| Plan Review Notes For Permit 20110845 |
| Permit Number |
20110845 |
|
| Review Stop |
M |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2021-03-22 13:29:36 | NO MECHANICAL VENTILATION PROVIDED. ONLY NATURAL | | | VENTILATION. IF EXISTING SINGLE HUNG WINDOW HAS LESS | | | THAN 3 SQUARE FEET IN GLAZING AREA (ONE-HALF OF WINDOW | | | MUST BE OPENABLE), THEN MECHANICAL VENTILATION IS | | | REQUIRED. SEC. R303.3 FBC-RESIDENTIAL. |
|