| 2020-11-30 13:43:16 | RENOVATION |
| | REVIEWED BY ROGER MCPHERSON |
| | 561-805-6716 |
| | [email protected]. |
| | CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1 |
| | AMENDMENTS |
| | |
| | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 |
| | CANNOT PROVIDE A COMPLETE REVIEW - NEED MORE |
| | INFORMATION |
| | 1) SHOW BUILDING OCCUPANCY CLASSIFICATION - FBC CHAPTER |
| | 3 (SHOW BUILDING USE FOR EACH ROOM) |
| | 2) SHOW BUILDING CONSTRUCTION TYPE - FBC CHAPTER 6 |
| | 3) PROVIDE A LIFE SAFETY PLAN SHOWING THE MEANS OF |
| | EGRESS SIZING, SPRINKLERED?, OCCUPANT LOAD ETC. - FBC |
| | CHAPTER 10 |
| | 4) SHOW THE EXISTING BUILDING CODE COMPLIANCE METHOD |
| | USED PER FBC EXISTING BUILDING 301.1 |
| | 5) PLEASE SHOW THE CEILING HEIGHT FOR THE LOFT TO |
| | COMPLY WITH FBC 1208.2 |
| | 6) PLEASE SHOW STAIR AND RAMP HANDRAIL DETAILS TO |
| | COMPLY WITH FBC 1014 |
| | 7) PLEASE SHOW RAMP SLOPE TO COMPLY WITH FBC 1012 |
| | 8) PLEASE SHOW STAIR DETAILS TO COMPLY WITH FBC 1011 |
| | 9) PLEASE PROVIDE ROOF/CEILING FRAMING PLAN SHOWING |
| | LAYOUT, STRAPPING DETAILS, UPLIFT REQUIREMENTS ETC. - |
| | FBC 2308 |
| | 10) PLEASE PROVIDE THE STRUCTURAL DETAILS FOR THE NEW |
| | EXTERIOR WALLS. FBC 2304 |
| | 11) PLEASE SHOW THE WIND DESIGN PARAMETERS USED - FBC |
| | 1603.1.4 (WIND SPEED, RISK CAT., EXPOSURE) |
| | 12) PLEASE SHOW ACCESSIBLE DOOR CLEAR FLOOR SPACE TO |
| | COMPLY WITH FBC ACCESSIBILITY 404.2.4 MANEUVERING |
| | CLEARANCES. |
| | 13) PLEASE SHOW BATHROOMS AND KITCHENS TO COMPLY WITH |
| | ACCESSIBILITY PER FBC ACCESSIBILITY (SHOW ALL HEIGHTS |
| | AND SIZES FOR MIRRORS, SINKS, COUNTER TOPS, GRAB BARS, |
| | DISPENSERS, CLEAR FLOOR SPACE SIZES ETC.) |
| | 14) PLEASE SHOW THE GUARD RAIL DETAILS AT THE LOFT TO |
| | COMPLY WITH FBC 1015 AND 1607 |
| | 15) PLEASE SHOW WALL, FLOOR AND CEILING INSULATION TO |
| | COMPLY WITH FBC ENERGY CODE |
| | 16) PLEASE SHOW THE ATTIC VENTILATION TO COMPLY WITH |
| | FBC 1503.5 |
| | 17) PLEASE PROVIDE COMPLETE MIAMI DADE OR FLORIDA STATE |
| | PRODUCT APPROVALS FOR THE NEW EXTERIOR WINDOWS AND |
| | DOORS. |
| | 18) PLEASE PROVIDE COMPLETE MIAMI DADE OR FLORIDA STATE |
| | PRODUCT APPROVALS FOR THE ROOFING SYSTEM. |
| | 19) PLEASE SHOW THE COMPONENTS AND CLADDING REQUIRED |
| | WIND LOADS PER FBC 1609 |
| | 20) PLEASE PROVIDE A DOOR AND WINDOW SCHEDULE. |
| | 21) PLEASE SHOW SMOKE DETECTOR LOCATIONS, FIRE ALARMS, |
| | SPRINKLERS ETC TO COMPLY WITH - FBC 420 |
| | 22) PLEASE SHOW FOUNDATION APRON TO COMPLY WITH FBC |
| | APPENDIX F101.6.1 |
| | 23) PLEASE SHOW THE MEZZANINE (LOFT) TO COMPLY WITH FBC |
| | 505 (SIZE, EGRESS, OPENNESS ETC) |
| | 24) PLEASE PROVIDE REAR DECK STRUCTURAL DETAILS. |
| | |
| | |