Plan Review Notes
Plan Review Notes For Permit 20110934
Permit Number 20110934
Review Stop B
Sequence Number 1
Notes
Date Text
2020-11-20 17:29:57RESIDENTIAL (R3) BUILDING REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 NOTE: SEC. 702.6 FBC-EXISTING BUILDING. ALL NEW WORK
 SHALL COMPLY WITH THE MATERIALS AND METHODS
 REQUIREMENTS IN THE FLORIDA BUILDING CODE.
  
 1- "SHAKER" PVC DOORGLASS ASSEMBLY SUBMITTED (FLORIDA
 PRODUCT APPROVAL FL30712.1)
 IS NOT A COMPLETE DOOR ASSEMBLY. ACCORDING TO GENERAL
 NOTE #6 ON SHEET 1 OF 4 THIS DOORGLASS ASSEMBLY WAS
 TESTED WITH THE SPECIFIC PANELS SHOWN ON SHEET 4 OF 4.
 PROVIDE COMPLETE PRODUCT APPROVAL FOR ANY DOOR LISTED
 ON SHEET 4 OF 4 OR PROVIDE COMPLETE SITE SPECIFIC
 ENGINEERING FOR ANOTHER DOOR PRODUCT APPROVAL.
  
 THERMA TRU DOOR PRODUCT APPROVAL SUBMITTED (FL7640.1)
 REQUIRES SITE SPECIFIC ENGINEERING WHEN THERE IS A
 DEVIATION/CHANGES TO THE DOOR ASSEMBLY. SEE GENERAL
 NOTE #5 ON SHEET 1 OF 9.
  
 SEC. 107.2.1.2 CITY AMENDMENTS AND SEC. 61G20-3.001
 F.A.C.
  
 2- FLORIDA PRODUCT APPROVALS SUBMITTED ARE INCOMPLETE.
 NEED TO PROVIDE COMPLETE FLORIDA PRODUCT APPROVAL
 INCLUDING THE FLORIDA PRODUCT APPROVAL COVER PAGE THAT
 CORRESPONDS TO THE DRAWINGS SUBMITTED. THE FLORIDA
 PRODUCT APPROVAL IS REQUIRED BECAUSE IT SHOWS IF
 PRODUCT IS APPROVED AND CURRENT CODE IN EFFECT. CHAPTER
 553 F.S.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]