Plan Review Notes
Plan Review Notes For Permit 20111104
Permit Number 20111104
Review Stop M
Sequence Number 2
Notes
Date Text
2021-02-04 15:33:421ST REVIEW FBC-2020 MECHANICAL
 PERMIT-20111104
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2020
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2020
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2020
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M2.0.0: PLEASE USE THE 2017 EDITION OF FBC
 MECHANICAL CODE.
  
 2) SHEET M2.0.0: PLEASE PROVIDE OUTDOOR AIR
 CALCULATIONS BASED ON 2017 FBC M 403.3.1.1. YOU DO NOT
 USE THE OCCUPANT COUNT GIVEN BY THE A SHEETS. STEP 1:
 YOU WOULD TAKE THE SQ. FT. OF THE SPACE AND DIVIDE BY
 1000, TAKE THIS NUMBER AND MULTIPLY BY THE NUMBER IN
 THE (OCCUPANT DENSITY) COLUMN, THEN MULTIPLY THAT
 NUMBER BY THE NUMBER IN THE (PEOPLE OUTDOOR AIR-FLOW
 RATE IN BREATHING ZONE) COLUMN. STEP 2: TAKE THE SQ.
 FT. OF THE AREA AND MULTIPLY THIS BY THE NUMBER IN THE
 (AREA OUTDOOR AIRFLOW RATE IN BREATHING ZONE) COLUMN.
 LAST STEP IS TO TAKE THE ANSWER FROM THE FIRST STEP AND
 SECOND STEP AND ADD TOGETHER. THIS IS THE MINIMUM
 OUTDOOR AIR RATE FOR THIS SPACE.
  
 (VENTILATION SYSTEMS SHALL BE DESIGNED TO HAVE THE
 CAPACITY TO SUPPLY THE MINIMUM OUTDOOR AIRFLOW RATE,
 DETERMINED IN ACCORDANCE WITH THIS SECTION. IN EACH
 OCCUPIABLE SPACE, THE VENTILATION SYSTEM SHALL BE
 DESIGNED TO DELIVER THE REQUIRED RATE OF OUTDOOR
 AIRFLOW TO THE BREATHING ZONE. THE OCCUPANT LOAD
 UTILIZED FOR DESIGN OF THE VENTILATION SYSTEM SHALL BE
 NOT LESS THAN THE NUMBER DETERMINED FROM THE ESTIMATED
 MAXIMUM OCCUPANT LOAD RATE INDICATED IN TABLE
 403.3.1.1.)
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved