| 2020-12-22 09:49:21 | 12/22/20 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1. THESE ARE MULTI-FAMILY DWELLINGS. THE WATER USERS |
| | WILL BE REQUIRED TO INSTALL A BACKFLOW PREVENTION |
| | ASSEMBLY AT THE POINT OF DELIVERY THAT IS LEAD-FREE AND |
| | A CURRENT YEAR CERTIFICATION PER THE CITY OF WEST PALM |
| | CROSS UTILITIES DEPARTMENT AND THEIR CONNECTION CONTROL |
| | PROGRAM. |
| | |
| | 2. A LICENSED CONTRACTOR MUST REQUIRE SUB PLUMBING AND |
| | GAS PERMITS FOR THE SCOPE OF WORK PER THE WPB |
| | AMENDMENTS TO THE FBC SEC. 105.1. |
| | |
| | 3. ON SHEET A-1; |
| | A. THE PLUMBING ISOMETRIC SHOW TWO AIR ADMITTANCE |
| | VALVE, THE SYSTEM MUST HAVE A VENT THROUGH THE ROOF. A |
| | MINIMUM OF ONE STACK VENT OR VENT STACK EXTENDED TO THE |
| | OUTDOORS TO THE OPEN AIR PER THE FBC SEC. P 918.7. SHOW |
| | COMPLIANCE WITH THE PLANS. |
| | |
| | B. PLEASE SHOW DIMENSION BETWEEN FIXTURES INSTALLATION |
| | TO CONFORM TO THE 2017 FBC SEC. R 2705.1 (5). |
| | |
| | C. HOT WATER LINES NOT IN CONDITION SPACE SHALL BE |
| | INSULATED WITH A MINIMUM R-3 PER THE 2017 FBC SEC. RE |
| | 403.5.3. |
| | |
| | D. HOT GAS HEATER IF CONDENSATE NEEDS TO BE 1' AWAY |
| | FROM STRUCTURE PER THE 2017 FBC SEC. R318.5. |
| | |
| | 4. PLEASE PROVIDE MANUFACTURES INSTALLATION INSTRUCTION |
| | FOR TH GAS WATER HEATER PER THE WPB AMENDMENTS TO THE |
| | FBC 107.2.1. |
| | |
| | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES. |
| | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA |
| | |
| | LUIS A. CRESPO |
| | PLUMBING PLAN EXAMINER / INSPECTOR |
| | EMAIL: [email protected] OFFICE: 561 805-6720 |
| | |