLYING A 3/4 INH, 1 INCCH AND AN 1 1/4 INCH HOT
 WATER LINE. I DO NOT SEE THE RECIRCUATION LINE ON THE
 WATER RISER.COMPLY WITH FBC-PLUMBING SEC.607.2. THE HOT
 WATER SYSTEM SHALL BE INSULATED IN ITS ENTIRETY PER
 FBC-ENERGY SEC. C404.4. THE THICKNESS OF THE INSULATION
 SHALL COMPLY WITH FBC-ENERGY TABLE C403.2.10.
 4) THE SANITARY RISER APPEARS TO SHOW VENTS THAT EXCEED
 40 FEET IN DEVELOPED LENGTH. VENTS EXCEEDING 40 FEET IN
 DEVELOPED LENGTH SHALL BE INCREASED BY ONE NOMINAL PIPE
 SIZE FOR THE ENTIRE LENGTH OF VENT PIPE PER
 FBC-PLUMBING SEC.906.2. THE VENT PIPE HAS NOT BEEN
 INCREASED FOR THE ENTIRE DEVELOPED LENGTH. THE SANITARY
 RISER SHOWS A 2 INCH VENT INCREASING TO 3 INCHES. THE
 VENT SHALL BE 3 INCH IN ITS ENTIRETU.
 5) SHT. A5.03 - SHOW THE DIMEENSION FROM THE FINISH
 FLOOR TO THE BOTTOM EDGE OF THE REFLECTIVE SURFACE OF
 THE MIRROR. COMPLY WITH FBC-ACCESS. SEC.603.3. THE
 NARRATIVE RESPONSE REFERS TO SHT. A5.01 WHICH IS FOR
 PARTITION TYPESAND NOT APPLICABLE..
 6) SHT. A1.30 - EQUIPMENT GENERAL NOTES REFERS TO
 MIAMI-DADE SEC. 24-42.4. DELETE THIS NOTE AS IT IS NOT
 APPLICABLE.
 7) PLACE A NOTE ON SHT. CP-101 THAT A SEPARATE PERMIT
 IS REQUIRED FOR THE NEW BACKFLOW PREVENTER.
  