| 2020-12-02 09:35:21 | 12/02/20 1ST GAS REVIEW**DENIED** WITH COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1. THE CITY OF WEST PALM BEACH HAS NO RECORD OF |
| | EXISTING TANK-LESS GAS ON STRUCTURE, THERE WAS A PERMIT |
| | IN 2007 FOR A 35 BTU?S HEATER IN SHED AND A 30 BTU?S |
| | BBQ. A FULL EVALUATION OF ALL GAS EQUIPMENT WILL BE |
| | NEEDED AT THIS TIME. PLEASE PROVIDE THE FOLLOWING ITEM. |
| | |
| | 2. GAS RISER DIAGRAM REQUIRED PER THE WPB AMENDMENTS TO |
| | THE FBC SEC. 107.3.5.3 (12) RESIDENTIAL GAS. |
| | |
| | 3. SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS THE |
| | LENGTH OF ALL CUT SECTIONS OF PIPE PER THE 2017 FBC |
| | RES. SECS. G2413.4.1, G2413.4.2. |
| | |
| | 4. TYPE OF GAS (LP OR NATURAL) PER THE WPB AMENDMENTS |
| | TO THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION |
| | DOCUMENTS. |
| | |
| | 5. SHOW THE LOCATION OF ALL MP (STEP-DOWN) REGULATORS. |
| | A LISTED SHUTOFF VALVE SHALL BE INSTALLED IMMEDIATELY |
| | AHEAD OF EACH MP REGULATOR PER THE 2017 FBC RES. SEC. |
| | G2420.4. |
| | |
| | 6. INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM |
| | ON THE PLAN PER THE 2017 FBC FG SEC. 402.2 OR 2017 FBC |
| | RES. SEC. G2413.2. |
| | |
| | 7. SUBMIT MANUFACTURER?S SPECIFICATION |
| | SHEETS/INSTALLATION MANUAL FOR TANK-LESS ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH 2017 FBC FG |
| | SEC.305.1 OR 2017 FBC RES. SEC. G2408.1. |
| | |
| | 8. LIST THE BTU LOAD OF EACH APPLIANCE AND THE TOTAL |
| | BTU LOAD ON THE SYSTEM. REFER TO THE 2017 FBC RES. |
| | SECS. G2413.3, G2413.4, AND TABLES G2413.4 (1) THROUGH |
| | G2413.4 (21). |
| | |
| | 9. SUBMIT THE SIZING TABLE USED IN THE DESIGN FOR THE |
| | GAS SYSTEM OR PLACE A NOTE ON BOTH SETS OF PLANS |
| | LISTING THE SIZING TABLES FROM GAS CODES OR ANOTHER |
| | STANDARD THAT WERE USED IN THE DESIGN OF THIS SYSTEM |
| | PER THE 2017 FBC RES. SEC. G2413.3. |
| | |
| | 10. PLEASE SHOW ALL UNIONS IN FRONT OF REGULATOR 1? OF |
| | EITHER SIDE PER THE 2017 FBC RES. SEC G2421.2 OR 2017 |
| | FBC FG SEC 410.2. |
| | |
| | 11. PLEASE LABEL THE SHUTOFF VALVE ON GAS ISOMERIC PER |
| | THE 2017 FBC RES. SEC. G2401.1.3. |
| | |
| | 12. SHOW DRIP LEG ON EQUIPMENT INSTALLED, EXCEPT FOR |
| | APPLIANCES, RANGE, DRYERS & OD GRILLS PER THE 2017 FBC |
| | RES. SEC. G2419.2. |
| | |
| | 13. PLEASE REFER TO THE SPECIFICATION ON THE TANK-LESS |
| | AS IT SHOWS A WINDOW ABOVE, GIVE THE LOCATION AND |
| | DISTANCE OF ANY OPERABLE DOORS OR WINDOWS IN RELATION |
| | TO THE WATER HEATER. THE LOCATION OF THE WATER HEATER |
| | SHALL COMPLY WITH THE MANUFACTURER'S INSTALLATION |
| | INSTRUCTIONS PER THE WPB AMENDMENTS TO THE FBC SEC. |
| | 107.2.1. INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | 14. IF TANK-LESS REQUIRES CONDENSATE DRAIN IT BE 1' |
| | AWAY FROM STRUCTURE PER THE 2017 FBC SEC R318.5. |
| | |
| | 15. WATER PIPES NOT IN CONDITION SPACE NEED TO BE |
| | INSULATED WITH A MINIMUM R-3 PER THE 2017 FBC SEC. RE |
| | 403.5.3. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA |
| | |
| | LUIS A. CRESPO |
| | PLUMBING PLAN EXAMINER / INSPECTOR |
| | EMAIL: [email protected] OFFICE: 561 805-6720 |
| | |