| Plan Review Notes For Permit 20111104 |
| Permit Number |
20111104 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2021-01-11 16:01:18 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | FLORIDA BUILDING CODE 2017 6TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | | NFPA 70 2014 EDITION | | | | | | JAKE LEAHY BN, BU, PX | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | 1) OTHER THAN DWELLING UNITS. ALL 125-VOLT, | | | SINGLE-PHASE, 15- AND 20-AMPERE RECEPTACLES INSTAL LED | | | IN THE LOCATIONS SPECIFIED IN 210.8(B)(1) THROUGH (8) | | | SHALL HAVE GROUND-FAULT CIRCUITINTERRUPTER PROTECTION | | | FOR PERSONNEL | | | (5) SINKS ? WHERE RECEPTACLES ARE INSTALLED WITHIN 1.8 | | | M (6 FT) OF THE OUTSIDE EDGE OF THE SINK | | | (7) LOCKER ROOMS WITH ASSOCIATED SHOWERING FACILITIES | | | | | | OUTLETS IN LOCKER AREA NEED TO BE GFCI PROTECTED | | | | | | OUTLETS WITHIN 6' OF THE SINK IN BREAK ROOM NEED TO BE | | | GFCI PROTECTED | | | |
|