| Plan Review Notes For Permit 20111036 |
| Permit Number |
20111036 |
|
| Review Stop |
B |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2021-03-05 14:25:11 | 03/05/21 TALKED TO DUANE BURROWES (ARCH.) TO GO OVER | | | COMMENTS. STAIRS EXTENSION DETAIL WAS CLARIFIED. NEED | | | RAMP EXTENSION DETAILS. JG. | | | | | | | | | SECOND BUILDING REVIEW COMMENTS FOR REVISED DRAWINGS TO | | | COMPLY WITH PROVISO: | | | | | | 1- SHEET A4.2: | | | A)OK. | | | | | | ORIGINAL COMMENT: | | | B)DETAIL #16 RAMP AND STAIR DETAILS: NEED TO SHOW THE | | | TOP AND BOTTOM EXTENSIONS AT RAMP. AND PROVIDE DETAILS. | | | SEC. 505.10.1 FBC-ACCESSIBILITY. | | | | | | RESPONSE: | | | REPEAT COMMENT. NO ADDRESSED. RAMP SHOWS TOP AND BOTTOM | | | EXTENSIONS BUT DETAILS WERE NOT PROVIDED. NOTE: SEE | | | FIGURE 505.10.1 FBC-ACCESSIBILITY FOR HANDRAIL | | | EXTENSION DETAIL AT RAMPS AND PROVIDE DETAIL AS | | | REQUIRED. | | | | | | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY | | | QUESTIONS REGARDING THESE COMMENTS, | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | (561)805-6712 | | | [email protected] |
|