| Plan Review Notes For Permit 20111031 |
| Permit Number |
20111031 |
|
| Review Stop |
B |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2021-04-12 14:06:58 | CONDO BATH REMODEL | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | | AMENDMENTS | | | | | | 3RD REVIEW | | | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | | 1) DOCUMENTS PROVIDED SHOW A CLASS "D" FIRE RATING - | | | MUST SHOW A FIRE CLASSIFICATION OF "C" (COULD BE A, B | | | OR C) FBC 803.1.1 INTERIOR WALL AND CEILING FINISH | | | MATERIALS. | | | INTERIOR WALL AND CEILING FINISH MATERIALS SHALL BE | | | CLASSIFIED IN ACCORDANCE WITH ASTM E84 OR UL 723. SUCH | | | INTERIOR FINISH MATERIALS SHALL BE GROUPED IN THE | | | FOLLOWING CLASSES IN ACCORDANCE WITH THEIR FLAME SPREAD | | | AND SMOKE-DEVELOPED INDEXES. | | | | | | CLASS A: = FLAME SPREAD INDEX 0-25; SMOKEDEVELOPED | | | INDEX 0-450. | | | CLASS B: = FLAME SPREAD INDEX 26-75; SMOKEDEVELOPED | | | INDEX 0-450. | | | CLASS C: = FLAME SPREAD INDEX 76-200; SMOKEDEVELOPED | | | INDEX 0-450. |
|