| 2021-03-26 16:29:09 | 3RD REVIEW FBC-2020 MECHANICAL |
| | PERMIT-20110707 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE |
| | FBC M- FLORIDA MECHANICAL CODE |
| | FBC EC- FLORIDA ENERGY CONSERVATION |
| | FBC FG- FLORIDA FUEL GAS |
| | FBC EX- FLORIDA EXISTING BUILDING CODE |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: APPROVED WITH THE FOLLOWING |
| | PREVISO: NOTE (5) OF THE MECHANICAL REVIEWER?S COMMENTS |
| | WILL NEED TO BE ADDRESSED BY 04/09/2021 |
| | |
| | 1) AS OF THIS DATE (03-26-2021) THERE HAVE BEEN NO |
| | MECHANICAL PERMITS PULLED FOR THE MECHANICAL SYSTEMS |
| | FOR THIS PROJECT. |
| | |
| | 2) CHRIS COLE?S COMMENT ON 04/22/2019: 1) IN ACCORDANCE |
| | WITH THE ARCHITECT'S NARRATIVE, THE KITCHEN COOKING |
| | APPLIANCES AND EQUIPMENT, THE KITCHEN HOODS AND FIRE |
| | SUPPRESSION SYSTEMS WILL BE DONE UNDER SEPARATE PERMIT. |
| | AS A RESULT, THE NARRATIVE INDICATES GAS-FIRED COOKING |
| | APPLIANCE SUBMITTALS, COMBUSTION AIR CALCULATIONS, AIR |
| | BALANCE CALCULATIONS, AND MAKE UP AIR TEMPERATURE |
| | COMPLIANCE WILL ALSO BE DEFERRED TO A FUTURE DATE. |
| | PLEASE PLACE LARGE BOLD NOTES ON THE PLAN TO INDICATE |
| | THIS FOR PUBIC RECORD AND FOR THE CONTRACTORS IN THE |
| | FIELD. |
| | |
| | 3) KITCHEN HOODS AND EQUIPMENT MUST BE SUBMITTED |
| | SEPARATELY FOR REVIEW AND PERMITTING. HOOD PLANS HAVE |
| | BEEN LOCKED AND WILL NOT BE PRINTED WITH THIS VERSION. |
| | PLEASE CONTACT THE PERMIT LIBRARIAN AT |
| | [email protected] TO HAVE THE HOOD SHEETS REMOVED |
| | FROM THIS SUBMITTAL. |
| | |
| | 4) REFRIGERATION EQUIPMENT MUST BE SUBMITTED SEPARATELY |
| | FOR REVIEW AND PERMITTING. REFRIGERATION PLAN HAS BEEN |
| | LOCKED AND WILL NOT BE PRINTED WITH THIS VERSION. |
| | PLEASE CONTACT THE PERMIT LIBRARIAN AT |
| | [email protected] TO HAVE THE REFRIGERATION SHEET |
| | REMOVED FROM THIS SUBMITTAL. |
| | |
| | 5) PLEASE PROVIDE OUTDOOR AIR CALCULATIONS FOR EACH USE |
| | OF SPACE IN THIS BUILDING. EXAMPLE: 1ST FLOOR HAS A BAR |
| | AREA BESIDE OF THE DINING ROOM/LOUNGE IT SHOULD BE |
| | CALCULATED AT 100 OCCUPANTS PER 1000 SQ FT. THE |
| | VESTIBULE SHOULD BE COUNTED AS A LOBBY. THERE IS ALSO A |
| | STAGE IN THIS AREA WHICH SHOULD BE COUNTED AS 70 |
| | OCCUPANTS PER 1000 SQ.FT. THE 2ND FLOOR HAS A |
| | LOBBY/PREFUNCTION AREA THAT NEEDS MORE OUTDOOR AIR THAN |
| | A LOBBY. THE STAGE ON THE MEZZANINE SHOULD BE COUNTED |
| | AS 70 OCCUPANTS PER 1000 SQ.FT.. THE RELAX AREA SHOULD |
| | BE COUNTED AS PART OF THE LOBBY/PREFUNCTION AREA. THE |
| | ROOF HAS A ROOF TOP BAR THAT ISN?T SHOWN AT ALL IN THE |
| | OUTDOOR AIR CALCULATIONS. ONCE THESE AREAS HAVE CHANGED |
| | THE AIR BALANCE SCHEDULES SHOULD BE UPDATED. |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD |
| | SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER |
| | SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN |
| | THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS |
| | PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS |
| | PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR |
| | UPDATED. |
| | |