Plan Review Notes
Plan Review Notes For Permit 20111059
Permit Number 20111059
Review Stop G
Sequence Number 1
Notes
Date Text
2020-12-02 17:14:172ND REVIEW FBC-2017 RES. FUEL GAS
 PERMIT- 20111059
 12/2/2020
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE A DESCRIPTION OF WORK ON THE PERMIT
 APPLICATION AND A VALUE FOR GAS PIPING AND APPLIANCE
 INSTALLATIONS- SECTIONS 105.1, 107.1, AND 109.3 WPB.
 THE TOTAL VALUE OF THE PROJECT SHALL INCLUDE LABOR,
 MATERIAL, EQUIPMENT AND APPLIANCES. SUBMIT A COPY OF
 THE SIGNED CONTRACT AND/OR ESTIMATES AND INVOICES TO
 VERIFY THE PROJECT COSTS. COSTS ASSOCIATED WITH THE GAS
 PIPING AND APPLIANCE INSTALLATIONS THAT WERE ACCOUNTED
 FOR UNDER THE MASTER PERMIT- 20010400 CAN BE EXCLUDED,
 HOWEVER DOCUMENTATION OF THOSE COSTS MUST BE PROVIDED.
  
 2) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE
 TANKLESS WATER HEATER, COOKTOP, AND THE DRYER. SUBMIT
 ONLY THE SHEETS THAT SHOW BTUH CAPACITIES AND INPUT
 PRESSURES. PLEASE NOTE THAT PERMITS FOR THE POOL AND
 GENERATOR HAVE NOT BEEN SUBMITTED. CLARIFY HOW THE BTUH
 LOADS FOR THE POOL HEATER AND GENERATOR WERE
 DETERMINED- SECTION G2408.1 FBC RES.
  
 3) GAS RISER:
  
 A) INDICATE A NEW OR EXISTING GAS METER AND SHOW THE
 TYPE AND SIZE OF MAIN SUPPLY RISER AT THE METER-
 G2412.8 RES.
  
 B) THE PIPE SIZING TABLES 402.4(13) AND 402.4(20) ARE
 FOR LOW PRESSURE SEMIRIGID COPPER TUBING AND PE. THERE
 IS NO COPPER SHOWN ON THE RISER AND THE PE PIPING IS 2
 PSI. PLEASE PROVIDE THE CORRECT SIZING TABLES FOR ALL
 TYPES OF PIPING RELATIVE TO THE GAS PRESSURES- REFER TO
 TABLES G2413.4(1)- G2413.4(8) FBC RES. PLEASE NOTE THAT
 TABLES 402.4(1) AND 402.4(3) ARE BOTH LOW PRESSURE
 TABLES FOR SCHEDULE 40 GALVANIZED. WHICH TABLE IS
 APPLICABLE TO THE PROJECT.
  
 C) SHOW THE TYPES AND SIZES OF RISER PIPES SUPPLYING
 THE TWH, POOL HEATER, AND GENERATOR- SECTION G2413.3.
  
 D) SHOW GAS-TIGHT CAPS FOR THE SUPPLY LINES TO THE
 FUTURE POOL HEATER AND GENERATOR- G2415.15 FBC RES.
  
 E) SHOW THE OUTLET PRESSURE AT THE REGULATOR SHOWN ON
 THE 1 IN. GALV. RISER- G2421.2.
  
 F) SHOW THE REQUIRED PIPE UNIONS WITHIN 1 FT. OF EITHER
 SIDE OF THE REGULATOR- SECTION G2421.2(7).
  
 G) SHOW THE EHD'S OF THE 1 IN. AND 1/2 IN. CSST-
 SECTION G2413.4 AND INDICATE THE PIPE SIZING TABLE
 USED. A COMPLETE REVIEW OF THE SIZING CANNOT BE
 ACCOMPLISHED AT THIS TIME.
  
 H) SHOW THE TYPE AND SIZE OF UNDERGROUND GAS PIPING TO
 THE COOKTOP- SECTION G2413.3.
  
 I) SHOW THE TYPE AND SIZE OF PIPE SLEEVE- SECTIONS
 G2415.14 AND SHOW HOW IT WILL BE PROTECTED FROM
 CORROSION- SECTION G2415.11.
  
 J) SHOW HOW THE SLEEVE VENT WILL BE INSTALLED TO
 PREVENT THE ENTRANCE OF INSECTS- SECTION G2415.14.1.
  
 3) SUBMIT MARKED UP OR HIGHLIGHTED SPECS SHOWING THE
 SELECTED MODELS, THE MAX INLET AND OUTLET SIZES AND
 PRESSURES AND ORIFICE SIZES.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  