| Date |
Text |
| 2021-01-11 09:36:16 | RENOVATION |
| | REVIEWED BY ROGER MCPHERSON |
| | 561-805-6716 |
| | [email protected]. |
| | CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1 |
| | AMENDMENTS |
| | |
| | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 |
| | CANNOT PROVIDE A COMPLETE REVIEW - NEED MORE |
| | INFORMATION |
| | 1) SHOW BUILDING OCCUPANCY CLASSIFICATION - FBC CHAPTER |
| | 3 (SHOW BUILDING USE FOR EACH ROOM) |
| | 2) SHOW BUILDING CONSTRUCTION TYPE - FBC CHAPTER 6 |
| | 3) PROVIDE A LIFE SAFETY PLAN SHOWING THE MEANS OF |
| | EGRESS SIZING, SPRINKLERED?, OCCUPANT LOAD ETC. - FBC |
| | CHAPTER 10 |
| | 4) SHOW THE EXISTING BUILDING CODE COMPLIANCE METHOD |
| | USED PER FBC EXISTING BUILDING 301.1 |
| | 5) PLEASE SHOW THE CEILING HEIGHT FOR THE LOFT TO |
| | COMPLY WITH FBC 1208.2 |
| | 6) PLEASE SHOW STAIR AND RAMP HANDRAIL DETAILS TO |
| | COMPLY WITH FBC 1014 |
| | 7) PLEASE SHOW RAMP SLOPE TO COMPLY WITH FBC 1012 |
| | 8) PLEASE SHOW STAIR DETAILS TO COMPLY WITH FBC 1011 |
| | 9) PLEASE SHOW ACCESSIBLE DOOR CLEAR FLOOR SPACE TO |
| | COMPLY WITH FBC ACCESSIBILITY 404.2.4 MANEUVERING |
| | CLEARANCES. |
| | 10) PLEASE SHOW BATHROOMS AND KITCHENS TO COMPLY WITH |
| | ACCESSIBILITY PER FBC ACCESSIBILITY (SHOW ALL HEIGHTS |
| | AND SIZES FOR MIRRORS, SINKS, COUNTER TOPS, GRAB BARS, |
| | DISPENSERS, CLEAR FLOOR SPACE SIZES ETC.) |
| | 11) PLEASE SHOW THE GUARD RAIL DETAILS AT THE LOFT TO |
| | COMPLY WITH FBC 1015 AND 1607 |
| | 12) PLEASE SHOW WALL, FLOOR AND CEILING INSULATION TO |
| | COMPLY WITH FBC ENERGY CODE |
| | 13) PLEASE SHOW THE ATTIC VENTILATION TO COMPLY WITH |
| | FBC 1503.5 |
| | 14) PLEASE PROVIDE COMPLETE MIAMI DADE OR FLORIDA STATE |
| | PRODUCT APPROVALS FOR THE NEW EXTERIOR WINDOWS AND |
| | DOORS. |
| | 15) PLEASE PROVIDE COMPLETE MIAMI DADE OR FLORIDA STATE |
| | PRODUCT APPROVALS FOR THE ROOFING SYSTEM. |
| | 16) PLEASE PROVIDE A DOOR AND WINDOW SCHEDULE. |
| | 17) PLEASE SHOW SMOKE DETECTOR LOCATIONS, FIRE ALARMS, |
| | SPRINKLERS ETC TO COMPLY WITH - FBC 420 |
| | 18) PLEASE SHOW FOUNDATION APRON TO COMPLY WITH FBC |
| | APPENDIX F101.6.1 |
| | 19) PLEASE SHOW THE MEZZANINE (LOFT) TO COMPLY WITH FBC |
| | 505 (SIZE, EGRESS, OPENNESS ETC) |
| | 20) TO BE DEFERRED - REAR DECK STRUCTURAL DETAILS. |
| | 21) ROOFING SYSTEM AND WINDOW AND DOOR PRODUCT |
| | APPROVALS MAY BE DEFERRED SUBMITTALS BY LISTING ITEMS |
| | TO BE DEFERRED ON THE CONSTRUCTION DOCUMENTS - |
| | 107.3.4.1 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS |
| | SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE |
| | PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE |
| | TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO |
| | THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD. |
| | DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR |
| | APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED |
| | DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST |
| | THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS |
| | FOR REVIEW BY THE BUILDING OFFICIAL. DOCUMENTS FOR |
| | DEFERRED SUBMITTAL ITEMS SHALL BE SUBMITTED TO THE |
| | REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE |
| | WHO SHALL REVIEW THEM AND FORWARD THEM TO THE BUILDING |
| | OFFICIAL WITH A NOTATION INDICATING THAT THE DEFERRED |
| | SUBMITTAL DOCUMENTS HAVE BEEN REVIEWED AND FOUND TO BE |
| | IN GENERAL CONFORMANCE TO THE DESIGN OF THE BUILDING. |
| | THE DEFERRED SUBMITTAL ITEMS SHALL NOT BE INSTALLED |
| | UNTIL THE DEFERRED SUBMITTAL DOCUMENTS HAVE BEEN |
| | APPROVED BY THE BUILDING OFFICIAL. |
| | |
| | |