Plan Review Notes
Plan Review Notes For Permit 20110978
Permit Number 20110978
Review Stop P
Sequence Number 2
Notes
Date Text
2020-12-30 17:49:332ND REVIEW FBC-2017 PLUMBING
 PERMIT- 20110978
 12/30/2020
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
 COMMENTS FROM THE 1ST REVIEW LISTED BELOW HAVE NOT BEEN
 COMPLETELY ADDRESSED NOTES IN CAP LETERS HAVE BEEN
 ADDED FOR CLARIFICATION.
  
 1) SHEETS A110, A120, A400, P100: PLEASE PROVIDE THE
 ACCESSIBLE WATER CLOSET AND LAVATORY CLEAR FLOOR SPACE
 DIMENSIONS, AND TURNING CIRCLE DIAMETERS- SECTIONS
 604.3.1, 606.2, & 304.3.1 FBC ACC. SHEET A400: PLEASE
 PROVIDE THE CLEAR FLOOR SPACE DIMENSIONS FOR THE WATER
 CLOSETS AND LAVATORIES.
  
 3) A400: SHOW THE HEIGHTS OF THE GRAB BARS FROM THE
 FINISHED FLOORS TO THE TOPS OF THE GRIPPING SURFACES-
 SECTION 609.4 FBC ACC. THE HEIGHTS ARE SHOWN MEASURED
 TO THE CENTER OF THE BARS.
  
 4) A400: REFER TO SECTIONS 306, 307, AND 602 FBC ACC
 AND PROVIDE DRINKING FOUNTAIN INSTALLATION DETAILS AND
 ELEVATION VIEWS SHOWING KNEE AND TOE CLEARANCES, SPOUT
 HEIGHTS, AND SPOUT LOCATIONS. INDICATE HOW THE
 FOUNTAINS WILL BE IN COMPLIANCE WITH SECTION 307.2-
 PROTRUDING OBJECTS INTO THE CIRCULATION PATH. DETAILS
 TO SHOW ACCESSIBILITY (FBC ACC) COMPLIANCE NOT
 PROVIDED.
  
 5) A701: CORRECT THE HEIGHT OF THE BREAKROOM COUNTERTOP
 SINK TO MAX 34 INCHES- SECTION 606.3 FBC ACC. BREAKIOOM
 ELEVATION DETAIL SHOWING 36 IN. MEASUREMENT NOT
 CORRECTED.
  
 7) P001: THE DRINKING FOUNTAIN DRAIN AND VENT ARE NOT
 SHOWN IN THE SANITARY RISER DRAWING- SECTION 107.3.5.3
 WPB. THE SANITARY ISOMETRIC APPEARS TO SHOW THE
 DRINKING FOUNTAIN AND BREAKROOM SINK DRAINS CONNECTING
 INTO THE BATHROOM HORIZONTAL WET VENT WHICH IS
 PROHIBITED PER SECTION 912.1 FBC P: ONLY THE FIXTURES
 WITHIN THE BATHROOM GROUPS SHALL CONNECT TO THE
 WET-VENTED HORIZONTAL BRANCH DRAIN. ANY ADDITIONAL
 FIXTURES SHALL DISCHARGE DOWNSTREAM OF THE HORIZONTAL
 WET VENT.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  