| 2020-12-22 11:12:22 | 12/22/20 1ST GAS REVIEW**DENIED** WITH COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1. CITY RECORDS SHOW AN EXISTING GAS SYSTEM AT THIS |
| | PROPERTY. THE BTU LOAD OF THE CURRENT GAS SYSTEM MUST |
| | BE ADDED TO THE TOTAL BTU LOAD ON THE SYSTEM TO ENSURE |
| | THE EXISTING SYSTEM IS SIZED CORRECTLY. IF UNDERSIZED, |
| | THE EXISTING SYSTEM MUST BE REDONE TO ENSURE A SAFE |
| | OPERATING SYSTEM. SUBMIT A GAS PIPING RISER DIAGRAM |
| | THAT SHOWS THE TYPE OF EXISTING APPLIANCE, THE BTU LOAD |
| | OF EACH APPLIANCE, THE PIPE SIZE AND TYPE OF PIPE TO |
| | EACH APPLIANCE, AND THE DISTANCE OF THE LONGEST LENGTH |
| | OF PIPING FROM THE POINT OF DELIVERY TO THE MOST REMOTE |
| | OUTLET AND THE LOAD OF THE SECTION. NOTE: IF THE |
| | EXISTING SYSTEM IS PRESSURE IS 2 PSI, A LINE PRESSURE |
| | REGULATOR IS REQUIRED AT ALL THE EXISTING APPLIANCES |
| | PER THE 2017 FBC R SECS. G2412.4, G2412.8, G2413.1, |
| | G2413.2, G2413.3. |
| | |
| | 2 INDICATE THE PLAN IN WHICH THE GAS CODE'S SIZING |
| | TABLES ARE BEING USED FOR THE SYSTEM PER THE WPB |
| | AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. |
| | |
| | 3. THE TYPE OF PIPE MENTION IS NOT APPROVED TO BE |
| | INSTALLED UNDERGROUND. YOU MAY USE TRAC PIPE OR PE FOR |
| | UNDERGROUND AND CSST OR METAL PIPE ABOVE GROUND, SO |
| | PLEASE CLARIFY PER THE WPB AMENDMENTS TO THE FBC SEC. |
| | 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | 4. GAS RISER DIAGRAM REQUIRED, SO PLEASE SUBMIT AN |
| | ISOMETRIC DRAWING THAT CLEARLY SHOWS THE LENGTH OF ALL |
| | CUT SECTIONS OF PIPE PER 2017 FBC RES. SECS. G2413.4.1, |
| | G2413.4.2. |
| | |
| | 5. SHOW THE TYPE OF PIPE MATERIAL BEING USED, ALL PIPE |
| | SIZES, AND THE CORRESPONDING EHD NUMBER OF THE |
| | CORRUGATED STAINLESS-STEEL OR TRAC PIPE TUBING (IF |
| | APPLICABLE) FOR EACH PIPE SIZE PER THE WPB AMENDMENTS |
| | TO THE FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION |
| | DOCUMENTS. |
| | 6. A LICENSED CONTRACTOR MUST REQUIRE A SUB GAS PERMIT |
| | FOR THE SCOPE OF WORK PER THE WPB AMENDMENTS TO THE FBC |
| | SEC. 105.1. |
| | |
| | 7. TYPE OF GAS (LP OR NATURAL) PER THE WPB AMENDMENTS |
| | TO THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION |
| | DOCUMENTS. |
| | |
| | 8. SHOW ALL MP (STEP-DOWN) REGULATORS' LOCATION. A |
| | LISTED SHUTOFF VALVE SHALL BE INSTALLED IMMEDIATELY |
| | AHEAD OF EACH MP REGULATOR. 2017 FBC RES. SEC. G2420.4. |
| | |
| | 9. SHOW THE DISTANCE FROM THE POINT OF DELIVERY (GAS |
| | METER / MP REGULATOR / LP TANK) TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND OR SYSTEM PER THE 2017 FBC |
| | RES. SEC. G2413.4.1. |
| | |
| | 10. IF THIS TANKLESS UNIT CALL FOR A 10.5" WATER COLUMN |
| | AND THE SERVICE METER DISCHARGES IS A 12" WATER COLUMN |
| | REQUIRING A REGULATOR FOR THIS UNIT AS PER |
| | MANUFACTURER'S SPECIFICATION. SUBMIT MANUFACTURER'S |
| | SPECIFICATIONS FOR THE PRESSURE REGULATORS. REGULATORS |
| | INSTALLED ON THE BUILDING'S EXTERIOR SHALL BE APPROVED |
| | FOR OUTDOOR INSTALLATION PER THE 2017 FBC RES. SEC. |
| | G2421.1. |
| | |
| | 10. INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM |
| | ON THE PLAN PER THE 2017 FBC RES. SEC. G2413.2. |
| | |
| | 11. SUBMIT MANUFACTURER'S SPECIFICATION |
| | SHEETS/INSTALLATION MANUAL FOR GAS TANK-LESS TO VERIFY |
| | COMPLIANCE WITH 2017 FBC RES. SEC. G2408.1. |
| | |
| | 12. PLEASE SHOW ALL REGULATORS, UNIONS IN FRONT OF |
| | REGULATOR 1' OF EITHER SIDE, DRIP LEG, LABEL SHUT OFF |
| | VALVES WITH THEM LABELED PER THE 2017 FBC RES. SEC |
| | G2421.2 |
| | |
| | 13. ON THE PLAN, PLEASE THE LOCATION OF THE TANK-LESS |
| | WATER HEATER AND THE LOCATION AND DISTANCE OF ANY |
| | OPERABLE DOORS OR WINDOWS IN RELATION TO THE WATER |
| | HEATER. THE LOCATION OF THE WATER HEATER SHALL COMPLY |
| | WITH THE MANUFACTURER'S INSTALLATION INSTRUCTIONS. THE |
| | HOUSE PLAN CAN BE HAND-DRAWN PER THE WPB AMENDMENTS TO |
| | THE FBC SEC. 107.2.1. INFORMATION ON CONSTRUCTION |
| | DOCUMENTS. |
| | |
| | NOTE: YOU MAY CHOOSE TO HAVE A GAS REVIEW DONE THIS |
| | TIME AND ADDRESS THE COMENTS ABOVE. THIS WILL HAVE THE |
| | GAS APPROVE FOR A SUB PERMIT, OR IF YOU DECIDED NOT TO |
| | ADDRESS THESE COMMENTS, PLEASE PUT A NOTE ON THE GAS |
| | HEATER ( A SEPARATE PERMIT BY A LICENSED CONTRACTOR FOR |
| | THE GAS SYSTEM). THEN PLEASE TAKE OFF ANY GAS SHOWN ON |
| | PLANS; THESE COMMENTS CAN BE FORWARD TO THE GAS |
| | CONTRACTOR FOR REFERENCE. AN N WILL BE PUT ON THIS |
| | REVIEW, WHICH STANDS FOR NOT REQUIRED BUT, A SUB PERMIT |
| | WON'T BE ISSUED UNIT A REVIEW IS DONE FOR THAT SUB |
| | PERMIT, SO PLEASE BE ADVISED ON THIS PROCEDURE. |
| | |
| | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES. |
| | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA |
| | |
| | LUIS A. CRESPO |
| | PLUMBING PLAN EXAMINER / INSPECTOR |
| | EMAIL: [email protected] OFFICE: 561 805-6720 |
| | |