| Date |
Text |
| 2020-11-20 09:06:59 | 11/20/20 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1. ON THE ISOMETRIC DRAWING, THE VENT THAT IS LABEL |
| | STUDOR MUST EXIT OUT THE BUILDING PER 2017 FBC R |
| | P3102.1 REQUIRED VENT EXTENSION. |
| | |
| | 2. SHOWER COMPARTMENTS SHALL HAVE NOT LESS THAN 900 |
| | SQUARE INCHES (0.6 M2) OF INTERIOR CROSS-SECTIONAL AREA |
| | PER THE 2017 FBC SEC. R P2708.1 GENERAL. |
| | |
| | 3. PLEASE SHOW THE WALL FOR THE BATHROOM PER THE WPB |
| | AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. |
| | |
| | 4. PLEASE SHOW THE MINIMAL FOR FIXTURE PER THE 2017 FBC |
| | SEC. R 2705.1 (5) GENERAL. |
| | |
| | 5. A SUB GAS, MECHANICAL, ELECTRICAL, AND THE BUILDING |
| | PERMIT IS REQUIRED BY A LICENSED CONTRACTOR FOR THE |
| | SCOPE OF WORK PER THE WPB AMENDMENTS TO THE FBC SEC. |
| | 105.1. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA |
| | |
| | LUIS A. CRESPO |
| | PLUMBING PLAN EXAMINER / INSPECTOR |
| | EMAIL: [email protected] OFFICE: 561 805-6720 |
| | |