Plan Review Notes
Plan Review Notes For Permit 20111104
Permit Number 20111104
Review Stop P
Sequence Number 1
Notes
Date Text
2021-01-07 10:35:071ST REVIEW FBC-2017 PLUMBING
 PERMIT- 20111104
 1/7/2021
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE ACCESSIBLE PLUMBING FIXTURE DETAILS FOR THE
 NEW SHOWER ROOMS, WELLNESS ROOM, AND BUSINESS LOUNGE-
 FBC-17 ACCESSIBILITY.
  
 A) CLEAR FLOOR SPACE DIAGRAMS AND DIMENSIONS FOR THE
 WATER CLOSETS- SECTION 604.3.
 B) CLEAR FLOOR SPACE DIAGRAMS AND DIMENSIONS FOR THE
 LAVATORIES- SECTION 606.2.
 C) TURNING SPACE DIAMETERS- SECTION 304.3.
 D) CENTERLINE OF THE WATER CLOSETS FROM THE SIDE WALLS-
 SECTION 604.2.
 E) HEIGHTS OF THE WATER CLOSET SEATS FROM THE FINISHED
 FLOORS- SECTION 604.4.
 F) HEIGHTS OF THE MIRRORS FROM THE FINISHED FLOORS TO
 THE REFLECTIVE SURFACES- SECTION 603.3
 G) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB
 BARS FOR THE WATER CLOSETS- SECTION 604.5 & 609.4
 H) LOCATIONS OF THE WATER CLOSET FLUSH CONTROLS -
 SECTION 604.6.
 I) CENTERLINES OF THE TOILET PAPER DISPENSERS MEASURED
 FROM THE FRONTS OF THE WATER CLOSETS- SECTION 604.7.
 K) KNEE AND TOE CLEARANCES FOR LAVATORIES AND SINKS-
 SECTION 606.2.
 L) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE
 SHOWER- SECTION 608.2.2.1
 M) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB
 BARS FOR THE ACCESSIBLE SHOWER- SECTION 608.3.2 AND
 609.4.
 N) LOCATION OF CONTROL, FAUCET, AND SHOWER SPRAY IN THE
 SHOWER- SECTION 608.5.2 & 608.6.
 O) SHOWER SPRAY UNIT SPECIFICATIONS PER SECTION 608.6.
 P) CLEAR FLOOR SPACE DIAGRAMS AND DIMENSIONS, AND
 COMPLIANCE DETAILS FOR REACH RANGES AND OPERABLE PARTS
 FOR THE BOTTLE FILLER, ICE MAKER, AND COFFEE MAKER-
 SECTIONS 904.5.1, 305, 308, & 309.
  
 2) P0.0.0: PLEASE PROVIDE PIPE MATERIAL SPECIFICATIONS
 FOR SANITARY DRAINS AND VENTS, AND WATER DISTRIBUTION
 AND SUPPLY LINES- SECTION 303.2 FBC P. PLEASE NOTE THAT
 BASED ON MECHANICAL PLAN NOTES IT APPEARS PIPING MAY BE
 RUNNING THROUGH PLENUM RATED SPACES WHERE PVC PIPES AND
 CONDUITS ARE PROHIBITED.
  
 3) P0.0.0 & P1.1.2: PLEASE INCLUDE THE SHOWER FAUCET
 AND SPRAY, TEMPERATURE LIMITING DEVICES (MIXING
 VALVES), AND BACKFLOW PREVENTERS IN THE FIXTURE
 SCHEDULE- SECTION 607.2.1 AND TABLE 608.1 FBC P.
  
 4) P1.1.1: INSTALLATION OF THE NEW SANITARY DRAINS WILL
 REQUIRE THE CONCRETE FLOOR SLAB TO BE X-RAYED TO IN
 ORDER TO LOCATE REINFORCING STEEL OR POST STRESSED
 FLOOR TENDONS. PLEASE PLACE A NOTE ON THE PLANS TO
 VERIFY COMPLIANCE WILL BE MET- SECTION 107.2.1 WPB.
  
 5) P2.0.0: SHOW THE LOCATIONS OF THE MIXING VALVES AT
 LAVATORIES- SECTIONS 416.5 & 607.2.1 FBC P. PROVIDE A
 PLUMBING PIPING DETAIL FOR INSTALLATION OF THE WATER
 HEATERS AND MIXING VALVES BELOW THE LAVATORY SINKS-
 TABLE C404.5.1 FBC EC.
  
 6) P2.0.0: SHOW WATER HAMMER ARRESTORS FOR SUPPLY LINES
 TO THE COFFEE MAKER, DISHWASHER, AND ICE MAKER- SECTION
 604.9 FBC P.
  
 7) PROVIDE ENLARGED SHOWER PAN AND THRESHOLD
 INSTALLATION DETAILS IN ACCORDANCE WITH SECTION 417.3-
 417.5.2 FBC P, AND SECTION 608.7 FBC ACC.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  