| 2021-04-20 12:24:12 | WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION |
| | SERVICES/ BUILDING DIVISION |
| | 2020 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 20111068 / 2017 FBC |
| | ADD: 522 CLEMATIS ST. |
| | CONT: TBD/ TO BE DETERMINED / CONTACT: JESSICA ROLLINGS |
| | TEL: ??? |
| | E-MAIL: [email protected] |
| | |
| | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: MON. APRIL 19TH/ 2021 |
| | ACTION: DENIED |
| | |
| | 1A) THE PERMIT APPLICATION DESCRIPTION OF WORK |
| | DESCRIBES THE RENOVATION AND INTERIOR IMPROVEMENTS INTO |
| | A NEW FOOD MARKETPLACE. IT WOULD APPEAR THERE IS NO |
| | FOOD MARKET AS PER SAY A GROCERY STORE BUT MULTIPLE |
| | FOOD VENDORS ON THE 1ST FLOOR A A2 OCCUPANCY AN A2 |
| | OCCUPANCY AND A NEW VERTICAL ADDITION CREATING A ROOF |
| | TOP 2ND STORY. PEASE NOTE YES YOU MAY CLAIM A LEVEL 3 |
| | ALTERATION TO THE 1ST FLOOR. PLEASE REVIEW ALL OF THE |
| | STRUCTURAL REQUIREMENTS FOUND IN THE 2017 FBC-EXISTING |
| | BUILDING CODE IN THE STRUCTURAL SECTION 907.1- 907.4.2. |
| | THE FLOOR PLAN SHOWS THE EXISTING EXTERIOR WALLS BEING |
| | TERRA-COTTA TILE. |
| | |
| | 1B) THERE IS ANOTHER ISSUE TO BE CONSIDERED, THE LAST |
| | KNOWN USE. THE LAST KNOWN USE (BUSINESS TAX/ |
| | OCCUPATIONAL LICENSE) WAS FOR AUTHENTIC PROVENCE INC. A |
| | MERCANTILE USE WHERE THEY SOLD RETAIL GARDEN |
| | ACCESSORIES, GARDEN EQUIPMENT, RETAIL SUPPLIES AND |
| | NURSERY. UNDER THE REQUIREMENTS IN THE2017 EXISTING |
| | BUILDING CODE FOR A CHANGE OF OCCUPANCY FOR A BUILDING |
| | YOU MUST ALSO SHOW COMPLIANCE FOR SECTIONS 1002 THROUGH |
| | 1012 OF THE EXISTING BUILDING CODE SHALL ALSO APPLY. |
| | UNDER THE PROJECT DETAILS YOU NEED TO ALSO ADD THE |
| | SECTION REQUIREMENT FOR CHANGE OF OCCUPANCY. |
| | |
| | 1C) THE 3RD ISSUE IS THE VERTICAL ADDITION REQUIREMENTS |
| | FOUND IN THE 2017 FBC-BUILDING CHAPTER 11, 1102.1, |
| | 1102.2 1102.3 1103.2 ADDITIONAL GRAVITY LOADS AND |
| | 1105.1 ACCESSIBILITY REQUIREMENTS. SEE THE 2020 |
| | FBC-ACCESSIBILITY CODE. |
| | |
| | 2) THE COVERSHEET CS-1 VERSES THE LIFE-SAFETY SHEET: |
| | |
| | 2A) THE 1ST FLOOR OCCUPANT LOAD ANALYSIS IS TAKEN @ 15 |
| | SQ. FT./ OCCUPANT. DIRECTLY IN FRONT OF EACH OF THE |
| | VENDOR STANDS WHERE THERE IS STANDING ONLY THE OCCUPANT |
| | LOAD SHOULD BE TAKEN AT 5SQ. FT./ OCCUPANT, TAKING THE |
| | 15 SQ. FT. IS FOR TABLE AND CHAIRS WHICH ARE NOT SHOWN |
| | ON THE 1ST FLOOR LIFE SAFETY PLAN. |
| | |
| | 2B) THE 2ND FLOOR LIFE SAFETY PLAN HAS ALSO TAKEN THE |
| | 15 SQ. FT. OCCUPANT LOAD FOR TABLES AND CHAIRS WHEREAS |
| | THE ONLY THING SHOWN ON THE 2ND FLOOR IS THE BAR NO |
| | CHAIRS WHERE THE 5 FEET PER OCCUPANT LOAD IS CORRECT. |
| | THE WORST-CASE SCENARIO HAS TO BE TAKEN SINCE THE 2ND |
| | FLOOR DOES NOT SHOW A SEATING FLOOR PLAN. |
| | |
| | 2C) THE COVERSHEET STATES THIS BUILDING CONSTRUCTION |
| | TYPE TO BE TYPE V-B SPRINKLERED. PLEASE NOTE TO HAVE |
| | CONSTRUCTION TYPE V-B BUILDING IT IS REQUIRED TO BE A |
| | SPRINKLERED BUILDING AS REQUIRED BY TABLE 504.4 OF THE |
| | 2017 FBC-B. THIS REVIEW THERE WERE NO PRE-LIMINARY FIRE |
| | SPRINKLER DRAWINGS FROM THE ARCHITECT. PLEASE PROVIDE |
| | WHAT AREAS OF THE BUILDING ARE GOING TO BE FIRE |
| | SPRINKLERED. 1ST FLOOR BELOW CEILING, ABOVE CEILING, |
| | INTERSTITIAL SPACE BETWEEN ROOF AND 2ND FLOOR FRAMING |
| | AND WHERE IN THE 2ND FLOOR WILL FIRE SPRINKLERS BE |
| | PLACED. WILL HERE BE COVERED DINING AREAS ON THE 2ND |
| | FLOOR. |
| | |
| | 2D)(1) PLEASE NOTE THE OCCUPANT LOAD AS SHOWN ON THE 2 |
| | COVERSHEET IS CURRENTLY LISTED AT 496 OCCUPANTS. WITH |
| | ANY ADDITIONAL OCCUPANT LOADING EITHER THE 7 SQ. FT./ |
| | OCCUPANT OR THE 5 SQ. FT. / OCCUPANT THIS WILL PUT YOU |
| | OVER 500 OCCUPANTS CREATING A THRESHOLD BUILDING. |
| | PLEASE NOTE IF THE OCCUPANT LOAD CAN BE KEPT AT UNDER |
| | 500 OCCUPANTS THEN COMMENT 3 GOES AWAY. IF COMMENT 3 |
| | (3A-3I) GOES AWAY THEN ALL STEEL WORK WILL NEED TO BE |
| | INSPECTED BY A 3RD PARTY, THE BUILDING DEPARTMENT WOULD |
| | HANDLE ALL OTHER STRUCTURE/ BUILDING INSPECTIONS. |
| | |
| | WELDED OR BOLTED CONNECTIONS. THIS BUILDING CONTAINS |
| | EITHER BOLTED AND OR WELDED CONNECTIONS. THE CONTRACTOR |
| | IS REQUIRED TO PROVIDE WELD PROCEDURE SPECIFICATIONS & |
| | WELDER OPERATOR PERFORMANCE QUALIFICATION RECORDS IN |
| | ACCORDANCE WITH THE REFERENCED STANDARDS AT TIME OF |
| | INSPECTION FOR FIELD WIELDING, ON THE JOB-SITE |
| | WIELDING. THIRD PARTY CERTIFICATION WILL BE REQUIRED. |
| | THE OWNER MAY JUST HIRE A 3RD PARTY ENGINEERING FIRM TO |
| | COMPLETE AND APPROVE THE FORMER INSPECTIONS. REPORTS |
| | SUBMITTED TO BUILDING INSPECTOR AT TIME OF FRAMING |
| | INSPECTION. |
| | 2017 FBC-B 2204.1 WELDING |
| | 1. WELD PROCEDURES SPECIFICATIONS |
| | 2. QUALIFICATIONS OF WELDING PERSONAL |
| | 2017 FBC-B 2204.2 BOLTING. |
| | IF FURTHER CLARIFICATION AND OR QUESTIONS IS REQUIRED, |
| | PLEASE CONTACT THE CHIEF BUILDING INSPECTOR KEN CONRAD |
| | AT 561-805-6666. |
| | |
| | 2D)(2) PLEASE ALSO CONSIDER IF THE OCCUPANT LOAD IS 500 |
| | OR LESS THAN ONLY 2 EXITS ARE REQUIRED. IF THE OCCUPANT |
| | LOAD IS OVER 500 THEN 3 VERTICAL EXITS WOULD BE |
| | REQUIRED. SEE THE 2017 FBC-B TABLE 1006.3.1. |
| | |
| | 3) THRESHOLD BUILDING / FL S. S. 553.71(7) ?THRESHOLD |
| | BUILDING" MEANING ANY BUILDING WHICH IS GREATER THAN |
| | (3) STORIES OR 50 FT. IN HEIGHT, OR WHICH HAS AN |
| | ASSEMBLY OCCUPANCY CLASSIFICATION AS DENIED IN THE |
| | FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ. FT. IN |
| | AREA AND AN OCCUPANT CONTENT OF GREATER THAN 500 |
| | PERSONS. |
| | |
| | 3A) 109.3.6.1 THRESHOLD INSPECTION PLAN. THE ENFORCING |
| | AGENCY SHALL REQUIRE A (WRITTEN/ TYPED) SPECIAL |
| | INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON A |
| | THRESHOLD BUILDING PURSUANT TO A STRUCTURAL INSPECTION |
| | PLAN PREPARED BY THE ENGINEER OF RECORD. THE STRUCTURAL |
| | INSPECTION PLAN MUST BE SUBMITTED TO THE ENFORCING |
| | AGENCY PRIOR TO THE ISSUANCE OF A BUILDING PERMIT FOR |
| | THE CONSTRUCTION OF A THRESHOLD BUILDING. THE PURPOSE |
| | OF THE STRUCTURAL INSPECTION PLAN IS TO PROVIDE |
| | SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO THAT |
| | THE BUILDING CAN BE ADEQUATELY INSPECTED FOR COMPLIANCE |
| | WITH THE PERMITTED DOCUMENTS. |
| | |
| | 3B) THRESHOLD INSPECTOR: WPB AMENDMENT 109.3.6.2 W.P.B. |
| | CONSTRUCTION SERVICES DEPARTMENT REQUEST FOR THRESHOLD |
| | BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY FL S S |
| | 553.79(5) FLORIDA STATUTES TO THE MINIMUM INSPECTIONS |
| | REQUIRED BY THIS CODE. THE THRESHOLD INSPECTION FORMS |
| | ARE REQUIRED TO BE FILED OUT BY ALL PARTIES WITH |
| | INTEREST, NOTARIZED AND RETURNED TO THIS OFFICE, AND |
| | REVIEWED AND APPROVED BEFORE PERMIT ISSUANCE WILL TAKE |
| | PLACE. |
| | |
| | 3C) THRESHOLD BLDG., REQUIRED STATEMENT: W.P.B. |
| | AMENDMENT 110.3.7.4.4 ALL PLANS FOR THE BUILDING WHICH |
| | ARE REQUIRED TO BE SIGNED AND SEALED BY THE ARCHITECT |
| | OR ENGINEER OF RECORD CONTAIN A STATEMENT THAT, TO THE |
| | BEST OF THE ARCHITECT'S OR ENGINEER'S KNOWLEDGE, THE |
| | PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE |
| | FIRE-SAFETY STANDARDS AS DETERMINED BY THE LOCAL |
| | AUTHORITY IN ACCORDANCE WITH THIS SECTION AND 633 |
| | FLORIDA STATUTE. |
| | |
| | 3D) FOR THE SPECIAL INSPECTOR PLEASE PROVIDE A RESUME' |
| | OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE |
| | RESUME' MUST BE ACCOMPANIED BY ALL CERTIFICATES AS |
| | SPECIFIED HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE |
| | WILL REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED, |
| | AN INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES |
| | WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST |
| | MEETING THE ABOVE CRITERIA. |
| | |
| | 3E) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR |
| | HISTORY FOR THIS TYPE OF CONSTRUCTION. |
| | |
| | 3F) NOTE FOR PAPER PLANS 3 SETS OF DOCUMENTS ARE |
| | REQUIRED. FOR DIGITAL PLANS, AFTER PERMIT ISSUANCE, |
| | PLEASE E-MAIL THE PERMIT LIBRARIAN OF THE PERMIT BEING |
| | ISSUED, THE PERMIT LIBRARIAN WILL THEN E-MAIL YOU THE |
| | APPROVED AND BATCH STAMPED PLANS SO YOU MAY PRINT YOUR |
| | PLANS, TWO SETS OF PLANS WILL NEED TO BE PRINTED IN |
| | COLOR, (1) FOR THE THRESHOLD INSPECTOR, THE OTHER FOR |
| | THE MEP INSPECTORS OTHER PLANS YOU WISH TO PRINT MAYBE |
| | IN BLACK & WHITE.. |
| | 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| | CODE, CHAPTER 1, ADMINISTRATION, 110.3.7 THRESHOLD |
| | BUILDINGS, GUIDELINES AND POLICIES FOR PROJECTS |
| | CONCERNING SPECIAL INSPECTORS. |
| | |
| | 3G) 110.3.7.4.3 ALL SHORING AND RESHORING PROCEDURES, |
| | PLANS AND DETAILS SHALL BE SUBMITTED TO THE ENFORCEMENT |
| | AGENCY FOR RECORDKEEPING. EACH SHORING AND RESHORING |
| | INSTALLATION SHALL BE SUPERVISED, INSPECTED AND |
| | CERTIFIED TO BE IN COMPLIANCE WITH THE SHORING |
| | DOCUMENTS BY THE CONTRACTOR. |
| | |
| | 3H) PLEASE CALL THE CITY OF WEST PALM BEACH?S AUTOMATED |
| | TELEPHONE INSPECTIONS LINE (561) 805-6700) FOR ALL |
| | BUILDING INSPECTIONS FOR AUDITING OF JOBSITE |
| | INSPECTIONS WITHOUT THIS THE PERMIT EXPIRES IN 6 |
| | MONTHS, ABANDONMENT OF JOB, NO INSPECTION ACTIVITY. |
| | |
| | 3I) 109.3.6 THRESHOLD BUILDINGS, OPERATING GUIDELINES |
| | FOR THRESHOLD INSPECTORS #26. ASSURE THAT THE DESIGNER |
| | HAS REQUIRED ON THE PLANS OR SPECIFICATIONS ONE |
| | MATERIAL, APPROVED FOR FIRE STOPPING PENETRATIONS, FOR |
| | WALLS AND CEILINGS. |
| | 4) PLEASE NOTE THE PROPOSED DEMOLITION PLAN & LIFE |
| | SAFETY SHOWS NEW DOOR OPENINGS ON THE EAST SIDE OF THE |
| | BUILDING WHICH ARE WITHIN ONE FOOT OF THE PROPERTY LINE |
| | AND NEW OUTSWING DOORS THAT TRANSGRESS OVER THE |
| | PROPERTY LINE. PLEASE REVIEW IN THE 2017 FBC-B TABLE |
| | 705.8 0-33 FEET FROM THE PROPERTY LINE (SPRINKLERED) NO |
| | OPENINGS ARE PERMITTED. |
| | 5A) PLEASE NOTE FOR THE LIFE SAFETY PLAN ALSO MISSING |
| | IS THE REQUIREMENT THAT A 1-HOUR FIRE RATING IS |
| | REQUIRED FOR EXTERIOR WALLS BASED ON THE IRE SEPARATION |
| | DISTANCE FOR 0-5 FEET FROM THE PROPERTY LINE SEE TABLE |
| | 602 OF THE FBC-B. |
| | 5B) PLEASE NOTE WHEN YOU LOOK AT GEO NAV COUNTY ARIAL |
| | MAPS TO THE EAST AND WEST ARE STEPPED BUILDINGS BOTH A |
| | BIT HIGHER THAN THE PARAPET OF 522 WITH WINDOWS IN EACH |
| | BUILDING AT THE PROPERTY LINE. THE EAST BUILDING DOES |
| | HAVE A WINDOW WELL SECTION THAT STEPS BACK 5 FEET |
| | HORIZONTAL DISTANCE FROM THE PROPERTY LINE. PLEASE |
| | PROVIDE IF THESE BUILDINGS HAVE AREAL RIGHTS OVER 522 |
| | IF NOT THEN YOU WILL NEED TO SHOW COMPLIANCE WITH 2020 |
| | FBC-BUILDING SECTIONS: |
| | 706.6.1 STEPPED BUILDINGS. |
| | 706.7 COMBUSTIBLE FRAMING IN FIRE WALLS. |
| | 706.8. OPENINGS. |
| | |
| | 6) THE PROPOSED DEMO PLAN FOR THE 1ST FLOOR SHOWS THE |
| | REMOVAL OF MOST OF THE 1ST FLOOR SLAB. HAS THIS BEEN |
| | VERIFIED THAT THIS IS STEM WALL CONSTRUCTION, OTHERWISE |
| | YOU WILL LOSE THE EXTERIOR WALL ELEMENTS? 102.1.2 |
| | ADDITIONAL INFORMATION IS REQUIRED. |
| | |
| | 7A) THE LIFE SAFETY PLAN DOES NOT SHOW IN THE BUILDING |
| | DATA LIVE LOAD INFORMATION FOR ASSEMBLY AREA FLOOR |
| | LOADING, NEW STAIRS AND EXITS, HANDRAILS AND GUARDS. |
| | 2017 FBC-B TABLE 1607.1. |
| | 7B) THE LIFE SAFETY PLAN DOES NOT INCORPORATE INTO THE |
| | BUILDING DATA THE BUILDING RISK CATEGORY FACTOR SINE |
| | THERE IS AS SHOWN NOW 496 OCCUPANTS. NEITHER DOES THE |
| | S-1 SHEET IDENTIFY THE BUILDING RISK CATEGORY FACTOR. |
| | THE S-1 SHEET DOES IDENTIFY THE VULT WIND SPEED OF 170 |
| | MPH, 3 SECOND GUST. PLEASE REVIEW THE 2017 FBC-B TABLE |
| | 1604.5 RISK CATEGORY III. BUILDINGS AND OTHER |
| | STRUCTURES WHOSE PRIMARY OCCUPANCY IS PUBLIC ASSEMBLY |
| | WITH AN OCCUPANT LOAD OF GREATER THAN 300 HAS A RISK |
| | CATEGORY III. PLEASE REVIEW IN THE 2017 FBC-B FIGURE |
| | 1609.3(2) OR 180 MPH VULT. |
| | |
| | 8A) SHEET S-1 STATES THE PLANS WERE DESIGNED UNDER THE |
| | 2017 FBC-B AND ASCE 7-10 AND ALTERATION LEVEL 2. PLEASE |
| | UPDATE THE CODES TO 2017 FBC-B ASCE 7-10, RICK CATEGORY |
| | III/ 180 MPH VULT AND ALTERATION LEVEL III, AND NEW |
| | VERTICAL ADDITION UNDER THE 2017 EXISTING BUILDING CODE |
| | SECTION 1103.2. NOTE THERE IS NO EXPOSURE CATEGORY |
| | GIVEN. |
| | |
| | 8B) WITH THE BUILDING RISK CATEGORY CHANGED THE WIND |
| | DESIGN PRESSURES FOR THE COMPONENTS AND CLADDING WILL |
| | ALSO BE AFFECTED AND INCREASED. TO 2017 FBC-B ASCE |
| | 7-10, RICK CATEGORY III/ 180 MPH VULT. |
| | |
| | 8C) NOTE, DEPENDING ON THE OUTCOME OF 2D & 3 THIS MAY |
| | BE CONSIDERED A THRESHOLD BUILDING. THIS DETERMINATION |
| | SHOULD BE MADE BY THE NEXT REVIEW CYCLE. |
| | |
| | 9A) COMPONENTS & CLADDING. 2017 FBC-B 1609.1.2 |
| | PROTECTION OF OPENINGS, 1609.6.4.4.1 COMPONENTS & |
| | CLADDING. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS, |
| | ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3 NOV. 01/ |
| | 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION |
| | SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: |
| | (31)(A) EXTERIOR DOORS, MULLIONS & ROOF HATCHES. |
| | (B) WINDOWS & MULLIONS |
| | (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL |
| | LOUVERS, EFIS SYSTEMS, |
| | (D) ROOFING PRODUCTS AND ASSEMBLIES, LIGHTWEIGHT |
| | CONCRETE INSULATION, ROOF TOP VENTILATORS |
| | (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C |
| | STANDS |
| | |
| | 9B) W. P. B. 107.3.4. PRODUCT APPROVALS. THOSE PRODUCTS |
| | WHICH ARE REGULATED BY FLORIDA ADMINISTRATIVE CODE RULE |
| | 61G20 SHALL BE REVIEWED AND APPROVED IN WRITING (SHOP |
| | DRAWING STAMP OF APPROVAL) BY THE DESIGNER OF RECORD |
| | PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC. |
| | |
| | 9C) 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF |
| | THIS SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE |
| | PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE |
| | TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO |
| | THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD. |
| | DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR |
| | APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED |
| | DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST |
| | THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS |
| | FOR REVIEW BY THE BUILDING OFFICIAL. |
| | |
| | DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE |
| | SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN |
| | RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD |
| | THEM TO THE BUILDING OFFICIAL WITH A NOTATION |
| | INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE |
| | BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO |
| | THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL |
| | ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED |
| | SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING |
| | OFFICIAL. |
| | |
| | 9D) IDENTIFY GLAZING/ MULLIONS. PLEASE IDENTIFY ON THE |
| | PRODUCT APPROVAL BEFORE SUBMITTING TO DESIGNER OF |
| | RECORD AND BEFORE SUBMISSION TO THE BUILDING |
| | DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, PLEASE |
| | IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF GLAZING, |
| | MULLION SIZE, LENGTH IF UNREINFORCED OR REINFORCED |
| | INFORMATION IF REQUIRED, ATTACHMENTS AND ASSOCIATE |
| | PRESSURES FOR EACH OPENING SIZE. 2017 FBC-B 1405.13.1 |
| | INSTALLATION. WINDOWS AND DOORS SHALL BE INSTALLED IN |
| | ACCORDANCE WITH APPROVED MANUFACTURER?S INSTRUCTIONS. |
| | FASTENER SIZE AND SPACING SHALL BE PROVIDED IN SUCH |
| | INSTRUCTIONS AND SHALL BE CALCULATED BASED ON MAXIMUM |
| | LOADS AND SPACING USED IN THE TESTS. |
| | |
| | 10) THE LS-1 LIFE SAFETY PLAN NOR SHEET A-8.0 STAIR |
| | PLAN SHOW WHAT THE TRAVEL DISTANCE IS FOR THE NEW FRONT |
| | STAIRWAY ( EXIT ACCESS STAIRWAY) ON THE 2ND FLOOR DOWN |
| | THE STAIRS (PARALLEL TO STAIRS) AND DISTANCE TO THE |
| | FRONT ENTRY/ EXIT DOOR. PLEASE DEMONSTRATE COMPLIANCE |
| | WITH TABLE 1017.2 AND SECTION 1017.3.1 EXIT ACCESS |
| | STAIRWAYS OF THE 2017 FBC-B. |
| | |
| | 11A) SHEET A-8.0 STAIR PLANS IN THE BOTTOM RIGHT CORNER |
| | INDICATES THE RISERS ARE TO BE 7 INCHES PLUS, PLEASE |
| | NOTE SECTION 1011.5.2 RISER HEIGHT IS TO BE BETWEEN 4 |
| | INCHES MINIMUM TO 7 INCHES MAXIMUM. |
| | |
| | 11B) THE LEFT SIDE OF THIS SHEET, (CIRCLED) THE GUARD |
| | AND HANDRAIL ARE DRAWN WRONG THEY STOP ON TOP OF THE |
| | FIRST TREAD THEY DO NOT GO TO THE LANDING, BOTH THE |
| | HANDRAIL AND GUARD WOULD BE TOO HIGH, ESPECIALLY THE |
| | HANDRAIL. SEE 114.2 HEIGHT. SEE CIRCLED RED LINE |
| | DRAWING. |
| | |
| | 12A) PLEASE REVIEW THE D-1.0 DEMO SHEET. THE PLAN SHOWS |
| | THE PROPOSED ELECTRICAL ROOM TO HAVE A PORTION OF THE |
| | WALL REMOVED. THE LIFE SAFETY SHEET SHOWS A NEW STAIR |
| | AND DOORWAY GOING TO THE ELECTRICAL ROOM. THERE IS A |
| | SECOND STAIRWAY THAT IS LEADING FROM THE ROOF LEVEL AND |
| | ENDING WITHIN THE COURTYARD, IT APPEARS TO BE AN OPEN |
| | OR EXTERIOR STAIRWAY. SHEET A-8.0 DETAIL # 2 SHOWS THE |
| | ELECTRICAL DOOR DIRECTLY BENEATH THE OPEN STAIRS |
| | LEADING FROM THE ROOF. SECTION 1027.6 EXTERIOR EXIT |
| | STAIRWAY PROTECTION. THE STAIRWAY SHALL BE SEPARATED |
| | FROM THE INTERIOR OF THE BUILDING AS REQUIRED IN |
| | SECTION 1023.2. |
| | OPENINGS SHALL BE LIMITED TO THOSE NECESSARY FOR EGRESS |
| | FROM NORMALLY OCCUPIED SPACES, THIS WOULD NOT BE AN |
| | ELECTRICAL ROOM. |
| | |
| | 12B) THIS SAME DETAIL # 2 IS ADJACENT TO THE PROPERTY |
| | LINE. THIS DETAIL DOES NOT SHOW COMPLIANCE WITH |
| | 1027.5(1) ADJACENT LOTS. |
| | |
| | 12C) THE LS-1 SHEET 1ST FLOOR OUTSIDE DINING AREA SHOWS |
| | IT IS AN ENCLOSED COURTYARD. SINCE THIS IS CONSIDERED A |
| | COURTYARD THE OCCUPANT LOAD OF THE COURTYARD AND 1ST |
| | FLOOR ARE TO BE COMBINED TO SHOW THE TOTAL NUMBER OF |
| | OCCUPANTS LEADING THROUGH THE BACK GATES AND LEADING TO |
| | THE PUBLIC WAY. SHOW COMPLIANCE WITH 1004.5 OUTDOOR |
| | AREAS OF THE 2017 FBC-B. |
| | |
| | 13) SHEETS A-3.0, MEP 3.4 & MEP3-4.1 ALL SHOW |
| | MECHANICAL EQUIPMENT ON TOP OF THE EXISTING ROOF. THERE |
| | ARE NO DETAILS FOR THE ROOF TOP PENETRATIONS THROUGH |
| | THE TWIN T?S NOR HOW TO TIE DOWN THE CURBING OR ROOFTOP |
| | EQUIPMENT, AIR HANDLERS, INTAKE AND EXHAUST VENTS AND |
| | OR RACKS AND STANDS. |
| | |
| | 107.2.1.2 FOR ROOF ASSEMBLIES REQUIRED BY THE CODE, THE |
| | CONSTRUCTION DOCUMENTS SHALL ILLUSTRATE, DESCRIBE AND |
| | DELINEATE THE TYPE OF ROOFING SYSTEM, MATERIALS, |
| | VENTING, FASTENING REQUIREMENTS, FLASHING REQUIREMENTS |
| | AND WIND RESISTANCE RATING THAT ARE REQUIRED TO BE |
| | INSTALLED. PRODUCT EVALUATION AND INSTALLATION SHALL |
| | INDICATE COMPLIANCE WITH THE WIND CRITERIA REQUIRED FOR |
| | THE SPECIFIC SITE. |
| | |
| | 2020 FBC-M- 301.15 WIND RESISTANCE. MECHANICAL |
| | EQUIPMENT, APPLIANCES AND SUPPORTS THAT ARE EXPOSED TO |
| | WIND SHALL BE DESIGNED AND INSTALLED TO RESIST THE WIND |
| | PRESSURES DETERMINED IN ACCORDANCE WITH THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | FBC-B-1609.6.4.4.1 COMPONENTS AND CLADDING. WIND |
| | PRESSURE FOR EACH COMPONENT OR CLADDING ELEMENT IS TO |
| | BE DESIGNED FOR WIND PRESSURES COMPONENTS AND |
| | ATTACHMENTS. |
| | |
| | LATERAL FORCE-RESISTING SYSTEM |
| | FOR ALL ROOF TOP EQUIPMENT, CURBS, FANS OR A/C STANDS, |
| | AND OR VENTS, DETAILED ATTACHMENT TO THE ROOF FRAMING & |
| | DECK AS WELL AS FROM THE CURB OR ROOF STAND TO THE |
| | EQUIPMENT ABOVE. |
| | |
| | 2017 FBC-B 1604.4 ANALYSIS. LOAD EFFECTS ON STRUCTURAL |
| | MEMBERS AND THEIR CONNECTIONS SHALL BE DETERMINED BY |
| | METHODS OF STRUCTURAL ANALYSIS THAT TAKE INTO ACCOUNT |
| | EQUILIBRIUM, GENERAL STABILITY, GEOMETRIC COMPATIBILITY |
| | AND BOTH SHORT- AND LONG-TERM MATERIAL PROPERTIES. |
| | EVERY STRUCTURE SHALL BE DESIGNED TO RESIST THE |
| | OVERTURNING EFFECTS CAUSED BY THE LATERAL FORCES |
| | SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR WIND |
| | LOADS. |
| | |
| | THE ROOF TOP A/C STAND PRODUCT APPROVALS, TO BE |
| | REVIEWED BY THE DESIGNER OF RECORD. PLEASE IDENTIFY THE |
| | FOLLOWING REQUIREMENTS CALCULATING THE AREA (SIDE VIEW) |
| | OF THE ROOF TOP COMPRESSORS, CONFIGURATION ON STAND, |
| | THE MEAN ROOF HEIGHT OF THE STAND AND COMPRESSORS, |
| | WEIGHT, CIRCLED THE DESIGN PARAMETERS IN THE TABLES, |
| | ANCHORS AND UPLIFT VERSES MOMENT FOR THE UNIT TO THE |
| | STAND AND THE STAND TO THE ROOF. THE PRODUCT APPROVAL |
| | IS TO BE REVIEWED BY THE DESIGNER OF RECORD, APPROVED |
| | BEFORE SUBMISSION TO THE BUILDING DEPARTMENT. |
| | |
| | 14) SHEET MEP3-4.1 ON THE AIR COMPRESSOR TO RACK STATES |
| | THE WINDS TO WITHSTAND 170 MPH. PLEASE CHANGE SINCE THE |
| | RISK FACTOR IS AN III MEETING THE 180 VULT WIND DESIGN. |
| | |
| | |
| | 15) THE LIFE SAFETY PLANS DO NOT SHOW ANY ACCESSIBLE |
| | FEATURES FOR SEATING, COUNT OF SEATS, NOR BAR TOP |
| | MODIFICATIONS FOR ACCESSIBLE SEATING. THE LIFE SAFETY |
| | SHEET DOES NOT SHOW COMPLIANCE WITH THE 2017 |
| | FBC-ACCESSIBILITY CODE. |
| | 15A) 226.1 WHERE DINING SURFACES ARE PROVIDED FOR THE |
| | CONSUMPTION OF FOOD OR DRINK, AT LEAST 5 PERCENT OF THE |
| | SEATING SPACES AND STANDING SPACES AT THE DINING |
| | SURFACES SHALL COMPLY WITH 902. |
| | |
| | 15B) 226.2 DISPERSION. DINING SURFACES AND WORK |
| | SURFACES REQUIRED TO COMPLY WITH 902 SHALL BE DISPERSED |
| | THROUGHOUT THE SPACE OR FACILITY CONTAINING DINING |
| | SURFACES AND WORK SURFACES. |
| | |
| | 15C) 206.2.5 206.2.5 RESTAURANTS AND CAFETERIAS. IN |
| | RESTAURANTS AND CAFETERIAS, AN ACCESSIBLE ROUTE SHALL |
| | BE PROVIDED TO ALL DINING AREAS, INCLUDING RAISED OR |
| | SUNKEN DINING AREAS, AND OUTDOOR DINING AREAS. |
| | |
| | 15D) 902.1 DINING SURFACES AND WORK SURFACES SHALL |
| | COMPLY WITH 902.2 AND 902.3. ADVISORY 902.1 GENERAL. |
| | DINING SURFACES INCLUDE, BUT ARE NOT LIMITED TO, BARS, |
| | TABLES, LUNCH COUNTERS, AND BOOTHS. EXAMPLES OF WORK |
| | SURFACES INCLUDE WRITING SURFACES, STUDY CARRELS, |
| | STUDENT LABORATORY STATIONS, BABY CHANGING AND OTHER |
| | TABLES OR FIXTURES FOR PERSONAL GROOMING, COUPON |
| | COUNTERS, AND WHERE COVERED BY THE ADA SCOPING |
| | PROVISIONS, EMPLOYEE WORK STATIONS. |
| | |
| | 15E)(1) 902.2 CLEAR FLOOR OR GROUND SPACE. A CLEAR |
| | FLOOR SPACE COMPLYING WITH 305 POSITIONED FOR A FORWARD |
| | APPROACH SHALL BE PROVIDED. KNEE AND TOE CLEARANCE |
| | COMPLYING WITH 306 SHALL BE PROVIDED. |
| | |
| | 15E)(2) 902.3 HEIGHT. THE TOPS OF DINING SURFACES AND |
| | WORK SURFACES SHALL BE 28 INCHES MINIMUM AND 34 INCHES |
| | MAXIMUM ABOVE THE FINISH FLOOR OR GROUND. |
| | |
| | 16) I MIGHT OF MISSED THE PLAN BUT I DID NOT SEE |
| | ARCHITECTURAL SHEETS WITH THE RESTROOM CONFIGURATIONS, |
| | AND DETAILS FOR ACCESSIBLE ELEMENTS WITHIN THE REST |
| | ROOMS NOR COMPLIANCE WITH THE 2020 ACCESSIBILITY CODE. |
| | |
| | 17) I MIGHT OF MISSED THE PLAN BUT I DID NOT SEE |
| | ARCHITECTURAL SHEETS WITH THE RESTROOM FINISHES AND |
| | COMPLIANCE WITH |
| | 2017 FBC-B 1210.2.2. WALLS & PARTITIONS. THIS COMMENT |
| | IS A RESULT OF THE BUILDING OFFICIAL INTERPRETATION ON |
| | 06/2020. IN RESTROOMS & SERVICE SINK AREAS EPOXY PAINT |
| | IS NO LONGER CONSIDERED A SMOOTH HARD, NON-ABSORBENT |
| | SURFACE. |
| | |
| | 17A) 1210.2.2 WALLS & PARTITIONS WITHIN 2 FEET OF |
| | SERVICE SINKS, URINALS, AND WATER CLOSETS SHALL HAVE A |
| | SMOOTH, HARD, NON-ABSORBENT SURFACE TO A HEIGHT OF NOT |
| | LESS THAN 4 FEET ABOVE THE FLOOR, EXCEPT FOR STRUCTURAL |
| | ELEMENTS, THE MATERIAL USED IN SUCH WALLS SHALL BE OF A |
| | TYPE THAT IS NOT ADVERSELY AFFECTED BY MOISTURE. |
| | |
| | 17B) 2509.1. WET AREAS. SHOWERS AND PUBLIC TOILET WALLS |
| | SHALL COMPLY WITH 1210.2. |
| | |
| | 17C) 1210.2. FINISH MATERIALS. WALLS, BASE, FLOORS AND |
| | PARTITIONS IN TOILET AND BATHROOMS SHALL COMPLY WITH |
| | SECTIONS 1210.1 THROUGH 1210.4. |
| | |
| | 18) IMPACT FEES - DIGITAL SUBMITTALS: PLANS WILL BE |
| | REVIEWED BY THE PBC IMPACT FEE OFFICE DIGITALLY VIA |
| | PROJECT DOX UPON NOTIFICATION BY THIS OFFICE. |
| | NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST FINAL |
| | FORM. YOU MAY COORDINATE WITH THE IMPACT FEE OFFICE AT |
| | (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL IMPACT |
| | FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME THE |
| | FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM CAN |
| | BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINISTRAT |
| | ION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON |
| | APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE RECEIPT TO |
| | YOUR PROJECT OR EMAIL IT TO [email protected] . |
| | |
| | 19) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS |
| | REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT |
| | REVIEW CYCLE. |
| | |
| | PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID |
| | 19 |
| | IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS |
| | 561-718-9724. |
| | WORKING HOURS ARE MON.- WED. 8:00 AM- NOON. PART-TIME/ |
| | RETIRED. |
| | |
| | JAMES A. WITMER BN, PX, SFP, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT |
| | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 |
| | TEL: 561-805-6717 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | DEVELOPMENT SERVICES HOME PAGE |
| | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| | |
| | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| | |
| | MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF |
| | FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |