2020-12-03 18:29:201ST REVIEW FBC-2017 PLUMBING
 PERMIT- 20110978
 12/3/2020
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEETS A110, A120, A400, P100: PLEASE PROVIDE THE
 ACCESSIBLE WATER CLOSET AND LAVATORY CLEAR FLOOR SPACE
 DIMENSIONS, AND TURNING CIRCLE DIAMETERS- SECTIONS
 604.3.1, 606.2, & 304.3.1 FBC ACC.
  
 2) A110, A120: SHOW THE CLEAR FLOOR DIAGRAM AND
 DIMENSIONS AT THE NEW BREAKROOM SINK- SECTION 305.3 FBC
 ACC.
  
 3) A400: SHOW THE HEIGHTS OF THE GRAB BARS FROM THE
 FINISHED FLOORS TO THE TOPS OF THE GRIPPING SURFACES-
 SECTION 609.4 FBC ACC.
  
 4) A400: REFER TO SECTIONS 306, 307, AND 602 FBC ACC
 AND PROVIDE DRINKING FOUNTAIN INSTALLATION DETAILS AND
 ELEVATION VIEWS SHOWING KNEE AND TOE CLEARANCES, SPOUT
 HEIGHTS, AND SPOUT LOCATIONS. INDICATE HOW THE
 FOUNTAINS WILL BE IN COMPLIANCE WITH SECTION 307.2-
 PROTRUDING OBJECTS INTO THE CIRCULATION PATH.
  
 5) A701: CORRECT THE HEIGHT OF THE BREAKROOM COUNTERTOP
 SINK TO MAX 34 INCHES- SECTION 606.3 FBC ACC.
  
 6) A-140: THE FINISH SCHEDULE DOES NOT INDICATE
 COMPLIANCE FOR WALL FINISH MATERIALS AT THE TOILET ROOM
 FIXTURES AND MOP SINK- SECTION 310.3 FBC P AND SECTION
 1210.2.2 FBC B.
  
 7) P001: THE DRINKING FOUNTAIN DRAIN AND VENT ARE NOT
 SHOWN IN THE SANITARY RISER DRAWING- SECTION 107.3.5.3
 WPB.
  
 8) PROVIDE A WATER DISTRIBUTION RISER DRAWING- SECTION
 107.3.5.3 WPB.
  
 9) P001: PROVIDE THE EFFICIENCY RATING OF THE WATER
 HEATER IN THE SCHEDULE- TABLE C404.2 FBC EC.
  
 10) P001 & P100: THE WATER HEATER DETAIL SHOWS A HW
 RETURN LINE BUT THE ENLARGED PRESSURE PIPING PLAN DOES
 NOT SHOW A RETURN LINE. PLEASE CORRECT THE DETAIL OR
 THE DRAWING- SECTION 107.2.1 WPB.
  
 11) P001 & P100: P6 COFFEE MAKER IS SHOWN AT THE
 REFRIGERATOR LOCATION ON THE PRESSURE PIPING PLAN.
 PLEASE SHOW THE CORRECT LOCATION, THE WATER SUPPLY
 LINE, AND PROVIDE A WATER HAMMER ARRESTOR AND BACKFLOW
 PREVENTER ON THE SUPPLY LINE- SECTIONS 604.9 & 608.3
 FBC P.
  
 12) P001 & P100: CLARIFY IF THE REFRIGERATOR WILL
 CONTAIN AN ICE MAKER AND SHOW THE WATER SUPPLY LINE,
 WATER HAMMER ARRESTOR AND BACKFLOW PREVENTER- SECTIONS
 604.9 & 608.3 FBC P.
  
 13) P001 & P100: PLEASE PROVIDE A DEVICE SCHEDULE
 SHOWING MAKES, MODELS AND LISTINGS OF THE WATER HAMMER
 ARRESTORS, MIXING VALVES, BACKFLOW PREVENTERS, TRAP
 PRIMERS- SECTION 107.2.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  