| 2020-12-08 13:39:08 | 1ST REVIEW FBC-2017 RES. FUEL GAS |
| | PERMIT- 20110932 |
| | 12/8/2020 |
| | |
| | CODES IN EFFECT: |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| | EDITION 2017 |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) GAS RISER: |
| | |
| | A) SHOW THE TOTAL LOAD OF THE SYSTEM- SECTION G2413.2 |
| | FBC RES. PLEASE NOTE THE GENERATOR SPECS SUBMITTED |
| | UNDER THE MAIN GENERATOR PERMIT- 20120204 INDICATE A |
| | FULL GAS LOAD OF 306,000 BTUH FOR THE 24 KW GENERATOR. |
| | |
| | B) INDICATE THE TYPES OF PIPING AND THE PIPE SIZING |
| | TABLES USED- SEE SECTION G2413.3 AND TABLES G2413.4(1)- |
| | G2413.4(8) FBC RES. |
| | |
| | C) SHOW THE LOCATIONS OF THE STEP-DOWN REGULATORS AND |
| | THEIR OUTLET PRESSURES AT THE WATER HEATER AND |
| | GENERATOR- SECTION G2412.1 & G2421.2 FBC RES. PLEASE |
| | SUBMIT MARKED UP OR HIGHLIGHTED SPECS SHOWING THE |
| | SELECTED MODEL, THE MAX INLET AND OUTLET SIZE AND |
| | PRESSURES, SPRING DATA, AND ORIFICE SIZE. |
| | |
| | 2) PLEASE NOTE THE GENERATOR SHALL BE INSTALLED A |
| | MINIMIUM OF 10 FT. FROM MECHANICAL AND GRAVITY AIR |
| | INTAKES INTO THE BUILDING- SECTION R303.5.1 FBC RES. |
| | |
| | 3) THE CONTRACTOR OR QUALIFIER WHO PREPARED THE DRAWING |
| | SHALL PROVIDE HIS/HER PRINTED NAME AND SIGNATURE ON IT- |
| | SECTION 107.2.1 WPB, AND FLORIDA STATUTES 471.003(2)(H) |
| | & 471.025. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |