| Plan Review Notes For Permit 20111068 |
| Permit Number |
20111068 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2021-05-17 10:02:48 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | FLORIDA BUILDING CODE 2020 7TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED | | | NFPA 70 2017 EDITION | | | | | | JAKE LEAHY BN, BU, PX | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | PAGE A2.2 LTG GND | | | | | | 1) MDP PANEL SCHEDULE SHOWS PANEL "A" AND "B" AS SINGLE | | | POLE 20A WITH #12 WIRE. | | | | | | 2) PROVIDE FAULT CURRENT CLACULATION. | | | | | | PROVIDE CALCULATION FOR AVAILABLE SHORT CIRCUIT CURRENT | | | AT NEW PANEL TO CONFIRM AIC RATING IS ADEQUATE. NEC | | | 110.10 |
|