| 2020-12-02 17:14:17 | 2ND REVIEW FBC-2017 RES. FUEL GAS |
| | PERMIT- 20111059 |
| | 12/2/2020 |
| | |
| | CODES IN EFFECT: |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| | EDITION 2017 |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) PROVIDE A DESCRIPTION OF WORK ON THE PERMIT |
| | APPLICATION AND A VALUE FOR GAS PIPING AND APPLIANCE |
| | INSTALLATIONS- SECTIONS 105.1, 107.1, AND 109.3 WPB. |
| | THE TOTAL VALUE OF THE PROJECT SHALL INCLUDE LABOR, |
| | MATERIAL, EQUIPMENT AND APPLIANCES. SUBMIT A COPY OF |
| | THE SIGNED CONTRACT AND/OR ESTIMATES AND INVOICES TO |
| | VERIFY THE PROJECT COSTS. COSTS ASSOCIATED WITH THE GAS |
| | PIPING AND APPLIANCE INSTALLATIONS THAT WERE ACCOUNTED |
| | FOR UNDER THE MASTER PERMIT- 20010400 CAN BE EXCLUDED, |
| | HOWEVER DOCUMENTATION OF THOSE COSTS MUST BE PROVIDED. |
| | |
| | 2) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE |
| | TANKLESS WATER HEATER, COOKTOP, AND THE DRYER. SUBMIT |
| | ONLY THE SHEETS THAT SHOW BTUH CAPACITIES AND INPUT |
| | PRESSURES. PLEASE NOTE THAT PERMITS FOR THE POOL AND |
| | GENERATOR HAVE NOT BEEN SUBMITTED. CLARIFY HOW THE BTUH |
| | LOADS FOR THE POOL HEATER AND GENERATOR WERE |
| | DETERMINED- SECTION G2408.1 FBC RES. |
| | |
| | 3) GAS RISER: |
| | |
| | A) INDICATE A NEW OR EXISTING GAS METER AND SHOW THE |
| | TYPE AND SIZE OF MAIN SUPPLY RISER AT THE METER- |
| | G2412.8 RES. |
| | |
| | B) THE PIPE SIZING TABLES 402.4(13) AND 402.4(20) ARE |
| | FOR LOW PRESSURE SEMIRIGID COPPER TUBING AND PE. THERE |
| | IS NO COPPER SHOWN ON THE RISER AND THE PE PIPING IS 2 |
| | PSI. PLEASE PROVIDE THE CORRECT SIZING TABLES FOR ALL |
| | TYPES OF PIPING RELATIVE TO THE GAS PRESSURES- REFER TO |
| | TABLES G2413.4(1)- G2413.4(8) FBC RES. PLEASE NOTE THAT |
| | TABLES 402.4(1) AND 402.4(3) ARE BOTH LOW PRESSURE |
| | TABLES FOR SCHEDULE 40 GALVANIZED. WHICH TABLE IS |
| | APPLICABLE TO THE PROJECT. |
| | |
| | C) SHOW THE TYPES AND SIZES OF RISER PIPES SUPPLYING |
| | THE TWH, POOL HEATER, AND GENERATOR- SECTION G2413.3. |
| | |
| | D) SHOW GAS-TIGHT CAPS FOR THE SUPPLY LINES TO THE |
| | FUTURE POOL HEATER AND GENERATOR- G2415.15 FBC RES. |
| | |
| | E) SHOW THE OUTLET PRESSURE AT THE REGULATOR SHOWN ON |
| | THE 1 IN. GALV. RISER- G2421.2. |
| | |
| | F) SHOW THE REQUIRED PIPE UNIONS WITHIN 1 FT. OF EITHER |
| | SIDE OF THE REGULATOR- SECTION G2421.2(7). |
| | |
| | G) SHOW THE EHD'S OF THE 1 IN. AND 1/2 IN. CSST- |
| | SECTION G2413.4 AND INDICATE THE PIPE SIZING TABLE |
| | USED. A COMPLETE REVIEW OF THE SIZING CANNOT BE |
| | ACCOMPLISHED AT THIS TIME. |
| | |
| | H) SHOW THE TYPE AND SIZE OF UNDERGROUND GAS PIPING TO |
| | THE COOKTOP- SECTION G2413.3. |
| | |
| | I) SHOW THE TYPE AND SIZE OF PIPE SLEEVE- SECTIONS |
| | G2415.14 AND SHOW HOW IT WILL BE PROTECTED FROM |
| | CORROSION- SECTION G2415.11. |
| | |
| | J) SHOW HOW THE SLEEVE VENT WILL BE INSTALLED TO |
| | PREVENT THE ENTRANCE OF INSECTS- SECTION G2415.14.1. |
| | |
| | 3) SUBMIT MARKED UP OR HIGHLIGHTED SPECS SHOWING THE |
| | SELECTED MODELS, THE MAX INLET AND OUTLET SIZES AND |
| | PRESSURES AND ORIFICE SIZES. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |