| Date |
Text |
| 2020-12-07 17:57:20 | 1ST REVIEW FBC-2017 PLUMBING |
| | PERMIT- 20110798 |
| | 12/7/2020 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEETS P103, P106, & P200: FLOOR SINK W727 SHOWN IN |
| | THE SANITARY ISOMETRIC IS NOT SHOWN ON THE UNDERGROUND |
| | PLUMBING PLAN AND IS NOT IN THE ROUGH-IN SCHEDULE- |
| | SECTION 107.2.1 WPB. |
| | |
| | 2) P106: PLEASE SHOW THE COMPLETE FILTERED PIPING RUN |
| | FROM P125 TO EACH FIXTURE OR APPLIANCE- SECTION 107.2.1 |
| | WPB AND 608.3 FBC P. |
| | |
| | 3) P200 & P201: ACCORDING TO THE REVISION NARRATIVE THE |
| | HAND SINK W706 HAS BEEN CONNECTED TO THE SANITARY |
| | HOWEVER THE PLANS DO NOT SHOW THE CHANGE- SECTION |
| | 107.2.1 WPB. |
| | |
| | 4) P201: PROVIDE THE TYPE AND SIZE OF TRELLIS |
| | DOWNSPOUTS AND SIZING CALCULATIONS PER TABLE 1106.3 FBC |
| | P. |
| | |
| | A) PROVIDE THE TYPE AND SIZE OF GUTTERS AND SIZING |
| | CALCULATIONS- TABLE 1106.6 FBC P. |
| | |
| | B) PROVIDE COMPLETE STORM DRAIN PIPING PLANS AND |
| | ISOMETRIC DRAWING. SHOW THE POINTS OF CONNECTIONS OF |
| | THE NEW LEADERS TO THE EXISTING STORM DRAIN PIPE, THE |
| | SIZE OF THE STORM DRAIN PIPE, THE GPM FLOW FROM EACH |
| | LEADER INTO THE SYSTEM, AND THE REVISED TOTAL GPM |
| | CAPACITY OF THE SYSTEM- TABLE 1106.2 FBC P. |
| | |
| | 5) P300: A SEPARATE PERMIT APPLICATION AND PLANS ARE |
| | REQUIRED FOR THE GAS PIPING INSTALLATIONS- SECTION |
| | 107.2.1 WPB. A REVIEW OF THE SYSTEM AND ALL REVISED |
| | CHANGES WAS NOT PERFORMED UNDER THIS REVISION |
| | SUBMITTAL. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |