| 2021-03-04 13:57:08 | 2ND REVIEW FBC-2017 PLUMBING |
| | PERMIT- 20110707 |
| | 3/4/2021 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDENTS TO THE FBC SIXTH EDITION |
| | 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | BASED ON THE RESUBMITTED PLANS AND NARRATIVE RESPONSES, |
| | FAILED COMMENTS FROM THE 1ST REVIEW ARE LISTED BELOW. |
| | REMARKS IN CAP LETTERS HAVE BEEN ADDED FOR FURTHER |
| | CLARIFICATION. |
| | |
| | 13) FAILED. P103 & P503: REFER TO SECTION 1107.1 FBC P |
| | AND VERIFY THE ROOFS ARE DESIGNED FOR THE MAXIMUM |
| | POSSIBLE DEPTH OF WATER THAT WILL POND THEREON AS |
| | DETERMINED BY THE RELATIVE LEVELS OF ROOF DECK AND |
| | OVERFLOW WEIRS, SCUPPERS, EDGES OR SERVICEABLE DRAINS |
| | IN COMBINATION WITH THE DEFLECTED STRUCTURAL ELEMENTS. |
| | IN DETERMINING THE MAXIMUM POSSIBLE DEPTH OF WATER, ALL |
| | PRIMARY ROOF DRAINAGE MEANS SHALL BE ASSUMED TO BE |
| | BLOCKED. THE MAXIMUM POSSIBLE DEPTH OF WATER ON THE |
| | ROOF SHALL INCLUDE THE HEIGHT OF THE WATER REQUIRED |
| | ABOVE THE INLET OF THE SECONDARY ROOF DRAINAGE MEANS TO |
| | ACHIEVE THE REQUIRED FLOW RATE OF THE SECONDARY |
| | DRAINAGE MEANS TO ACCOMMODATE THE DESIGN RAINFALL RATE |
| | AS REQUIRED BY SECTION 1106. THE NARRATIVE REFERENCES |
| | SHEETS A1.03A, A1.03B, & A1.03C. I WAS NOT ABLE TO |
| | LOCATE THE SHEETS IN THE SET, HOWEVER THE ROOF DRAINAGE |
| | PLANS ARE SHOWN ON SHEET A1.04. THE SHEET IS |
| | INCOMPLETE. REFER TO THE SCHEDULES ON THE PLANS AND |
| | LABEL THE 01. 02, 03, 04 AREAS ON THE PLANS, AND ALL |
| | ROOF DRAIN LOCATIONS ON FLAT ROOFS. PLEASE NOTE SOME DS |
| | LOCATIONS ARE NOT MARKED IN ACCORDANCE WITH MARKS SHOWN |
| | IN THE SCHEDULE. |
| | |
| | 14) FAILED. P103, P104 & P503: PROVIDE SECONDARY OR |
| | EMERGENCY OVERFLOW ROOF DRAIN SYSTEMS INCLUDING |
| | CALCULATIONS AND OVERFLOW DRAIN DETAILS- SEE SECTION |
| | 1108 FBC P. SEE COMMENT NOTES FOR #13. |
| | |
| | 15) FAILED. P503: PROVIDE A CONDENSATE DISPOSAL RISER- |
| | SECTION 107.2.1 WPB. THE RISER IS INCOMPLETE AND DOES |
| | NOT INCLUDE ALL THE FAN COIL UNITS THROUGHOUT THE |
| | FLOORS. |
| | |
| | 18) FAILED P501, SANITARY D: PROVIDE CLEANOUTS AT THE |
| | BASES OF THE 3 IN. STACKS. A) THE REVISION CLOUD IS |
| | BLOCKING THE TEXT OF NOTE 8. PLEASE PROVIDE THE CLOUD |
| | AROUND THE NUMBERS ONLY. B) ISO C: LABEL THE ISO AS |
| | GREASE WASTE ISOMETRIC AND LABEL THE GREASE WASTE LINE- |
| | GW. REMOVE THE HANDSINKS AND FLOOR SINK BY THE ICEMAKER |
| | AND ROUTE THE DRAINAGE TO THE SANITARY LINE. PLEASE SEE |
| | REMARKS UNDER NEW COMMENT #2 BELOW. |
| | |
| | 19) FAILED. P601: PLEASE PROVIDE INDIRECT WASTE |
| | PLUMBING PIPING DETAILS FOR THE 2 AND 3-COMPARTMENT |
| | SINKS, THE DISHWASHER, AND ALL OTHER DISHWASHING SINKS |
| | AND FOOD HANDLING EQUIPMENT OR FIXTURES- REFER TO |
| | SECTIONS 802.1, 802.1.1, 802.1.7, 802.1.8, AND 802.2 |
| | FBC P. A MINIMUM 4 IN. AIR GAP IS REQUIRED FOR A 2 IN. |
| | WASTE PIPE- SECTION 802.2.1 FBC P. |
| | |
| | 20) FAILED. P701: THE 2 AND 3-COMPARTMENT SINKS APPEAR |
| | TO BE MISSING FROM THE SCHEDULE- SECTION 107.2.1 WPB. |
| | ALL OTHER FIXTURES FROM THE KITCHEN CONSULTANT LIST ARE |
| | INCLUDED IN THE SCHEDULE. PLEASE NOTE THAT THE |
| | 3-COMPARTMENT SINK IS NOT IN THE KITCHEN SCHEDULE ON |
| | A4.04. |
| | |
| | 21) FAILED. P701: ITEM #35 WHICH IS REFERENCED IN ITEM |
| | #36 & 37 IS MISSING FROM THE SCHEDULE- SECTION 107.2.1 |
| | WPB. SEE COMMENT # 20 REMARKS. |
| | |
| | 25) FAILED. P-202, P403, P404 & P502: SHOW SHUTOFF |
| | VALVES FOR THE RISERS UP TO THE HOSE BIBS, BAR AND |
| | BATHROOMS- SECTION 606.1 FBC P. VALVES NOT SHOWN. NOTE |
| | 112 IS REQUIRING AN IN-LINE BF PREVENTER FOR THE HOSE |
| | BIB. REFER TO SECTION - 608.15.4.2 HOSE CONNECTIONS. |
| | SILLCOCKS, HOSE BIBBS, WALL HYDRANTS AND OTHER OPENINGS |
| | WITH A HOSE CONNECTION SHALL BE PROTECTED BY AN |
| | ATMOSPHERIC-TYPE OR PRESSURE-TYPE VACUUM BREAKER OR A |
| | PERMANENTLY ATTACHED HOSE CONNECTION VACUUM BREAKER. |
| | |
| | NEW COMMENTS BASED ON RESUBMITTED PLANS. |
| | |
| | 1) SHEETS P000, P101: LABEL THE GREASE WASTE LINE- (GW) |
| | AND THE SANITARY LINE- (SAN) PER THE SYMBOL LIST. THE |
| | GREASE WASTE IS MARKED ST AND MANY OF THE SANITARY |
| | LINES ARE NOT MARKED. |
| | |
| | 2) P101, P401, A4.04: IN COMPLIANCWE WITH SECTION |
| | 1003.3.1 FBC P, THE CHIEF PLUMBING INSPECTOR IS NOT |
| | PERMITTING HANDSINKS TO BE DRAINED INTO A GREASE |
| | INTERCEPTOR- PLEASE CORRECT THE PLANS SECTION 1003.3.1 |
| | FBC P. THE PLAN ALSO SHOWS CLEAR WATER WASTE FROM FLOOR |
| | SINKS BY THE ICE MACHINE (K12) DRAINING INTO THE GREASE |
| | WATE LINE WHICH IS NOT PERMITTED. PLEASE ROUTE THE |
| | DRAINAGE FROM THESE FIXTURES TO THE SANITARY. |
| | |
| | 2) P102: LABEL THE SAN DOWN IN THE CHASE. |
| | |
| | 3) P103: LABEL THE SAN DOWN IN THE MEN'S AND WOMEN'S |
| | RESTROOMS. |
| | |
| | 4) P401, DETAIL C: LABEL THE GREASE WASTE LINE- (GW) |
| | PER THE SYMBOL LIST. IT IS MARKED ST. |
| | |
| | 5) P501: A) THE REVISION CLOUD IS BLOCKING THE TEXT OF |
| | NOTE 8. PLEASE PROVIDE THE CLOUD AROUND THE NUMBERS |
| | ONLY. B) ISO C; LABEL THE ISO AS GREASE WASTE ISOMETRIC |
| | AND LABEL THE GREASE WASTE LINE- GW. REMOVE THE |
| | HANDSINKS AND FLOOR SINK BY THE ICEMAKER AND ROUTE THE |
| | DRAINAGE FROM THESE FIXTURES TO THE SANITARY LINE. |
| | |
| | 6) P701: EQUIPMENT SCHEDULES FOR TEA-1 AND TEA-2 ARE |
| | NOT PROVIDED. PLEASE NOTE THAT THERMAL EXPANSION TANKS |
| | SHALL BE INSTALLED ON THE WH COLD WATER INLET PIPE AT A |
| | POINT THAT IS DOWNSTREAM OF ALL CHECK VALVES, PRESSURE |
| | REDUCING VALVES AND BACKFLOW PREVENTERS. |
| | |
| | 7) P701: IT IS ACKNOWLEDFGED THAT THE GREASE |
| | INTERCEPTOR SHALL BE SEPARATELY PERMITTED. COMPLETE |
| | PLANS, CALCULATIONS, AND PRODUCT SPECIFICATIONS SHALL |
| | BE SUBMITTED. PLEASE NOTE THAT THE CURRENT CALCULATIONS |
| | DO NOT INCLUDE THE 2-COMPARTMENT SINK, AND THE DRAINAGE |
| | FROM THE FLOOR SINKS SERVING COOKING APPLIANCES, AND |
| | THE TRENCH DRAIN. |
| | |
| | 8) P702: PLEASE ADD A BACKFLOW PREVENTER FOR THE WATER |
| | FILTRATION SYSTEM FOR PROTECTION AGAINST CONTAMINATION- |
| | SECTION 608.3 FBC P. |
| | |
| | 9) IRR-1: BACKFLOW PREVENTERS ARE REQUIRED TO PROTECT |
| | THE POTABLE WATER SYSTEM PER SECTION 608.1 FBC P. THE |
| | POTABLE WATER FOR THE BUILDING IS CITY SUPPLIED, AND |
| | THE IRRIGATION WATER IS WELL SUPPLIED. PLEASE CLARIFY |
| | THE NEEED FOR THE BF PREVENTER. IS IT FOR PROTECTION OF |
| | THE PUMP, THE WELL WATER? |
| | |
| | 10) P-503: PLEASE SEE SEPARATE GAS REVIEW COMMENTS. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL/PLUMBING PLANS EXAMINER |