| 2021-04-23 09:21:02 | 1ST REVIEW FBC-2017 RES. |
| | PERMIT- 20110913 |
| | 4/23/2021 |
| | |
| | CODES IN EFFECT: |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| | EDITION 2017 |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | PLEASE NOTE THE PLANS FOR THE POOL ARE COPIES OF |
| | DIGITALLY SIGNED AND SEALED PLANS THAT WERE SCANNED |
| | INTO THE SYSTEM FOR REVIEW. AS A RESULT, SOME OF THE |
| | PRINT AND DETAILS ON THE PLANS ARE NOT LEGIBLE. A |
| | COMPLETE REVIEW WILL DEPEND ON RESUBMITTAL OF DIGITALLY |
| | SIGNED AND SEALED AND ELECTRONICALLY TRANSMITTED PLANS. |
| | PLEAE COMPLY WITH PRELIMINARY COMMENTS BELOW. |
| | |
| | 1) SHEET 1: THE POOL EQUIPMENT SCHEDULE DOES NOT |
| | INCLUDE THE RAYPACK POOL HEATER- SECTION 107.2.1 WPB. |
| | PLEASE UPDATE THE SCHEDULE TO INDICATE THE SELECTED |
| | MODEL AS INDICATED IN THE SUBMITTED PRODUCT SPECS- |
| | SECTION R4501.14 FBC RES. |
| | |
| | 2) SHEET 1 SPECIFICATIONS: PLEASE PROVIDE THE POOL |
| | TURNOVER RATE IN COMPLIANCE WITH SECTION 9.1.3 |
| | ANSI/APSP/ICC-5 2011. |
| | |
| | 3) SHEETS 1 & 3: PROVIDE THE WATER VELOCITY OF THE |
| | SUCTION AND PRESSURE PIPING- SECTION 9.2 |
| | ANSI/APSP/ICC-5 2011, AND SECTION R4501.6.3 FBC RES. |
| | |
| | 4) SHEET 3: PROVIDE A COMPLETE TDH CALCULATION THAT |
| | INCLUDES THE POOL HEATER AND SUBMIT THE WORKSHEET. |
| | SUBMIT TOTAL DYNAMIC HEAD CALCULATIONS FOR THE MAXIMUM |
| | SYSTEM FLOW. THE MAXIMUM FLOW OF THE PUMP FROM ITS PUMP |
| | CURVE AND THE SIMPLIFIED TOTAL DYNAMIC HEAD CALCULATION |
| | IS NO LONGER ALLOWED TO BE USED IN DETERMINING MAXIMUM |
| | SYSTEM FLOW RATE PER ANSI/APSP/ICC 7- 2013 SECS. 4.4.9, |
| | 4.4.9.1. THE 2013 EDITION ADDRESSES FLOW RATE IN |
| | GALLONS PER MINUTE (GPM). IT REQUIRES THAT MAXIMUM |
| | SYSTEM FLOW RATE DOES NOT EXCEED THE LISTED MAXIMUM |
| | FLOW RATE OF THE SUCTION OUTLET FITTING ASSEMBLY (DRAIN |
| | COVER). THE TDH CALCULATIONS MUST INCLUDE ALL OF THE |
| | SYSTEM COMPONENTS INCLUDING SUCTION AND RETURN PIPING, |
| | FITTINGS, VALVES, HEATER, FILTER, AND CHLORINATOR. ALL |
| | SYSTEM COMPONENTS EXCEPT THE PUMP. |
| | |
| | 5) SHEET 3: THE MODEL NUMBER OF THE PUMP IN THE TABLE |
| | AND IN THE CURVE IS NOT LEGIBLE. PROVIDE A LEGIBLE |
| | CURVE THAT IDENTIFIES ON THE CURVE KEY THE SELECTED |
| | PUMP TO BE INSTALLED ON THIS POOL. THIS IS NEEDED TO |
| | CONFIRM THE MAXIMUM SYSTEM FLOW FROM THE TDH |
| | CALCULATIONS. ANSI/APSP/ICC 7 - 2013 SECS. 4.4.9, |
| | 4.4.9.1. |
| | |
| | 6) SHEETS 1 & 3: INDICATE HOW WATER BE SUPPLIED TO THE |
| | POOL. PLEASE NOTE IF AN AUTOFILL IS TO BE INSTALLED A |
| | BACKFLOW DEVICE SHALL BE INSTALLED AT THE AUTOFILL, AND |
| | A REDUCED PRESSURE BACKFLOW DEVICE SHALL BE INSTALLED |
| | AT THE METER UNDER A SEPARATE PERMIT- SECTION R4501.10 |
| | FBC RES. |
| | NOTE: A FL. LICENSED PLUMBING CONTRACTOR SHALL OBTAIN A |
| | SEPARATE PERMIT FOR INSTALLATION OF THE BACKFLOW |
| | PREVENTER IN ACCORDANCE WITH SECTION 105.1 WPB AND SEC. |
| | 90-33 WPB CODE OF ORDINANCES. THE DEVICE SHALL BE |
| | TESTED AND CERTIFIED BY THE WPB UTILITIES DEPARTMENT |
| | PRIOR TO FINAL INSPECTION BY THE BUILDING DEPARTMENT. |
| | PLEASE CONTACT THE WPB UTILITIES CENTRAL OPERATIONS |
| | DEPT.AT 561-822-2210 FOR FURTHER INFORMATION. |
| | |
| | 7) SHEETS 1 & 3: PROVIDE POOL PIPING TEST CRITERIA- |
| | SECTION R4501.12.1 FBC RES. PLEASE NOTE THAT AIR TESTS |
| | ARE PROHIBITED FOR PVC PIPING- SECTION 312.1 FBC P. |
| | |
| | 8) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE PUMP, |
| | FILTER, AND MAIN DRAIN COVER- SECTION R4501.6.2 FBC |
| | RES. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |