| 2021-05-21 11:47:51 | 05/21/21 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | ON SHEET 3.3P; |
| | |
| | 1. THE CODE REFERENCES IS 5 TH EDITION 2014 PLEASE |
| | CHANGE TO 2017 6 TH EDITION PER THE WPB AMENDMENTS TO |
| | THE FBC SEC. 102.4 REFERENCED CODES AND STANDARDS. |
| | |
| | 2. PLEASE PROVIDE A VALVE AT THE END OF THE RUN WITH |
| | CAP FOR FUTURE USE PER THE 2017 FBC FG SEC. 409.5. |
| | |
| | 3. PLEASE SHOW THE VALVE AND REGULATORS. A LISTED |
| | SHUTOFF VALVE SHALL BE INSTALLED IMMEDIATELY AHEAD OF |
| | EACH MP REGULATOR. 2017 FBC FG SEC. 409.4. |
| | |
| | 4. PLEASE LABEL THE SHUTOFF VALVE ON GAS ISOMERIC OR |
| | SHOW SYMBOL ON LEGEN PER THE 2017 FBC FG SEC. 409.5. |
| | |
| | 5. THE BEGINNING OF THE GAS SYSTEM HAS NO SIZE OR |
| | DIMENSION, PLEASE SHOW THE TYPE OF PIPE MATERIAL BEING |
| | INSTALLED, ALL PIPE SIZES FOR EACH PIPE SIZE PER THE |
| | WPB AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. |
| | |
| | 6. PLEASE GIVE THE DISTANCE FROM THE POINT OF DELIVERY, |
| | GAS METER TO THE MOST REMOTE OUTLET IN THE BUILDING |
| | AND/OR SYSTEM PER THE 2017 FBC FG SEC. 402.4.1. |
| | |
| | 7. SUBMIT MANUFACTURER'S SPECIFICATION |
| | SHEETS/INSTALLATION MANUAL FOR TANKLESS GAS EQUIPMENT |
| | TO VERIFY COMPLIANCE WITH 2017 FBC FG SEC.305.1. |
| | |
| | 8. A REGULATOR IS REQUIRED TO BRING THE SYSTEM DOWN TO |
| | 10.5 WC. PLEASE SUBMIT THE MANUFACTURER'S |
| | SPECIFICATIONS FOR THE PRESSURE REGULATORS. REGULATORS |
| | INSTALLED ON THE EXTERIOR OF THE BUILDING SHALL BE |
| | APPROVED FOR OUTDOOR INSTALLATION PER THE 2017 FBC RES. |
| | SEC. 410.1. |
| | |
| | 9. PLEASE SHOW ALL UNIONS IN FRONT OF REGULATOR 1' OF |
| | EITHER SIDE PER THE FBC FG SEC 410.2. |
| | |
| | 10. GAS UNITS REQUIRE CONDENSATE AND THEY NEED TO BE 1' |
| | AWAY FROM STRUCTURE AND TO A SAFE LOCATION ( NOT INTO |
| | SANITARY SYSTEM) PER THE 2017 FBC SEC R318.5. |
| | |
| | 11. SHOWING THE LOCATION OF THE TANK-LESS WATER HEATER |
| | AND THE LOCATION WITH THE DISTANCE OF ANY OPERABLE |
| | DOORS OR WINDOWS IN RELATION TO THE WATER HEATER AND TO |
| | EACH UNIT. THE LOCATION OF THE WATER HEATER SHALL |
| | COMPLY WITH THE MANUFACTURER'S INSTALLATION |
| | INSTRUCTIONS PER THE WPB AMENDMENTS TO THE FBC SEC. |
| | 107.2.1. INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES. |
| | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION, |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |