| 2021-03-11 16:46:58 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1 |
| | WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL |
| | MANUAL REVISED 2017 |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION |
| | FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH |
| | EDITION |
| | FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION |
| | FAC= FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | |
| | 20111108 514 14TH ST |
| | 3RD REVIEW |
| | |
| | PLUMBING COMMENTS:DENIED |
| | |
| | NOTE: IN RECEIPT OF BIG WATER HEMP LOR 2 RESPONSE TO |
| | PLBG REVIEW 2 DATED 2/23/2021, FORWARDED BY EMAIL FROM |
| | KIMBERLY LEWIS OF SR CONSTRUCTION SERVICES LLC ON |
| | 3/11/2021. |
| | |
| | PLEASE NOTE THAT PLAN SHEETS 014 P-2 PLUMBING ISOMETRIC |
| | DETAILS, 013 P-1 PLUMBING FLOOR PLAN-ENLAGED |
| | PLAN-TRENCH INFILLS AND 015 IRR-1 IRRIGATION |
| | PLAN-IRRIGATION ISOMETRIC-DETAILS HAVE BEEN REDLINED IN |
| | AN ATTEMPT TO HELP CLARIFY COMMENTS. |
| | COMMENTS FROM REVIEW DATED 2/23/2021. |
| | |
| | 1) IRR-1: SUBMIT MANUFACTURER'S SPECIFICATIONS FOR ALL |
| | COMPONENTS OF THE HYDROPONIC IRRIGATION SYSTEM |
| | INCLUDING THE REVERSE OSMOSIS TREATMENT SYSTEM, BOOSTER |
| | PUMP, WATER STORAGE TANKS, PIPING AND TUBING, AND THE |
| | ADDITIONAL COMPONENTS LISTED ON THE PLAN SHEET. PLEASE |
| | NOTE THE SPECS MAY BE DEFERRED SUBMITTALS TO PROVIDED |
| | AT A LATER DATE WITH THE ARCHITECT?S APPROVAL STAMP- |
| | SEE SECTIONS 107.1, 107.3, AND 107.3.4.1 WPB AMENDMENTS |
| | TO THE FBC-2017. |
| | PROVISO: SPECS MAY BE DEFERRED SUBMITTALS TO PROVIDED |
| | AT A LATER DATE WITH THE ARCHITECT?S APPROVAL STAMP- |
| | SEE SECTIONS 107.1, 107.3, AND 107.3.4.1 WPB AMENDMENTS |
| | TO THE FBC-17. PROCEED AT YOUR OWN RISK. |
| | |
| | 2) PLEASE PROVIDE AN ITEMIZED BREAKDOWN OF COSTS |
| | ASSOCIATED WITH THE CHANGES IN THE PLANS AND PROJECTS |
| | INCLUDING THE IRRIGATION SYSTEM, ADDITIONAL TOILET |
| | ROOM, WATER HEATERS ETC.- SECTION 109.3 WPB. |
| | RESPONSE; TO BE PROVIDED BY GC. |
| | BREAKDOWN MUST BE PROVIDED AND APPROVED PRIOR TO |
| | APPROVAL FOR PERMIT. |
| | |
| | 3) CLARIFY IF THE IRRIGATION SYSTEM WILL BE INSTALLED |
| | BY THE PLUMBING SUB-CONTRACTOR OR BY ANOTHER IRRIGATION |
| | OR PLUMBING CONTRACTOR. PLEASE NOTE THAT SUB-PERMIT |
| | APPLICATIONS MUST BE SUBMITTED AND ARE AT NO FEE IF |
| | SUBMITTED WITH THE MAIN PERMIT APPLICATION- SECTION |
| | 105.1 WPB. AN ADDITIONAL FEE IS CHARGED FOR SUB-PERMITS |
| | SUBMITTED AFTER MASTER PERMIT ISSUANCE. |
| | RESPONSE; TO BE PROVIDED BY GC; |
| | PROVISO: IRR-1 SUBMIT MANUFACTURER'S SPECIFICATIONS FOR |
| | ALL COMPONENTS OF THE HYDROPONIC IRRIGATION SYSTEM |
| | INCLUDING THE REVERSE OSMOSIS TREATMENT SYSTEM, BOOSTER |
| | PUMP, WATER STORAGE TANKS, PIPING AND TUBING, AND THE |
| | ADDITIONAL COMPONENTS LISTED ON THE PLAN SHEET AS |
| | DEFERRED SUBMITTALS TO PROVIDED AT A LATER DATE WITH |
| | THE ARCHITECT?S APPROVAL STAMP- SEE SECTIONS 107.1, |
| | 107.3, AND 107.3.4.1 WPB AMENDMENTS TO THE FBC-17. |
| | MISSING DETAILS CAN BE PROVIDED ON THE PLANS, IN A |
| | SCHEMATIC DRAWING, OR BY DEFERRED SHOP DRAWINGS- FBC-17 |
| | P: |
| | A) WATER TANK ANCHORAGE- SECTION 606.5.2. |
| | B) SHUT OFF VALVE LOCATIONS FOR TANKS AND EQUIPMENT- |
| | 606.2 & 606.4. |
| | C) TANK OVERFLOW SYSTEM- 606.5.4. |
| | D) LOW PRESSURE CUTOFF FOR BOOSTER PUMP- 606.5.5 |
| | E) POTABLE WATER INLET CONTROL AND LOCATION- 606.5.6. |
| | F) TANK DRAIN PIPES- 606.5.7. |
| | PROCEED AT YOUR OWN RISK |
| | REFER TO SEE RED LINED PLAN ?015 IRR-1 IRRIGATION |
| | PLAN-IRRIGATION ISOMETRIC-DETAILS? |
| | |
| | |
| | ADDITIONAL COMMENTS |
| | 1.RE: P-2 SANITARY ISOMETRIC; THE UNDERGROUND COMMON |
| | VENTS NOTED ON THE DRAWING ARE PROHIBITED. SEE THE |
| | FOLLOWING. REFER TO SEE RED LINED PLAN ?014 P-2 |
| | PLUMBING ISOMETRIC DETAILS? REGARDING FLOOR DRAIN AND |
| | BATHROOM VENTING |
| | A.FBC PL 905.3 VENT CONNECTION TO DRAINAGE SYSTEM. |
| | EVERY DRY VENT CONNECTING TO A HORIZONTAL DRAIN SHALL |
| | CONNECT ABOVE THE CENTERLINE OF THE HORIZONTAL DRAIN |
| | PIPE. |
| | B.FBC PL 905.4 VERTICAL RISE OF VENT. |
| | EVERY DRY VENT SHALL RISE VERTICALLY TO A POINT NOT |
| | LESS THAN 6 INCHES (152 MM) ABOVE THE FLOOD LEVEL RIM |
| | OF THE HIGHEST TRAP OR TRAPPED FIXTURE BEING VENTED. |
| | EXCEPTION: VENTS FOR INTERCEPTORS LOCATED OUTDOORS. |
| | C.WET VENT FROM LAVATORY SHALL CONNECT TO THE FIXTURE |
| | DRAIN OF THE WATER CLOSET TO COMPLY WITH FBC PL 912.1 |
| | HORIZONTAL WET VENTING. PLEASE NOTE THAT ACCORDING TO |
| | FBC PL CHAPTER 2 DEFINITIONS, A FLOOR DRAIN IN THE |
| | BATHROOM IS INCLUDED AS AN ALLOWABLE FIXTURE FOR A |
| | BATHROOM GROUP AND AS SUCH MAY BE CONNECTED TO THE WET |
| | VENT DOWNSTREAM OF THE WATER CLOSET AND WET VENT |
| | INTERSECTION WITHOUT RE-VENTING THE FLOOR DRAIN. |
| | D. THE THREE (3) FLOOR DRAINS DOWNSTREAM OF THE |
| | BATHROOMS, SINKS AND DRINKING FOUNTAIN SHALL BE VENTED |
| | BY ONE OF THE METHODS NOTED IN FBC PL CHAPTER 9. |
| | PLEASE SEE RED LINED PLAN ?014 P-2 PLUMBING ISOMETRIC |
| | DETAILS? REGARDING FLOOR DRAIN AND BATHROOM VENTING |
| | PLEASE SEE RED LINED PLAN ?013 P-1 PLUMBING FLOOR |
| | PLAN-ENLAGED PLAN-TRENCH INFILLS? REGARDING SLAB |
| | CUTTING/TRENCHING FOR FLOOR DRAINS |
| | |
| | 2.PER WPB FBC 107.2.1, INDICATE ON THE PLUMBING PLANS, |
| | THE LOCATION(S) AND MODEL OF THE BRADLEY S-19-200B |
| | FAUCET MOUNTED EYEWASH PROVIDED IN SUPPORTING |
| | DOCUMENTS. RESPONSE NOTED TWO LOCATIONS BUT IS NOT |
| | NOTED ON THE PLANS. |
| | PLEASE SEE RED LINED PLAN ?014 P-2 PLUMBING ISOMETRIC |
| | DETAILS? |
| | |
| | 3. PROVIDE SPEC FOR IRRIGATION BACKFLOW PREVENTER WITH |
| | MANUFACTURER, AND MODEL. INDICATE TYPE (IE. REDUCED |
| | PRESSURE/RPZ). NOTE THE BACKFLOW PREVENTER IS DEDICATED |
| | TO THE IRRIGATION SYSTEM. |
| | |
| | 4.PER WPB FBC107.2.1, SHOW ON THE PLANS THE LOCATION, |
| | SIZE AND TYPE OF THE BACKFLOW PREVENTER INSTALLED |
| | DOWNSTREAM OF THE CITY METER. |
| | PLEASE SEE RED LINED PLAN ?013 P-1 PLUMBING FLOOR |
| | PLAN-ENLAGED PLAN-TRENCH INFILLS? REGARDING BACKFLOW |
| | PREVENTER AT THE CITY METER |
| | |
| | |
| | |
| | END OF COMMENTS. |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS.ALL PLANS TO BE SIGNED |
| | AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS. |
| | |
| | |
| | |
| | JERALD SMITH |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |