| 2020-12-03 16:51:09 | 1ST REVIEW FBC-2017 PLUMBING |
| | PERMIT- 20110928 |
| | 12/3/2020 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET P1: PROVIDE PLUMBING FIXTURE CALCULATIONS AND |
| | A SCHEDULE SHOWING THE REQUIRED AND PROVIDED FIXTURES |
| | IN COMPLIANCE WITH TABLE 403.3 FBC P. PLEASE NOTE THAT |
| | TWO MALE AND TWO FEMALE WATER CLOSETS ARE REQUIRED FOR |
| | THE B OCCUPANCY WITH 53 OCCUPANTS. THE PLAN SHOWS |
| | NON-COMPLIANCE. |
| | |
| | 2) A1: PROVIDE TOILET ROOM LENGTH AND WIDTH DIMENSIONS- |
| | SECTION 107.2.1 WPB. |
| | |
| | 3) A1: SHOW THE CLEAR FLOOR DIAGRAM AND DIMENSIONS AT |
| | THE NEW BREAKROOM SINK- SECTION 305.3 FBC ACC. |
| | |
| | 4) A3: SHOW THE HEIGHTS OF THE WATER CLOSETS FROM THE |
| | FINISHED FLOORS TO THE TOPS OF THE SEATS- SECTION 604.4 |
| | FBC ACC. |
| | |
| | 5) A3: SHOW THE HEIGHTS OF THE GRAB BARS FROM THE |
| | FINISHED FLOORS TO THE TOPS OF THE GRIPPING SURFACES- |
| | SECTION 609.4 FBC ACC. |
| | |
| | 6) PROVIDE A PLUMBING SUB-PERMIT APPLICATION- SECTION |
| | 105.1 WPB. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |