| Plan Review Notes For Permit 20111104 |
| Permit Number |
20111104 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2021-01-08 09:13:21 | INTERIOR OFFICE BUILDOUT | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1 | | | AMENDMENTS | | | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | | 1) DRAWINGS SHOW CORRIDOR WALLS BETWEEN ELEVATOR AND | | | OFFICES AS NON FIRE RATED. PLEASE SHOW HOW THE EXISTING | | | ELEVATOR HOIST WAY IS PROTECTED PER FBC 3006.3 | | | 2) PLEASE SHOW THE REQUIRED FLOOR SPACE FOR ALL | | | ACCESSIBLE ELEMENTS SUCH AS SINK, TOILETS, SHOWERS, | | | MICROWAVE, REFRIGERATOR ETC. PER FBC 305 | | | 3) PLEASE PROVIDE A MORE COMPLETE AND DETAILED DRAWING | | | SHOWING THE LOCATIONS, SIZE, HEIGHT FROM FLOOR, ETC. | | | FOR GRAB BARS, PAPER DISPENSERS, MIRRORS, TOILETS, | | | SHOWERS ETC. (PAPER DISPENSER LOCATION ON DRAWING | | | A3.0.2 DOES NOT COMPLY WITH FBC ACCESSIBILITY 604.7) | | | | | | |
|