| Plan Review Notes For Permit 20111008 |
| Permit Number |
20111008 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2020-12-03 13:01:14 | PLAN DENIED | | | 1) REFER TO SECTION 1503.4 MAKEUP AIR REQUIRED. PROVIDE | | | INFORMATION ON | | | KITCHEN HOOD SHOWING MAXIMUM CFM. 2017 BC RESIDENTIAL | | | CODE. | | | 2) REFER TO TABLE 1506.2 DUCT LENGTH. FOR BATHROOM | | | EXHAUST | | | 2017 FBC RESIDENTIAL CODE. | | | 3) SHOW TERMINATION OF DRYER VENT ON PLAN. | | | SECTION 107 FBC 2017. | | | PLAN REVIEW BY HAROLD MOSER | | | [email protected] | | | OFFICE 561-805-6732 | | | FAX 561-805-6676 |
|