Plan Review Notes
Plan Review Notes For Permit 20111059
Permit Number 20111059
Review Stop G
Sequence Number 2
Notes
Date Text
2020-12-14 18:08:213RD REVIEW FBC-2017 RES. FUEL GAS
 PERMIT- 20111059
 12/14/2020
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) GAS RISER: THE EHD 18 CSST PIPING TO THE 58,200 BTUH
 COOKTOP IS UNDERSIZED PER TABLE 402.4(15) FBC FG.
 EHD-23 IS REQUIRED BASED ON SECTIONS 402.4.1 AND
 402.4.2. THE PIPE RUN FROM THE LOW PRESSURE REGULATOR
 TO THE COOK TOP IS 77 FT. PLEASE CORRECT THE RISER.
  
 2) THE PRINTED NAME AND SIGNATURE OF THE FL. LICENSED
 GAS CONTRACTOR JOSEPH PETRILLO SHALL BE ON THE GAS
 RISER DRAWING IN COMPLIANCE WITH SECTION 107.2.1 WPB,
 AND FLORIDA STATUTES 471.003(2)(H) & 471.025. THE
 DRAWING APPEARS TO BEAR THE SIGNATURE AND SEAL OF THE
 NOTARY PUBLIC.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  