| 2020-12-30 17:49:33 | 2ND REVIEW FBC-2017 PLUMBING |
| | PERMIT- 20110978 |
| | 12/30/2020 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | COMMENTS FROM THE 1ST REVIEW LISTED BELOW HAVE NOT BEEN |
| | COMPLETELY ADDRESSED NOTES IN CAP LETERS HAVE BEEN |
| | ADDED FOR CLARIFICATION. |
| | |
| | 1) SHEETS A110, A120, A400, P100: PLEASE PROVIDE THE |
| | ACCESSIBLE WATER CLOSET AND LAVATORY CLEAR FLOOR SPACE |
| | DIMENSIONS, AND TURNING CIRCLE DIAMETERS- SECTIONS |
| | 604.3.1, 606.2, & 304.3.1 FBC ACC. SHEET A400: PLEASE |
| | PROVIDE THE CLEAR FLOOR SPACE DIMENSIONS FOR THE WATER |
| | CLOSETS AND LAVATORIES. |
| | |
| | 3) A400: SHOW THE HEIGHTS OF THE GRAB BARS FROM THE |
| | FINISHED FLOORS TO THE TOPS OF THE GRIPPING SURFACES- |
| | SECTION 609.4 FBC ACC. THE HEIGHTS ARE SHOWN MEASURED |
| | TO THE CENTER OF THE BARS. |
| | |
| | 4) A400: REFER TO SECTIONS 306, 307, AND 602 FBC ACC |
| | AND PROVIDE DRINKING FOUNTAIN INSTALLATION DETAILS AND |
| | ELEVATION VIEWS SHOWING KNEE AND TOE CLEARANCES, SPOUT |
| | HEIGHTS, AND SPOUT LOCATIONS. INDICATE HOW THE |
| | FOUNTAINS WILL BE IN COMPLIANCE WITH SECTION 307.2- |
| | PROTRUDING OBJECTS INTO THE CIRCULATION PATH. DETAILS |
| | TO SHOW ACCESSIBILITY (FBC ACC) COMPLIANCE NOT |
| | PROVIDED. |
| | |
| | 5) A701: CORRECT THE HEIGHT OF THE BREAKROOM COUNTERTOP |
| | SINK TO MAX 34 INCHES- SECTION 606.3 FBC ACC. BREAKIOOM |
| | ELEVATION DETAIL SHOWING 36 IN. MEASUREMENT NOT |
| | CORRECTED. |
| | |
| | 7) P001: THE DRINKING FOUNTAIN DRAIN AND VENT ARE NOT |
| | SHOWN IN THE SANITARY RISER DRAWING- SECTION 107.3.5.3 |
| | WPB. THE SANITARY ISOMETRIC APPEARS TO SHOW THE |
| | DRINKING FOUNTAIN AND BREAKROOM SINK DRAINS CONNECTING |
| | INTO THE BATHROOM HORIZONTAL WET VENT WHICH IS |
| | PROHIBITED PER SECTION 912.1 FBC P: ONLY THE FIXTURES |
| | WITHIN THE BATHROOM GROUPS SHALL CONNECT TO THE |
| | WET-VENTED HORIZONTAL BRANCH DRAIN. ANY ADDITIONAL |
| | FIXTURES SHALL DISCHARGE DOWNSTREAM OF THE HORIZONTAL |
| | WET VENT. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL/PLUMBING PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | [email protected] |
| | |
| | |