2021-02-09 15:59:102ND REVIEW FBC-2017 PLUMBING
 PERMIT- 20111104
 2/9/2021
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
 FAILED COMMENTS FROM THE 1ST REVIEW ARE LISTED BELOW
 WITH ADDITIONAL NOTES.
  
 1) PROVIDE ACCESSIBLE PLUMBING FIXTURE DETAILS FOR THE
 NEW SHOWER ROOMS, WELLNESS ROOM, AND BUSINESS LOUNGE-
 FBC-17 ACCESSIBILITY.
  
 C) FAILED. TURNING SPACE DIAMETERS- SECTION 304.3. NOT
 PROVIDED.
  
 D) FAILED. CENTERLINE OF THE WATER CLOSETS FROM THE
 SIDE WALLS- SECTION 604.2. SHEET A3.0.5: CENTERLINE OF
 WOMEN'S WATER CLOSET NOT SHOWN.
  
 E) FAILED. HEIGHTS OF THE WATER CLOSET SEATS FROM THE
 FINISHED FLOORS- SECTION 604.4. NOT PROVIDED.
  
 G) FAILED. LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF
 GRAB BARS FOR THE WATER CLOSETS- SECTION 604.5 & 609.4.
 SHEETS A3.02 & A3.05: SIDE WALL GRAB BARS SHALL EXTEND
 A MINIMUM OF 54 INCHES FROM THE REAR WALL- SEE FIGURE
 605.5.1. REAR WALL GRAB BARS NOT CENTERED CORRECTLY-
 SEE FIGURE 604.5.2. SIDE WALL GRAB BAR HEIGHTS NOT
 SHOWN.
  
 K) FAILED. KNEE AND TOE CLEARANCES FOR LAVATORIES AND
 SINKS- SECTION 606.2. NOT PROVIDED. DETAILS ON A4.04
 ARE NOT LAVATORIES.
  
 5) FAILED. P2.0.0: SHOW THE LOCATIONS OF THE MIXING
 VALVES AT LAVATORIES- SECTIONS 416.5 & 607.2.1 FBC P.
 PROVIDE A PLUMBING PIPING DETAIL FOR INSTALLATION OF
 THE WATER HEATERS AND MIXING VALVES BELOW THE LAVATORY
 SINKS- TABLE C404.5.1 FBC EC. MIXING VALVE LOCATIONS
 NOT SHOWN ON SHEETS P1.1.2 & P2.0.0.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  