Plan Review Notes
Plan Review Notes For Permit 20111112
Permit Number 20111112
Review Stop P
Sequence Number 1
Notes
Date Text
2021-01-14 09:13:381) A MINIMUM OF ONE EXAM ROOM SINK SHALL COMPLY WITH
 FBC-ACCESS. SECS.212.3 & 606.2. A CLEAR FLOOR SPACE
 COMPLYING WITH SEC. 305, POSITIONED FOR A FORWARD
 APPROACH, AND KNEE AND TOE CLEARANCE COMPLYING WITH
 SEC. 306 SHALL BE PROVIDED. IDENTIFY ON THE PLAN WHICH
 EXAM ROOM SINK WILLL MEET THIS REQUIREMENT.
 2) SHT. A1.40 - THE FINISH SCHEDULE SHOWS THE WALLS IN
 ROOM #155 TO PAINTED. SECTION 1210.2.2 OF THE
 FBC-BUILDING REQUIRES WALLS WITHIN 2 FEET OF SERVICE
 SINKS TO HAVE A SMOOTH, HARD, NONABSORBANT SURFACE TO A
 HEIGHT OF NOT LESS THAN 4 FEET ABOVE THE FINISH FLOOR.
 EPOXY PAINT DOES NOT MEET THE INTENT OF THIS SECTION.
 3) SHT. A5.03 - THE GRAB BARS SHALL BE MEASURED TO THE
 TOP OF THE GRIPPING SURFACE PER FBC-ACESS. SEC. 609.4.
 4) SHT. A5.03 - DETAILS #9 & #10 - SUBMIT ADDITIONAL
 INFORMATION AS TO THE TYPE OF WATERPROOFING MEMBRANE TO
 BE USED FOR THE ACCESSIBLE SHOWERS AND HOW THE MEMBRANE
 WILL BE ATTACHED TO THE SUBSTRATE AND ALSO HOW THE
 ATTACHMENT WIL BE MADE WATERTIGHT. WPB AMEND. TO FBC
 SEC.107.2.1.
 5) SHT. A5.03 - DETAIL #9 - APPEARS TO SHOW A THRESHOLD
 ALTHOUGH THE DETAIL TEXT STATES NO THRESHOLD. CLARIFY.
 6) SHT. A5.03 - ACCESSIBLE MOUNTING DIAGRAM FOR TOILET
 PAPER DISPENSER - THE DISPENSER SHALL BE MOUNTED A
 MINIMUM OF 15 INCHES AND A MAXIMUM OF 48 INCHES ABOVE
 THE FINISH FLOOR AND SHALL NOT BE LOCATED BEHIND GRAB
 BARS PER FBC-ACCESS. SEC.604.7.
 7) SHT.A5.03 - DETAILS #8 - THE HEIGHT OF THE HANDICAP
 WATER CLOSET IS SHOWN AS 1 FOOT 3 INCHES ABOVE THE
 FINISH FLOOR. COMPLY WITH FBC-ACCESS. SEC.604.4.
 8) SHT. A5.03 - DETAILS #1,3,5,& 7 - THE POSITION OF
 THE REAR GRAB BAR AND SIDE GRAB BAR SHALL COMPLY WITH
 FBC-ACCESS. SECS. 604.5.1 & 604.5.2. SHOW COMPLIANCE ON
 THE PLANS.
 9) SHT.SHT. A5.03 - DETAILS #1,3,5,& 7 - SHOW THE
 LENGTH OF THE SIDE AND REAR GRAB BARS ON THE PLANS.
 COMPLY WITH FBC-ACCESS. SECS. 604.5.1 & 604.5.2.
 10) SHT. D5.03 - DETAILS #2,4,6,& 8 - THE HEIGHT OF THE
 ACCESSIBLE WATER CLOSET IS SHOWN AS 1 FOOT 3 INCHES.
 CLARIFY.
 11) SHT. A5.03 - THE TOILET PAPER DISPENSER SHALL BE
 LOCATED 7-9 INCHES FROM THE FRONT OF THE TOILET BOWL TO
 THE CENTER LINE FIRST DISPENSER. FBC-ACCESS SEC. 604.7.
 12) A RECIRCULATION LINE IS REQUIRED PER FBC-PLUMBING
 SEC.607.2.SHOW THE RECIRCULATION LINE ON TH WATER
 RISER.
 13) THE SANITARY RISER APPEARS TO SHOW VENTS THAT
 EXCEED 40 FEET IN DEVELOPED LENGTH. VENTS EXCEEDING 40
 FEET IN DEVELOPED LENGTH SHALL BE INCREASED BY ONE
 NOMINAL PIPE SIZE FOR THE ENTIRE DEVELOPED LENGTH OF
 THE VENT PIPE PER FBC-PLUMBING SEC. 906.2.
 14) SHT. A5.03 - SHOW THE DIMENSION FROM THE FINISH
 FLOOR TO THE BOTTOM EDGE OF THE REFLECTIVE SURFACE OF
 THE MIRROR IN THE TOILET ROOMS. THE HEIGHT OF THE
 MIRROR SHALL COMPLY WITH FBC-ACCES.SEC.603..3.
 15) THERMOSTATIC MIXING VALVES ON LAVATORIES SHALL
 COMPLY WITH ASSE 1070. FBC-PLUMBING SEC. 416.5.
 16) THE FLOOR PLAN CALLS OUT ROOM # 139 & 149 AS LAB
 ROOMS. PLEASE PROVIDE INFORMATION AS TO WHAT TYPE
 MATERIALS/ COMPUNDS WILL BE STORED AND USED IN THESE
 ROOMS THAT MAY CONSTITUTE A PHYSICAL OR HEALTH HAZARD
 IN QUANTITIES IN EXCESS OF THOSE ALLOWED IN CONTROL
 AREAS COMPLYING WITH FBC-BUILDING SEC. 414 BASED ON THE
 MAXIMUM ALLOWABLE QUANTITY LIMITS IN TABLES 307.1 (1)
 AND 307.1 (2).
 17) SHTS. P2.0 & P2.1 - CLARIFY THE SCOPE OF WORK TO BE
 DONE ON THE PLUMBING SYSTEM IN THE EXISTING TOILET
 ROOMS. THE PLANS ARE UNCLEAR. WPB AMEND. TO FBC SEC.
 107.2.1.
 18) THE HOT WATER LINE AND RECIRCULATION LINE SHALL BE
 INSULATED IN ITS ENTIRETY WITH PIPE INSULATION. THE
 THICKNESS OF THE INSULATION SHALL COMPLY WITH
 FBC-ENERGY TABLE C403.2.10.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW