| 2021-01-12 16:57:58 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | FLORIDA BUILDING CODE 2017 6TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | | NFPA 70 2014 EDITION | | | | | | JAKE LEAHY BN, BU, PX | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | 1) OUTLET REQUIRED ON FRONT AND REAR OF EACH UNIT. | | | | | | E3901.7 OUTDOOR OUTLETS. | | | NOT LESS THAN ONE RECEPTACLE OUTLET THAT IS READILY | | | ACCESSIBLE FROM GRADE LEVEL AND LOCATED NOT MORE THAN 6 | | | FEET, 6 INCHES (1981 MM) ABOVE GRADE, SHALL BE | | | INSTALLED OUTDOORS AT THE FRONT AND BACK OF EACH | | | DWELLING UNIT HAVING DIRECT ACCESS TO GRADE LEVEL | | | | | | 2) AIC CALCULATION REQUIRED FOR SERVICE AND PANEL. | | | 110.9, 110,10 | | | | | | PROVIDE CALCULATION FOR AVAILABLE SHORT CIRCUIT CURRENT | | | AT NEW PANEL TO CONFIRM AIC RATING IS ADEQUATE. NEC | | | 110.10 | | | | | | 3) ONLY ONE SMOKE ALARM, THERE SHALL BE A MINIMUM OF | | | TWO ONE AT EACH LEVEL. | | | | | | PROVIDE SMOKE ALARM ON EACH STORY OF THE DWELLING. FBC | | | R314.3 |
|