| 2020-12-14 09:53:39 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT-20110970 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| | EDITION 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) IS THE NEW MECHANICAL SYSTEM CONDITIONING THE ENTIRE |
| | RESIDENCE? THERE IS NO INDICATION THAT ANOTHER SYSTEM |
| | IS IN USE NOW. FBC 107.2.1 |
| | |
| | 2) PLEASE SHOW THE DRYER DUCT AND EXHAUST TERMINATION. |
| | FBC RES M1502.3 |
| | |
| | 3) PLEASE SHOW THE CONDENSATION PIPING AND DRAINAGE |
| | LOCATION. FBC RES M1411.3 |
| | |
| | 4) PLEASE SHOW HOW THE CONDENSING UNIT WILL BE |
| | ANCHORED. FBC RES M1307.2 |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD |
| | SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER |
| | SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN |
| | THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS |
| | PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS |
| | PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR |
| | UPDATED. |
| | |