| 2020-12-14 18:08:21 | 3RD REVIEW FBC-2017 RES. FUEL GAS |
| | PERMIT- 20111059 |
| | 12/14/2020 |
| | |
| | CODES IN EFFECT: |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| | EDITION 2017 |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) GAS RISER: THE EHD 18 CSST PIPING TO THE 58,200 BTUH |
| | COOKTOP IS UNDERSIZED PER TABLE 402.4(15) FBC FG. |
| | EHD-23 IS REQUIRED BASED ON SECTIONS 402.4.1 AND |
| | 402.4.2. THE PIPE RUN FROM THE LOW PRESSURE REGULATOR |
| | TO THE COOK TOP IS 77 FT. PLEASE CORRECT THE RISER. |
| | |
| | 2) THE PRINTED NAME AND SIGNATURE OF THE FL. LICENSED |
| | GAS CONTRACTOR JOSEPH PETRILLO SHALL BE ON THE GAS |
| | RISER DRAWING IN COMPLIANCE WITH SECTION 107.2.1 WPB, |
| | AND FLORIDA STATUTES 471.003(2)(H) & 471.025. THE |
| | DRAWING APPEARS TO BEAR THE SIGNATURE AND SEAL OF THE |
| | NOTARY PUBLIC. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |