2020-12-16 17:02:31PLAN REVIEW / ELECTRICAL
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 2014 NEC
  
 1ST REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. PROVIDE UPDATED LOAD CALC'S.
 PROVIDE ACCURATE LOAD CALCULATIONS INCLUDING ALL LOADS
 FOR THE SERVICE AS WELL AS THE LOAD CALCULATIONS FOR
 THE INDIVIDUAL PANELS. NEC 220; FBC RE 3602.2.
  
 2. PROVIDE NEW PANEL SCHEDULE.
 PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED
 CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS,
 AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY
 WITH CODE. NEC 210.8, 210.12, 210.19, 210.20, 215.5,
 408.4; WPB FBC 107.3.5; FBC RE E3706.2, E3902
  
 3. PROVIDE ILLUMINATION AT ENTRY/EGRESS DOOR.
 FBC 1006.1.1 PER FBC-R, T-E3403
 ILLUMINATION OF MEANS OF EGRESS SHALL BE PROVIDED IN
 ACCORDANCE WITH THIS SECTION FOR EVERY BUILDING AND
 STRUCTURE.
  
 4. HIGH EFFICACY LAMPS
 PROVIDE COMPLIANCE: "A MINIMUM OF 75 PERCENT OF THE
 LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF
 THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 CONTAIN ONLY HIGH EFFICACY LAMPS".
  
 A NOTE ON THE PLAN WILL SUFFICE. FBC EC R404.1
  
 5. PROVIDE EQUIPMENT SERVICE OUTLET FOR C/U.
 E3901.12 HVAC OUTLET.
 A 125-VOLT, SINGLE-PHASE, 15- OR 20-AMPERE-RATED
 RECEPTACLE OUTLET SHALL BE INSTALLED AT AN ACCESSIBLE
 LOCATION FOR THE SERVICING OF HEATING, AIR-CONDITIONING
 AND REFRIGERATION EQUIPMENT. THE RECEPTACLE SHALL BE
 LOCATED ON THE SAME LEVEL AND WITHIN 25 FEET (7620 MM)
 OF THE HEATING, AIR-CONDITIONING AND REFRIGERATION
 EQUIPMENT. THE RECEPTACLE OUTLET SHALL NOT BE CONNECTED
 TO THE LOAD SIDE OF THE HVAC EQUIPMENT DISCONNECTING
 MEANS. (210.63)
  
 NOTICE: AFCI OUTLETS
 BRANCH CIRCUITS THAT SUPPLY 120-VOLT, SINGLE-PHASE, 15-
 AND 20-AMPERE OUTLETS INSTALLED IN KITCHENS, FAMILY
 ROOMS, DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES,
 DENS, BEDROOMS, SUN-ROOMS, RECREATIONS ROOMS, CLOSETS,
 HALLWAYS, LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS
 SHALL BE AFCI PROTECTED. PROVIDE COMPLIANCE. NEC
 210.12; FBC RE E3902.16
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  