Plan Review Notes
Plan Review Notes For Permit 20111104
Permit Number 20111104
Review Stop B
Sequence Number 1
Notes
Date Text
2021-01-08 09:13:21INTERIOR OFFICE BUILDOUT
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) DRAWINGS SHOW CORRIDOR WALLS BETWEEN ELEVATOR AND
 OFFICES AS NON FIRE RATED. PLEASE SHOW HOW THE EXISTING
 ELEVATOR HOIST WAY IS PROTECTED PER FBC 3006.3
 2) PLEASE SHOW THE REQUIRED FLOOR SPACE FOR ALL
 ACCESSIBLE ELEMENTS SUCH AS SINK, TOILETS, SHOWERS,
 MICROWAVE, REFRIGERATOR ETC. PER FBC 305
 3) PLEASE PROVIDE A MORE COMPLETE AND DETAILED DRAWING
 SHOWING THE LOCATIONS, SIZE, HEIGHT FROM FLOOR, ETC.
 FOR GRAB BARS, PAPER DISPENSERS, MIRRORS, TOILETS,
 SHOWERS ETC. (PAPER DISPENSER LOCATION ON DRAWING
 A3.0.2 DOES NOT COMPLY WITH FBC ACCESSIBILITY 604.7)
  
  