| 2020-12-30 10:58:23 | 2ND REVIEW FBC-2017 MECHANICAL |
| | PERMIT-20110798 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| | EDITION 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: APPROVED ONLY THE AIR CONDITIONING |
| | REVISIONS. |
| | |
| | 1) SHEET M200: UPDATED DIFFUSER LOCATION IN |
| | RECEIVING-APPROVED: |
| | |
| | 2) SHEET M200: CHANGED THE DIFFUSER TYPE BY THE DOOR- |
| | APPROVED: |
| | |
| | 3) SHEET M201: UPDATED THE RA DUCT CONNECTION TO THE |
| | AHU?S- APPROVED: |
| | |
| | 4) SHEET M400: REMOVED THE ICE MACHINE CONDENSING |
| | UNITS- APPROVED: |
| | |
| | 5) DID NOT REVIEW ANY REVISIONS TO ANYTHING HAVING TO |
| | DO WITH THE HOOD IN THIS REVIEW AS IT MUST BE SUBMITTED |
| | AS A REVISION TO THE HOOD PERMIT (# 20090888) |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD |
| | SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER |
| | SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN |
| | THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS |
| | PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS |
| | PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR |
| | UPDATED. |
| | |