| Plan Review Notes For Permit 20110798 |
| Permit Number |
20110798 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2020-11-23 16:22:11 | BUILDING PROVISO: WELDED OR BOLTED CONNECTIONS. THE | | | CONTRACTOR IS REQUIRED TO PROVIDE WELD PROCEDURE | | | SPECIFICATIONS & WELDER OPERATOR PERFORMANCE | | | QUALIFICATION RECORDS IN ACCORDANCE WITH THE REFERENCED | | | STANDARDS AT TIME OF INSPECTION FOR FIELD WIELDING, ON | | | THE JOB-SITE WIELDING. THIRD PARTY CERTIFICATION WILL | | | BE REQUIRED. REPORTS SUBMITTED TO BUILDING INSPECTOR AT | | | TIME OF FRAMING INSPECTION. | | | 2017 FBC-B 2204.1 WELDING | | | 1. WELD PROCEDURES SPECIFICATIONS | | | 2. QUALIFICATIONS OF WELDING PERSONAL | | | 2017 FBC-B 2204.2 BOLTING. | | | IF FURTHER CLARIFICATION AND OR QUESTIONS IS REQUIRED, | | | PLEASE CONTACT THE CHIEF BUILDING INSPECTOR KEN CONRAD | | | AT 561-805-6666. |
|