| 2020-12-02 12:55:06 | 1ST REVIEW FBC-2017 PLUMBING |
| | PERMIT- 20110733 |
| | 12/2/2020 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) PROVIDE PLUMBING PLANS AND SPECIFICATIONS. A |
| | THOROUGH REVIEW CANNOT BE ACCOMPLISHED WITH THE |
| | FOLLOWING DETAILS, DRAWINGS, SPECIFICATIONS AND |
| | INFORMATION ON THE PLANS: |
| | |
| | A) CODE COMPLIANCE DATA: PROVIDE A LIST OF CURRENT |
| | CODES AND STANDARDS USED IN THE DESIGN OF THE PROJECT- |
| | SECTION 107.2.1 WPB. |
| | |
| | B) COMPLIANCE METHOD PER THE FLORIDA EXISTING BUILDING |
| | CODE- SEE SECTION 301.3 FBC EX. |
| | |
| | C) OCCUPANCY CLASSIFICATION- CHAPTER 3 FBC B. |
| | |
| | D) OCCUPANCY LOAD CALCULATIONS- TABLE 1004.5 FBC B. |
| | |
| | E) PLUMBING FIXTURE CALCULATIONS PER TABLE 403.3 FBC P. |
| | PROVIDE A SCHEDULE OF REQUIRED AND PROVIDED PLUMBING |
| | FIXTURES- SECTION 107.3.5.1.3 WPB. |
| | |
| | F) SANITARY AND WATER RISER LAYOUT AND RISER DRAWINGS- |
| | SECTION 107.3.5.1.3 WPB. |
| | |
| | G) WATER SERVICE AND BACKFLOW PREVENTION- SECTION 603.1 |
| | & 604.1 FBC P, & SECTION 107.3.5.1.3 WPB. PLEASE NOTE A |
| | SEPARATE PERMIT IS REQUIRED FOR WATER SERVICE BACKFLOW |
| | PREVENTERS- SECTION 105.1 & 107.2.1 WPB. |
| | |
| | H) WATER HEATERS AND HOT AND TEMPERED WATER SYSTEMS- |
| | SECTION 107.3.5.1.3 WPB, AND SECTIONS 502.1 & 607.1 FBC |
| | P. |
| | |
| | I) PLUMBING FIXTURE SCHEDULES- SECTION 107.3.5.1.3 WPB, |
| | AND SECTION 405 FBC P. |
| | |
| | J) PLUMBING PIPING AND INSULATION SPECIFICATIONS- |
| | SECTION 107.3.5.1.3 WPB. |
| | |
| | L) ACCESSIBILITY DETAILS AND DRAWINGS IN ACCORDANCE |
| | WITH SECTIONS 211, 212, 213, AND CHAPTER 6 FBC ACC. |
| | |
| | 2) PROVIDE A PLUMBING SUB-PERMIT APPLICATION- SECTION |
| | 105.1 WPB. |
| | |
| | 3) PLEASE NOTE SEPARATE PERMITS ARE REQUIRED FOR GAS |
| | PIPING, IRRIGATION SYSTEM, AND WATER SERVICE BACKFLOW |
| | PREVENTERS- SECTIONS 105.1 & 107.2.1 WPB. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE NOTE THAT ADDITIONAL PLUMBING |
| | COMMENTS MAY OCCUR AFTER THE PLANS ARE SUBMITTED AND |
| | REVIEWED. |
| | |