| Plan Review Notes For Permit 20111108 |
| Permit Number |
20111108 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2020-12-02 13:12:57 | FIRE PROVISO: | | | | | | THE FIRE SPRINKLER SYSTEM IS REQUIRED TO BE MONITORED | | | PER NFPA 101, CH 9 | | | | | | 9.7.2 SUPERVISION. | | | 9.7.2.1* SUPERVISORY SIGNALS. | | | 9.7.2.1.1 WHERE SUPERVISED AUTOMATIC SPRINKLER SYSTEMS | | | ARE REQUIRED BY | | | ANOTHER SECTION OF THIS CODE, SUPERVISORY ATTACHMENTS | | | SHALL BE INSTALLED | | | AND MONITORED FOR INTEGRITY IN ACCORDANCE WITH NFPA 72, | | | NATIONAL FIRE | | | ALARM AND SIGNALING CODE, AND A DISTINCTIVE SUPERVISORY | | | SIGNAL SHALL BE | | | PROVIDED TO INDICATE A CONDITION THAT WOULD IMPAIR THE | | | SATISFACTORY | | | OPERATION OF THE SPRINKLER SYSTEM. | | | 9.7.2.1.2 SUPERVISORY SIGNALS SHALL SOUND AND SHALL BE | | | DISPLAYED EITHER AT | | | A LOCATION WITHIN THE PROTECTED BUILDING THAT IS | | | CONSTANTLY ATTENDED BY | | | QUALIFIED PERSONNEL OR AT AN APPROVED, REMOTELY LOCATED | | | RECEIVING | | | FACILITY. | | | | | | PLEASE ENSURE COMPLIANCE. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|